The text of a spec sheet · part 5 of 7
1771 Digital I/O AC Input and Output Modules Product Data, pages 37 to 45
Pages 37 to 45 of 61
The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-OD, Allen-Bradley 1771-OD16, Allen-Bradley 1771-ON and Allen-Bradley 1771-OND
Page 37
36
1771 Digital I/O AC Input and Output Modules
AC Output Module (Cat. No. 1771-OAN)
Status Indicators
Specifications (Cat. No. 1771-OAN) Outputs per module Module Location Voltage Range Nominal Voltage Maximum Output Current Per Point Per Group Per Module Maximum Surge Current Minimum Load Current Maximum On-state Voltage Drop Maximum Off-state Leakage Current Output Signal Delay Off to On On to Off Power Dissipation Thermal Dissipation Isolation Voltage Backplane Current Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
Wire Size Category
Keying Fuses Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
.2
32 (4 groups of 8) 1771-A1B thru -A4B or later I/O Chassis 1771-AM1, -AM2 I/O Chassis 80 to 265V ac, 47-63Hz 120V ac 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
1.0A at 30oC; Derate linearly to 0.3A at 60oC 2.0A at 30oC; Derate linearly to 0.6A at 60oC 8.0A at 30oC; Derate linearly to 2.4A at 60oC 10A for 25ms at 1Hz and 30oC 10A for 25ms at 0.5Hz and 60oC 10mA per output 1.5V ac (rms) @ 1A 2.3mA per output @ 230V ac, 60Hz 1.2mA per output @ 120V ac, 60Hz 1.0ms maximum 9.3ms @ 60Hz, 11.0ms @ 50Hz (maximum) 16.2W (max); 1.0W (min) 55.4 BTU/hr (max); 3.4 BTU/hr (min) Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142. 800mA @ 5V dc maximum 0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded (max)2 3/64 inch (1.2mm) insulation (max) 11 Between 16 and 18 Between 22 and 24 Four 4.0A, 250V normal blow fuses (1 per group) 1771-WN 7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-5.31
You use this conductor-category information for planning conductor routing as described in the system-level installation manual 14 gauge wire connected to all terminals may not allow the cover on the field wiring arm to close. A smaller gauge wire may be required.
00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
Status Indicators (red)
11853-I
Sample Connection Diagram Driving a 1771-IAN Module with a 1771-OAN Module AC (85-138V) Input Module (Cat. No. 1771-IAN)
AC (80 -265V) Output Module (Cat. No. 1771-OAN)
2 4 6
2 4 6
8 10 12
8 10 12 14
14 16 18 20 22 24
16 18 20 22 24
26 28
26 28
30 32 34 36
30 32 34 36
38
38
40
40
L2 ac Low
Publication 1771-2.182 - July 1996
12221-I
L1 ac high
Page 38
1771 Digital I/O AC Input and Output Modules
37
Isolated AC Output Module (Cat. No. 1771-OD Series C)
Simplified Schematic +5V
Output 1.2K Status Indicator LED Backplane Logic Circuitry
Opto Isolation
196K
Neon Indication (fuse blown)
196K
100 Rect & Filter Circuit
0.05µF 22
L1
5.0 Amp Fuse MOV 175V
100
Output 18515
Application Notes Device Compatibility. An output from this module can drive an Allen- Bradley Size 5 motor starter provided its supply voltage does not drop below 92V ac. Output Leakage Current. The switching device in the output circuit is a triac. There is a small leakage current in the off state due to both triac and output snubber circuits. The maximum leakage current per output is 5mA at 138V ac. Nominal leakage current is 1mA. The on-state voltage drop across the output terminals is no more than 2.0V ac at 100mA.
Connection to Input Modules. You can use the output of (Cat. no. 1771-OD) to drive input modules (Cat. No. 1771-IA, -IA2, -ID, -IAD). However, you must connect a 2.5K ohm 10W resistor between the output and L2 (common). As an alternative you can connect an electrocube snubber (part number RG-1676-1). Inputs configured with the output module are not isolated from each other unless you are using the Cat. No. 1771-ID module. Minimum/Maximum Load Current. The triac needs a minimum of 60mA load current to stay on. If your device pulls less than 60mA, the triac may not operate. The total continuous current the module supports is 6A (2A maximum per channel). If this rating is exceeded, the module overheats and damage may occur. Status Indicators. The module has 12 status indicators. The top six red indicators show the state of each output and are driven by the logic circuitry on the programmable controller side of the module These indicators light when their corresponding outputs are energized. The bottom six indicators display a blown-fuse condition at the respective output regardless of the state of the output. These outputs are driven by the user's power supply.
Connection Diagram Output 0A
1
Output 0B
2
Output 1A
3
Output 1B
4
Output 2A
5
Output 2B
6
Output 3A
7
Output 3B
8
Output 4A
9
Output 4B
10
Output 5A
11
Output 5B
12
L1 ac high
Output Device
L2 ac low
10593-I
Publication 1771-2.182 - July 1996
Page 39
38
1771 Digital I/O AC Input and Output Modules
Isolated AC Output Module (Cat. No. 1771-OD Series C) Specifications (Cat. No. 1771-OD/C) Outputs per Module Module Location Voltage Rating Output Current Rating (per channel) Surge Current (maximum) Load Current (minimum) On-state Voltage Drop Off-state Leakage Current Signal Delay Off to On On to Off Power Dissipation Thermal Dissipation Backplane Current Isolation Voltage Maximum Cable Length Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
Wire Size Category
6 1771 I/O Chassis 92 to 138V ac @ 47-63 Hz 2A per output (not to exceed 6A per module) 20A maximum for 100ms Repeatable every 5 seconds 60mA per output 2V ac (max) at 100mA 5mA (max) per output at 138V ac 1.0ms 8.3ms @ 60Hz 13.2 Watts (max); 1.2 Watts (min) 45.2 BTU/hr (max); 4.1 BTU/hr (min) 225mA Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142. 1000 ft (304.8 m)
14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11 Between 4 and 6 Between 30 and 32
Fuse
5A, 250V 3AG normal blow fuses (1 per output) Buss AGC-5, Littelfuse 312005
Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
ISOLATED AC OUTPUT
00 01 02 03 04 05 00 01 02 03 04 05
Output Status Indicators (red)
Fuse-Blown Indicators
10595-I
Sample Connection Diagram Driving a 1771-IAD Module with a 1771-OD Module AC/DC (120V) Input Module Cat. No. 1771-IAD
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)
Keying
Field Wiring Arm
Status Indicators
AC (120V) Isolated Output Module Cat. No. 1771-OD L1 ac High 1
3
7-9 inch-pounds
4
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17
2
Catalog Number 1771-WD • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.12
Input 00 Input 01
5 6 7 8 9
2.5K, 10W load resistor
10 11 12
L2 ac Low 10594-I
Publication 1771-2.182 - July 1996
Page 40
1771 Digital I/O AC Input and Output Modules
39
Isolated AC Output Module (Cat. No. 1771-OD16)
Simplified Schematic
+5V 680 Fuse Blown Indicator
Output Status 1.2K Indicator LED Backplane Logic Circuitry
Opto Isolation
Opto Isolation
3.0 Amp Fuse
10 41
L1
MOV 100
.033µF Output 18515
Application Notes
Connection Diagram
Device Compatibility. An output from this module can drive an Allen-Bradley Size 5 motor starter provided its supply voltage does not drop below 92V ac.
ac high
L1
Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. Connection to Input Modules. You can use an output of the 1771-OD16 module to drive an input of a 120V ac input module (1771-IA, -IA2, IAD, -ID or ID16). Inputs configured with the output module are not isolated from each other. Status Indicators. The front panel has one green active indicator, one red fuse-blown indicator and 16 red status indicators. The active indicator lights when the module has started up and successfully initialized. The fuse-blown indicator lights when a fuse has cleared or been removed and the channel associated with that fuse has been turned The fuse-blown circuit will not operate if the applied line voltage is above the module's spe-cified minimum on-state voltage, and the output load current is less than or equal to 5mA. The fuse-blown indicator will reset after the fuse has been replaced and chassis power has been recycled. The indicators are provided for field side indication of individual outputs.
Alternate Output Device Location
Output Device
L1 - 0 L1 - 1 L1 - 2 L1 - 3 Not Used L1 - 4 L1 - 5 L1 - 6 L1 - 7 Not used L1 - 10 L1 - 11
2 4 6 8 10 12 14 16 18 20 22 24
L1 - 12 L1 - 13 Not used L1 - 14 L1 - 15 L1 - 16 L1 - 17
26 28 30 32 34 36 38
Not used
40
Output 0 Output 1 Output 2 Output 3 Not used Output 4 Output 5 Output 6 Output 7 Output Device Not used Output 10 Output 11 Output 12 Output 13 L2 Not used ac low Output 14 Output 15 120V ac Output 16 Supply Output 17 Not used L1 ac high
10542-I
Publication 1771-2.182 - July 1996
Page 41
40
1771 Digital I/O AC Input and Output Modules
Isolated AC Output Module (Cat. No. 1771-OD16) Specifications (Cat. No. 1771-OD16) Outputs per Module Module Location Voltage Rating Current Rating (per channel)
16 1771-A1B thru -A4B or later I/O Chassis 74 to 138V ac, 47-63Hz 5mA-2A continuous (max) 20A surge for 100ms; repeatable every 2 seconds 8A continuous per module (maximum)
Power Rating On-state Voltage Drop (each output) On-state Load Current Off-state Leakage Current
3 Watts per output (max) @ 2A 5.7V rms (max.) @ load current <70mA 1.5V rms (max.) @ load current >70mA 5mA minimum 3.0mA max. @ 138V ac; 1.5mA (typical) @ 120V ac 25V ac maximum; 15V ac typical
Zero Voltage Turn-on Signal Delay Times Off to On On to Off Power Dissipation Thermal Dissipation Backplane Current Isolation Voltage Maximum Cable Length
8.8ms @ 60Hz max; 10.6ms @ 50Hz max 8.8ms @ 60Hz max; 10.6ms @ 50Hz max (zero cross switching) 13.0 Watts (max); 1.0 Watts (min) 44.4 BTU/hr (max); 3.4 BTU/hr (min) 200mA maximum Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142. 1000 ft (304.8 m)
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
Status Indicators
ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 FUSE
ACTIVE Indicator (green) Output Status Indicators (red) Fuse Blown Indicator (red)
Sample Connection Diagram Driving a 1771-ID16 with a 1771-OD16 Input Module (Cat. No. 1771-ID16)
Output Module (Cat. No. 1771-OD16)
2
2
4
4
6
6
8
8
10
10
12
12
14
14
16
16
18
18
20
20
22
22
24
3A 2AG Slo-Blo fuses (1 per output), Littelfuse P/N 229003
24
26
26
28
Optional Fuse Kit
Cat. No. 1771-FE (contains 5 fuses)
28
30
30
Field Wiring Arm
Catalog Number 1771-WN
32
32
34
34
36
36
38
38
40
40
Conductors
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum2
Wire Size
3/64 inch (1.2mm) insulation maximum 11
Category Keying
Between 22 and 24 Between 34 and 36
Fuses
Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
7-9 inch-pounds
• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Instructions 1 2
1771-5.21
You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 14 gauge wire connected to all terminals may not allow the field wiring arm cover to close. A smaller gauge wire may be required.
Publication 1771-2.182 - July 1996
10544-I
L2 ac low
120V ac Supply
L1 ac high
10559-I
Page 42
1771 Digital I/O AC Input and Output Modules
41
Isolated AC Output Module (Cat. No. 1771-ODD)
Simplified Schematic
Fuse Blown Indication
Output Indication (logic)
System Circuitry
Opto Isolation Fuse 3Amp L1
Opto Isolation 51
100
.022µF 47K
MOV
Isolated Output
10 Output 18513
Application Notes
Connection Diagram
Device Compatibility. An output from this module can drive an Allen-Bradley Size 5 motor starter, provided its supply voltage does not drop below 92V ac.
L1 ac high
Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. Connection to Input Modules. You can use this module (Cat. No. 1771-ODD) to drive input modules (Cat. Nos. 1771-IA, -IA2, -IAD, -ID). Inputs configured with the output module are not isolated from each other unless you are using the 1771-ID or 1771-ID16. Minimum/Maximum Load Current. The 1771-ODD module is designed for a 10mA minimum current on each output circuit. The total continuous current the module supports is 8A (2A maximum per channel). If this rating is exceeded, the module over heats and damage may occur. Status Indicators. The module has 32 status indicators. The 16 indicators on the left side show the state of each output and are driven by the logic circuitry on the programmable controller side of the module. They light when their corresponding outputs are energized. The 16 indicators on the right side display a blown-fuse condition. A fuse-blown indicator displays a blownfuse condition at the respective output regardless of the state of the output and are driven by the user's power supply.
L1 - 0 L1 - 1
2
L1 - 2
6
L1 - 3
8
Not Used
10
L1 - 4
12
L1 - 5
14
L1 - 6
16
L1 - 7
18
Not used
20
L1 - 10
22
L1 - 11
24
L1 - 12
26
L1 - 13
28
Not used
30
L1 - 14
32
L1 - 15
34
L1 - 16
36
L1 - 17
38
Not used
40
4
Output 0 Output 1 Output 2 Output 3 Not used Output 4 Output 5
Output Device
Output 6 Output 7 Not used Output 10 Output 11 Output 12 Output 13 Not used
L2
Output 14 ac low
Output 15 Output 16
120V ac Supply
Output 17 Not used
L1 ac high
10944-I
Publication 1771-2.182 - July 1996
Page 43
42
1771 Digital I/O AC Input and Output Modules
Isolated AC Output Module (Cat. No. 1771-ODD) Specifications (Cat. No. 1771-ODD) Outputs per Module Module Location Voltage Rating Current Rating (per channel)
On-state Voltage Drop (each output) On-state Load Current Off-state Leakage Current Signal Delay Off to On On to Off
16 1771-A1B thru -A4B or later I/O chassis, 1771-AM1, -AM2 I/O Chassis 85 to 138V ac, 47-63Hz 10mA-2A continuous (max) 20A surge for 100ms; repeatable every 2 seconds 8A per module maximum 6.5V RMS (max.) @ load current <65mA 1.5V RMS (max.) @ load current >65mA 10mA minimum 3.0mA @ 138V ac; 1.5mA @ 120V ac 8.8ms @ 60Hz max; 10.6ms @ 50Hz max 8.8ms @ 60Hz max; 10.6ms @ 50Hz max (zero cross switching)
Power Dissipation Thermal Dissipation Backplane Current Isolation Voltage
14.2 Watts (max); 0.1 Watts (min) 48.5 BTU/hr (max); 0.4 BTU/hr (min) 420mA 5V dc + 5% Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Cable Length (maximum)
1000 ft (304.8 m)
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)
Conductors
14 gauge (2mm2) stranded maximum2 3/64 inch (1.2mm) insulation maximum 11
Wire Size Category
Keying
Between 4 and 6 Between 30 and 32
Fuses
3A 2AG Slo-Blo fuses (1 per output) Littelfuse part number 229003
Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1 2
Catalog Number 1771-WN 7-9 inch pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-5.20
You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 14 gauge wire connected to all terminals may not allow the field wiring arm cover to close. A smaller gauge wire may be required.
Status Indicators
Output Status Indicators (on left)
00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
Fuse-blown Indicators (on right)
00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
10946-I
Sample Connection Diagram Driving a 1771-IAD with a 1771-ODD AC (120V) Isolated Output Module
AC/DC (120V) Input Module
Cat. No. 1771-ODD
Cat. No. 1771-IAD
L1 ac high
Output 0 Output 1 Output 2 Output 3 Not used Output 4 Output 5 Output 6 Output 7 Not used Output 10
L1 - 0 L1 - 1 L1 - 2 L1 - 3 Not Used L1 - 4 L1 - 5 L1 - 6 L1 - 7 Not used L1 - 10 L1 - 11
Output 11 Output 12 Output 13 Not used Output 14 Output 15 Output 16 Output 17 Not used
L1 - 12 L1 - 13 Not used L1 - 14 L1 - 15 L1 - 16 L1 - 17 Not used
Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 L2 ac low
L1
120V ac Supply
L2 10945-I
Publication 1771-2.182 - July 1996
Page 44
1771 Digital I/O AC Input and Output Modules
43
Isolated AC Output Module (Cat. No. 1771-ODZ)
Simplified Schematic Fuse 5Amp
100 Backplane Logic Circuitry
Opto Isolation
Rect & Filter Circuit
Output Indication (logic)
L1 200K
22
.022µF
100
Indication (fuse blown)
MOV 175V
200K
Output 18512
Application Notes
.
Connection Diagram
Device Compatibility. Output from this module can drive an Allen-Bradley Size 5 motor starter, provided its supply voltage does not drop below 92V ac. Connection to Input Modules. You can use an output of this module (Cat. No.1771-ODZ) to drive an input of a 120V ac input module (Cat. Nos. 1771-IA, -IA2, -ID, -IAD, -ID16, -IAN) to indicate status of turning on a motor starter.
Output 0
1
L1, 0-1
2
Output 1
3
Minimum/ Maximum Load Current. The triac needs a minimum of 15mA load current to stay on. If your device pulls less than 15mA, the circuit may not operate. The total continuous current the module supports is 6A (2A maximum per channel). If this rating is exceeded, the module overheats and damage may occur.
Output 2
4
L1, 2-3
5
Status Indicators. The module has 16 status indicators. The red indicators show the state of each output and are driven by the logic circuitry on the programmable controller side of the module. They light when their corresponding outputs are energized. The 8 orange indicators display a fuse-blown condition at the respective output regardless of the state of the output and are driven by the user's power supply.
Output 3
6
Output 4
7
L1, 4-5
8
Output 5
9
Output 6
10
L1, 6-7
11
Output 7
12
Output Device
L1 ac high
(Actual wiring runs in this direction.)
L2 120V ac Supply ac low
10422-I
Publication 1771-2.182 - July 1996
Page 45
44
1771 Digital I/O AC Input and Output Modules
Isolated AC Output Module (Cat. No. 1771-ODZ) Specifications (Cat. No. 1771-ODZ) Outputs per Module Module Location Output Voltage Range Output Load Current (maximum) Maximum Surge Current per Output and Module Minimum Load Current On-state Voltage Drop (max) Off-state Leakage Current (max) Signal Delay Times Off to On On to Off Power Dissipation Thermal Dissipation Backplane Current Isolation Voltage Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors Wire Size Category Keying Fuse Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
8 1771 I/O Chassis 92 to 138V ac, 47 to 63Hz 2A per output, not to exceed 6A per module 20A for 100ms; repeatable every 5 seconds 15mA per output 1.6V maximum at 2A 2mA per output at 138V ac 1ms 8.3ms @ 60Hz 11.4 Watts (max.); 1.8 Watts (min.) per module 38.9 BTU/hr (max); 6.14 BTU/hr (min.) 350mA @ 5V dc + 5% Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142. 0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF) 5 to 95% without condensation 14 gauge (2mm2) stranded (max) 3/64 inch (1.2mm) insulation (max) 11 Between 4 and 6 Between 34 and 36 5A, 250V 3AG Normal Blow, Littelfuse part number 312005 Cat. No. 1771-WD 7-9 inch pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.130
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
Status Indicators
00 01 02 03 04 05 06 07
00 to 07 Status Indicators (Red)
F U S E B L O W N
Fuse-Blown Indicators 10424-I
Sample Connection Diagram Driving a 1771-IA Module with a 1771-ODZ Module Isolated AC Output Module (Cat. No. 1771-ODZ)
120V AC Input Module (Cat. No. 1771-IA) L1 ac High
1
A
2
O
3
1
4
2
5
3
6
4
7 8
5
9
6
10 11
7 B
12 L2 ac Low
10423-I
Publication 1771-2.182 - July 1996