DC Output Driver Module Cat. No. 1771-OB Installation Data
To The Installer
This document provides information on: important pre–installation considerations power supply requirements initial handling procedures installing the module using the indicators for troubleshooting module specifications
Pre-installation Considerations
The 1771–OB module can control the following output devices: dc motor starters indicators solenoids
Power Requirements
Your module receives its power through the 1771 I/O chassis backplane from the chassis power supply. The module requires 165mA from the output of this supply. Add this to the requirements of all other modules in the I/O chassis to prevent overloading the chassis backplane and/or backplane power supply.
Page 2
Installation Data DC Output Driver Module Cat. No. 1771-OB Initial Handling
The dc output driver module is shipped in a static–shielded bag to guard against electrostatic discharge damage. Observe the following precautions when handling the module.
Electrostatic Discharge Damage ATTENTION: Under some conditions, electrostatic discharge can degrade performance or damage the module. Observe the following precautions to guard against electrostatic damage.
Wear an approved wrist strap grounding device, or touch a grounded object to discharge yourself before handling the module. Do not touch the backplane connector or connector pins. If you configure or replace internal components, do not touch other circuit components inside the module. If available, use a static–free work station. When not in use, keep the module in a static–shielded bag.
Installing Your Module
In this section we tell you how to key your I/O chassis, install your module and make your wiring connections.
Keying Your I/O Chassis Use the plastic keying bands, shipped with each I/O chassis, to key the I/O slots to accept only this type of module. The module circuit board is slotted in two places on the rear edge. The position of the keying bands on the backplane connector must correspond to these slots to allow insertion of the module. You can key any connector in an I/O chassis to receive this module except for the left–most connector reserved for adapter or processor modules. Place keying bands between the following numbers labeled on the backplane connector: Between 4 and 6 Between 18 and 20 You can change the position of these keys if system redesign and rewiring makes insertion of a different module necessary.
2
Page 3
Installation Data DC Output Driver Module Cat. No. 1771-OB
Installing the Output Driver Module To install the dc output driver module in your 1771 I/O chassis, follow the steps listed below. ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or installing an I/O module. Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.
1.
Turn off power to the I/O chassis.
2.
Position the module so that the circuit board on the rear of the module lines up with the top and bottom card guides in the chassis.
3.
Slide the module into the chassis. Do not force the module into its backplane connector. Apply firm, even pressure on the module to seat it properly.
4.
Snap the chassis latch over the top of the module to secure its position.
3
Page 4
Installation Data DC Output Driver Module Cat. No. 1771-OB Connecting Wiring to the Output Driver Module
Connections to the output driver module are made to the 10 terminal field wiring arm (cat. no. 1771–WA) shipped with the module. The wiring arm pivots on the I/O chassis to connect with the terminals on the front of the module. The wiring arm allows the module to be removed from the chassis without disconnecting the wiring. 1.
Make certain all power is removed from the module before making wiring connections.
2.
Swing the wiring arm up into position on the front of the module. The locking tab on the module will secure it into place.
3.
Make connections to the field wiring arm as shown in Figures 1 and 2. (Use the label on the front of the wiring arm to identify your wiring.) ATTENTION: The field wiring arm terminal identification is not the same as the number of the bit which controls that output.
Figure 1 Connection Diagram See Applicable Codes and Laws +DC
A
Output 0
0
Output 1
1
Output 2
2
Output 3
3
Output 4
4
Output 5
5
Output 6
6
Output 7
7
DC Common
B
(Actual wiring runs in this direction.)
+ DC Output Device -
+ DC Power Supply -
11394
You must supply dc voltage to terminal A on the field wiring arm. Supply dc common to output devices and terminal B on the field wiring arm. 4
Page 5
Installation Data DC Output Driver Module Cat. No. 1771-OB
ATTENTION: Proper polarity, as indicated in the connection diagram (Figure 1) must be observed with dc power connections. Reverse polarity, or incorrect application of 120V ac, may cause damage to the module.
Important: You can directly drive terminals on a DC (12–24V) Input Module (cat. no. 1771–IB) from terminals on the DC (12–24V) Output module (cat. no. 1771–OB) as shown in figure 2. Important: Use the same dc power source to power both modules to ensure that ground is at the same potential. Figure 2 Driving an Input module with an Output module DC (12-24V) Input Module (Cat. No. 1771-IB)
DC Output Driver Module (Cat. No. 1771-OB) 12-24V DC +DC
A
A
Not used
Output 0
0
0
Input 0
Output 1
1
1
Input 1
Output 2
2
2
Input 2
Output 3
3
3
Input 3
Output 4
4
4
Input 4
Output 5
5
5
Input 5
Output 6
6
6
Input 6
Output 7
7
7
Input 7
DC Common
B
B
DC Common
(Actual wiring runs in this direction.)
(See Applicable Codes and Laws)
11889-I
5
Page 6
Installation Data DC Output Driver Module Cat. No. 1771-OB Interpreting the Status Indicators
The front panel of your module contains 9 red status LED indicators (Figure 3). The top LED is the fuse blown indicator. It illuminates when a fuse has blown in the module. The remaining 8 red status indicators correspond to each of the 8 inputs. They illuminate when the corresponding output energizes. Figure 3 Status Indicators
Blown Fuse Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7
Status Indicators
11890-I
6
Page 7
Installation Data DC Output Driver Module Cat. No. 1771-OB
Replacing a Fuse
Each of the 8 outputs on the module are individually fused to protect the user’s power supply. Fuses are accessed by removing the front component–side cover on the module. If a blown fuse is indicated: 1.
Turn off system power. ATTENTION: Remove system power before removing or installing your module in the 1771 I/O chassis. Failure to observe this warning could result in damage to module circuitry and/or undesired operation with possible injury to personnel.
2.
Pivot the field wiring arm away from the module, and remove the module from the chassis.
3.
Remove the protective cover from the side of the module by removing the 2 screws.
4.
Replace the blown fuse with a 2 amp 8AG normal blow fuse.
5.
Reinstall the protective cover and reinstall the module in the chassis.
6.
Reposition the field wiring arm on the module.
7.
Restart system power.
7
Page 8
Installation Data DC Output Driver Module Cat. No. 1771-OB
Specifications
Outputs per Module
8
Module Location
1771 I/O chassis
Input Voltage Range
10 to 27V dc
Output Current
1.5A per output (not to exceed 8A per module)
Surge Current (maximum)
4A for 1ms, repeatable every 1 second
Off-state Leakage Current
1mA per output
On-state Voltage Drop
2V dc (maximum)
Delay Times
Turn on/off: 10ms
Power Dissipation
16.9 Watts (max.), 0.9 Watts (min.)
Thermal Dissipation
57.6 BTU/hr (max.), 3.0 BTU/hr (min.)
Backplane Current
165mA @ 5V dc +5%
Opto-electrical Isolation Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
Wire Size Category
1500V ac (RMS) 0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gage stranded maximum 3/64 inch insulation maximum 21
Keying
Between 4 and 6 Between 18 and 20
Fuses
2A 8AG (one per output)
Field Wiring Arm
Catalog Number 1771-WA
1 Refer to publication 1770-4.1, Programmable Controller Wiring and Grounding Guidelines.
With offices in major cities worldwide WORLD HEADQUARTERS Allen-Bradley 1201 South Second Street Milwaukee, WI 53204 USA Tel: (1) 414 382-2000 Telex: 43 11 016 FAX: (1) 414 382-4444
EUROPE/MIDDLE EAST/AFRICA HEADQUARTERS Allen-Bradley Europe B.V. Amsterdamseweg 15 1422 AC Uithoorn The Netherlands Tel: (31) 2975/43500 Telex: (844) 18042 FAX: (31) 2975/60222
Publication 1771–2.3 – June 1990 8
Supersedes publication 1771–2.3 –January 1984
As a subsidiary of Rockwell International, one of the world’s largest technology companies, Allen-Bradley meets today’s challenges of industrial automation with over 85 years of practical plant-floor experience. More than 11,000 employees throughout the world design, manufacture and apply a wide range of control and automation products and supporting services to help our customers continuously improve quality, productivity and time to market. These products and services not only control individual machines but integrate the manufacturing process, while providing access to vital plant floor data that can be used to support decision-making throughout the enterprise. ASIA/PACIFIC HEADQUARTERS Allen-Bradley (Hong Kong) Limited Room 1006, Block B, Sea View Estate 28 Watson Road Hong Kong Tel: (852) 887-4788 Telex: (780) 64347 FAX: (852) 510-9436
CANADA HEADQUARTERS Allen-Bradley Canada Limited 135 Dundas Street Cambridge, Ontario N1R 5X1 Canada Tel: (1) 519 623-1810 FAX: (1) 519 623-8930
LATIN AMERICA HEADQUARTERS Allen-Bradley 1201 South Second Street Milwaukee, WI 53204 USA Tel: (1) 414 382-2000 Telex: 43 11 016 FAX: (1) 414 382-2400
P/N955107–21 Printed in USA