For the Allen-Bradley 1771-OFE1

Page 11

Overview of the Analog Output Module What This Chapter Contains

About the Analog Output Module

Read this chapter to familiarize yourself with the analog output module. For information on

See page

The Analog Output Module (cat. no. 1771-OFE) is an intelligent block transfer module that converts binary or four-digit BCD values (supplied by your processor) to analog signals at its four module outputs. The module accomplishes the data transfer with block transfer programming. Block transfer write (BTW) programming moves up to 13 words of data from the processor to the module for digital to analog (D/A) conversion in one program scan. This information is converted to analog signals and is sent to the appropriate output channels. A block transfer read (BTR) moves five words of data from the module to the processor data table, if desired, for diagnostic purposes. The BTR is discussed in Chapter 7, “Diagnostics and Troubleshooting.” The module has a scaling feature that converts data sent to the module in engineering units to the proper analog signals. You may connect up to four analog output devices--such as valve positioners, motor speed controllers, signal converters or recorders--to the analog output module’s four channels. All analog output device inputs should conform to the voltage or current ratings of each module output channel.

)

Page 12

1-2

Module Features In the programmable controller system, the analog output module provides the following functions:

• • • • • four individually isolated differential outputs selectable scaling to engineering units selectable data format selectable voltage ranges (1771-OFE1 only) no external power required--power is drawn from the 1771 I/O chassis backplane. • requires only one I/O slot

Output Ranges There are three versions of the analog output module: Catalog Number

Module Output

Output Range

1771-OFE1

Voltage

1-5V dc 0-10V dc +10V dc

Selected by configuration jumpers

1771-OFE2

Current

4-20mA

Factory set

1771-OFE3

Current

0-50mA

Factory set

The voltage version (1771-OFE1) voltage output range is selected with configuration jumpers in the module: Note: The 1771-OFE1 is shipped with the selection jumpers in the +10V position. The current output versions (1771-OFE2 and -OFE3) are factory set.

Publication 1771-6.5.30 - November 1998

Page 13

1-3

How Analog Modules Communicate with Programmable Controllers

The processor transfers data to the module (block transfer write) and from the module (block transfer read) using BTW and BTR instructions in your ladder diagram program. These instructions let the processor send output values to the module, establish the module’s mode of operation (see illustration below) and receive status information from the module. Communication Between Processor and Module 2

5

1

3 + –

#('$('

4

-

('$(' *

1. The processor transfers your configuration and output data to the module via a block transfer write instruction. 2. The module converts the data into proportional voltage or current outputs. 3. These module outputs drive external analog devices. 4. When instructed by your ladder program, the processor performs a read block transfer of output values and module status. 5. The processor and module determine that the transfer was made without error. 6. Your ladder program can use and/or move the data (if valid) before it is written over by the transfer of new data in a subsequent transfer.

Accuracy Chapter Summary

The accuracy of your output module is described in Appendix A.

In this chapter you read about the functional aspects of the output module and how the module communicates with the programmable controller.

*

Page 14 read from a scan by OCR; it may hold reading errors

1-4

Publication 1771-6.5.30 - November 1998

Page 15

What This Chapter Contains

In this chapter, you will read about: For information on

See page

" 1, 1&3"0 1%" 2*-"/0 -"5 1%" 1,/0 1%" *,!2)" &")! /* 1 1%" /,2+! 1%"

Read this installation chapter completely before you install your module. Double check all connections and option selections before you begin programming your module.

! Compliance to European Union Directives

ATTENTION: To avoid injury to personnel and damage to equipment, disconnect and lockout all ac power supplies before installing and wiring the output module.

If this product has the CE mark, it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081-2EMC – Generic Emission Standard, Part 2 – Industrial Environment • EN 50082-2EMC – Generic Immunity Standard, Part 2 – Industrial Environment This product is intended for use in an industrial environment.

Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests.

6

Page 16

2-2

For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications: • Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1 • Guidelines for Handling Lithium Batteries, publication AG-5.4 • Automation Systems Catalog, publication B111 This equipment is classified as open equipment and must be mounted in an enclosure during operation to provide safety protection.

Calculating Power Requirements

The analog output module receives its power through the 1771 I/O chassis backplane from the chassis power supply. It does not require any other external power supply. When planning your system, you must consider the power usage of all modules in the I/O chassis to prevent overloading the I/O chassis backplane and/or power supply. Add this to the requirements of all other modules in the I/O chassis. Analog Module

!

#

Power Requirement

ATTENTION: Do not insert or remove modules from the I/O chassis while system power is ON. Failure to observe this rule could result in damage to module circuitry.

Page 17

2-3

Determine Module Location in the I/O Chassis

You can place your module in any I/O module slot of the I/O chassis with the following guidelines:

• Do not put the module in the same module group as a discrete high-density module. • Avoid placing output modules close to ac modules or high-voltage dc modules. • Group output modules together within an I/O chassis whenever possible to minimize noise interference from other modules. • You can put two output modules in the same module group.

Setting Module Configuration Jumpers

The module configuration jumpers consist of:

• the last state configuration jumper (all versions) • the voltage range configuration jumpers (1771-OFE1 only). Current Output Version Current version modules (1771-OFE2 and -OFE3) have all configuration jumpers installed and require no additional configuration. The configuration jumper for the Last State mode output level is in the default position (MID). See “Last State Configuration Jumpers” below.

Voltage Output Version If you are using the voltage output version, you need to set several configuration jumpers on the module’s circuit board. You must set these jumpers before you can proceed with configuring the module. When you set these jumpers, you configure each channel for one of the three voltage ranges listed above. The module is shipped with the plugs in the +10V position. Important:

You do not have to remove the module cover to set the configuration jumpers

Last State Configuration Jumpers The LAST STATE configuration jumpers determine the value of all the module’s outputs whenever communication between the module and the processor is lost. This condition occurs when a processor or adapter faults, or the processor is placed in the PROG or TEST mode, or if the remote I/O cable breaks.

Page 18

2-4

This is a significant safety feature. You can choose to have the module’s outputs go to the maximum, minimum, or middle of their respective ranges or hold their last state if a module or system fault occurs or if the system processor changes from RUN to PROG mode. You do this by placing the LAST STATE configuration jumpers on eight (four jumpers on sets of pins) of the stake pins marked MAX, MIN, MID on the module’s circuit board (Figure 2.1). If you do not place configuration jumpers in one of these positions, the module defaults to the HOLD LAST VALUE setting. Figure 2.1 shows jumper positions for the 1771-OFE, Series B, Analog Output Module LAST STATE Configuration Jumpers. Important:

Ignore the MAX, MIN, MID markings on the printed circuit board.

Important:

On power-up, the module’s output is disabled until the module receives the first block transfer write. The output then enables with the value that you send it in the block transfer write block.

Important:

We ship 1771-OFE modules with the LAST STATE configuration jumpers in the MID position. ATTENTION: Switch 1 of the I/O rack affects the function of the configuration settings as indicated in the table below.

!

Configuration Jumper Setting

Rack Switch 1 Setting

MIN

MID

MAX

HOLD LAST STATE

!

Page 19

2-5

Figure 2.1 LAST STATE Configuration Jumper Last State Output Level Configuration Jumpers

Front of Circuit Board

HOLD LAST STATE

MIN

MID

MAX

Table 2.A lists the output ranges and their minimum, maximum, and middle values. Table 2.A Output Last State Configuration Values Output Range Selection

Minimum Value

Middle Value

Maximum Value

4-20mA

4mA

12mA

20mA

0-50mA

0mA

25mA

50mA

1-5V

1V

3V

5V

0-10V

0V

5V

10V

+10V

Ć10V

0V

+10V

These output conditions are active only if the following conditions exist:

• the module faults • the processor is in the PROGRAM or TEST mode • rack switch 1 is in the reset position

Publication 1771-6.5.30 - November 1998

Page 20

2-6

Rack switch 1 determines what output conditions occur during a rack fault. Configuration Jumper Setting

Rack Switch 1 Setting

MIN

MID

MAX

HOLD LAST STATE

To set the last state configuration jumpers, proceed as follows.

!

ATTENTION: Do not insert modules into or remove modules from the I/O chassis while system power is ON. Failure to observe this rule could result in damage to module circuitry and unexpected machine operation.

1. Locate the jumpers as shown in Figure 2.1. 2. Carefully pull up on the jumpers to remove from the pins. 3. Reposition as necessary to provide the value selected in Table 2.A.

Setting Voltage Range Configuration Jumpers (1771-OFE1 only) If you ordered the voltage output version, you must set several configuration jumpers located inside the module on the circuit board. To do this, follow these steps: 2. Locate the configuration jumpers and set them according to your output voltage requirements (Figure 2.3). '&#'&

5. Position the jumpers as indicated in Figure 2.3.