Manual · Allen-Bradley
DC Output Driver Module Cat. No. 1771-OB Installation Data
Manual8 pagesPDF 71 KB
Installation data for the Allen-Bradley 1771-OB DC output driver module: handling, keying, wiring, status indicators, fuses and specifications.
Names · 1 model
The models it names
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Allen-Bradley installation data for the 1771-OB DC Output Driver Module, an 8-output dc module for the 1771 I/O chassis that drives dc motor starters, indicators and solenoids. It covers power requirements, electrostatic discharge handling, keying the I/O chassis, installing the module, wiring the 1771-WA field wiring arm (including driving a 1771-IB input module directly), reading the status indicators, replacing a fuse, and specifications.
Its parts
- To The Installer
- Pre-installation Considerations
- Power Requirements
- Initial Handling
- Installing Your Module
- Connecting Wiring to the Output Driver Module
- Interpreting the Status Indicators
- Replacing a Fuse
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley installation data (publication 1771-2.3, June 1990) for the 1771-OB DC output driver module. It explains power needs, chassis keying, installing and wiring the module, reading the status lights, replacing a fuse, and the module specifications.
- What it is
- DC output driver module with 8 outputs for a 1771 I/O chassis p. 8
- Voltage range
- 10 to 27 V dc p. 8
- Output current
- 1.5 A per output, 8 A max. per module p. 8
- Backplane current
- 165 mA at 5 V dc p. 1, 8
- Fuses
- One 2 A 8AG fuse per output p. 8
- Wiring arm
- 10 terminal field wiring arm, cat. no. 1771-WA, shipped with the module p. 8
- Surge current
- 4 A for 1 ms, repeatable every second p. 8
- Leakage, voltage drop
- 1 mA per output off-state; 2 V dc max. on-state drop p. 8
- Delay times
- Turn on/off 10 ms p. 8
- Isolation
- 1500 V ac (RMS) opto-electrical p. 8
- Operating temperature
- 0 to 60 C (32 to 140 F); storage -40 to 85 C p. 8
- Keying
- Between 4 and 6, and between 18 and 20 p. 8
- Wire size
- 14 gage stranded maximum p. 8
- Power dissipation
- 16.9 W max., 0.9 W min. p. 8
What this manual walks you through
- Keying an I/O chassis slot for the module p. 2
- Installing the module in a 1771 I/O chassis p. 3
- Wiring outputs and dc power to the field wiring arm p. 4
- Driving a 1771-IB input module directly from the outputs p. 5
- Reading the blown fuse and output status lights p. 6
- Replacing a blown fuse p. 7
Good to know
- Remove power from the chassis backplane and wiring arm before removing or installing the module. p. 3
- Reverse polarity or applying 120 V ac may damage the module. p. 5
- Wiring arm terminal numbers are not the same as the bit numbers that control the outputs. p. 4
- When driving a 1771-IB, power both modules from the same dc source. p. 5
- The module can be damaged by electrostatic discharge; handle it grounded and keep it in a static-shielded bag. p. 2
Questions this manual answers
What fuse does the 1771-OB use?
A 2 amp 8AG normal blow fuse, one for each output. p. 7
What voltage does the 1771-OB switch?
10 to 27 V dc, up to 1.5 A per output and 8 A per module. p. 8
Which wiring arm fits the 1771-OB?
The 10 terminal 1771-WA field wiring arm, which ships with the module. p. 4
How much backplane current does the 1771-OB draw?
165 mA from the chassis power supply. p. 1
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 1 part
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file