Analog Output Module User Manual (Cat. No. 1771-OFE Series B), pages 21 to 30
Pages 21 to 30 of 84
The original document is the PDF (555 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-OFE1
Page 21
2-7
Figure 2.3 Configuration Jumper Locations
LAST STATE
In Out
(side view of jumper)
Configuration Jumper Location
0-10V
P3, Jumper 5 6 7 8 9 10
Desired Voltage Range
Output Channel
1-5V
In In Out Out Out Out
+ 10V Out Out In In Out Out
Out Out Out Out In In
1
P5, Jumper 5 6 7 8 9 10
In In Out Out Out Out
Out Out In In Out Out
Out Out Out Out In In
2
P7, Jumper 5 6 7 8 9 10
In In Out Out Out Out
Out Out In In Out Out
Out Out Out Out In In
3
P9, Jumper 5 6 7 8 9 10
In In Out Out Out Out
Out Out In In Out Out
Out Out Out Out In In
4
Install the Keying Bands
!
ATTENTION: Observe the following precautions when inserting or removing keys:
• Insert or remove keys with your
Position the keying bands in the backplane connectors to correspond to the key slots on the module. Place the keying bands: between 10 and 12 between 26 and 28 fingers.
• Make sure the key placement is correct Incorrect keying or the use of a tool can result in damage to the backplane connector and possible system faults.
Upper Connector I/O chassis
You can change the position of these bands if subsequent system design and rewiring makes insertion of a different type of module necessary.
Publication 1771-6.5.30 - November 1998
Page 22
2-8
Install the Module and Field Wiring Arm
!
ATTENTION: Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing an I/O module.
• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.
1 wiring arm
Attach the wiring arm (1771-WC) to the horizontal bar at the bottom of the I/O chassis. The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires.
1771-WH remove horizontal bar
2
1771-A1B, ĆA2B, ĆA3B, ĆA3B1, ĆA4B I/O chassis locking tab install
17643
1771-A1B, ĆA2B, ĆA3B1, ĆA4B Series B I/O chassis locking bar pin locking bar card guides card guides module
Snap the chassis latch over the top of the module to secure it.
Publication 1771-6.5.30 - November 1998 module
Swing the chassis locking bar down into place to secure the modules. Make sure the locking pins engage.
19809
Page 23
2-9
Connect the Wiring
The analog devices connect to the analog module through a field wiring arm (cat. no. 1771-WC). The field wiring arm pivots on the front of the I/O chassis to connect with the module. You can remove the module from the chassis without disconnecting user wiring because wiring connections are made on the field wiring arm. The connection diagram (Figure 2.5) shows connections to the field wiring arm.
!
ATTENTION: To avoid injury to personnel and damage to equipment, disconnect and lockout ac power from the processor and system power supplies before wiring the module.
Figure 2.5 Connection of Analog Devices to the Field Wiring Arm (cat. no. 1771-WC)
User Analog Device Functional Ground
A
Channel 1 output (+) lead
0
Channel 1 output (Ć) lead
1
Channel 2 output (+) lead
2
Channel 2 output (Ć) lead
3
Channel 3 output (+) lead
4
Channel 3 output (Ć) lead
5
Channel 4 output (+) lead
6
Channel 4 output (Ć) lead
7
Not used
B
Not used
Field Wiring Arm Cat. No 1771-WC
12878
The sensor cable must be shielded. The shield must: • extend the length of the cable, but be connected only at the 1771 I/O chassis • extend up to the point of termination Important: The shield should extend to the termination point, exposing just enough cable to adequately terminate the inner conductors. Use heat shrink or another suitable insulation where the wire exits the cable jacket.
Publication 1771-6.5.30 - November 1998
Page 24
2-10
The module requires shielded cable for signal transmission to the analog devices. Use Belden 8761 shielded cable, which consists of a single insulated, twisted-pair of conductors, covered along their entire length by a foil shield and encased in plastic. The shield reduces the effect of induced noise at any point along the cable.
Ground the Chassis and Module
You must ground the shield at the chassis end only. We recommend connecting each output cable’s shield to a properly grounded common bus. Refer to “Industrial Automation Wiring and Grounding Guidelines for Noise Immunity,” publication 1770-4.1, for additional information. Figure 2.6 Cable Grounding
Remove a length of cable jacket from the Belden 8761 cable.
Pull the foil shield and bare drain wire from the insulated wires. Bare drain wire
Twist the foil shield and drain wire together to form a single strand.
Attach a ground lug.
Belden 8761 Cable Insulated wires 20104
Foil shield Chassis Ground
SingleĆpoint Grounding
When you connect grounding conductors to the I/O chassis grounding stud, place a star washer under the first lug, then place a nut with captive lock washer on top of each ground lug.
Extend shield to termination point. Expose just enough cable to adequately terminate inner conductors.
Ground Lug Nut
Nut and Captive Washer
Grounding Stud
I/O Chassis Side Plate
Star Washer
Use heat shrink tubing or other suitable insulation where wire exits cable jacket. Ground Lug1 Shield and Drain twisted together
1Use the cup washer if crimpĆon lugs are not used.
19480
Shield and Drain twisted together #10 ThreadĆforming screw
ExternalĆtooth Washers
19923
Publication 1771-6.5.30 - November 1998
Page 25
2-11
Interpreting the Indicator Lights
The front panel of the module contains a green RUN and a red FLT (fault) indicator. At power-up, the red FLT indicator lights and remains ON during an initial module self-check. If a fault is found initially or occurs later, the red FLT indicator stays lit. If a fault is not found, the red indicator will turn off and the green RUN indicator will turn on and remain on. Possible module fault causes and corrective actions are discussed in Chapter 7, “Diagnostics and Troubleshooting.” Figure 2.7 Diagnostic Indicators
ANALOG OUT (12 BIT) RUN FLT
17948
Chapter Summary
In this chapter, you learned how to set the module configuration jumpers, connect the field wiring to the field wiring arm, and install your module in the I/O chassis.
Publication 1771-6.5.30 - November 1998
Page 26
2-12
Publication 1771-6.5.30 - November 1998
Page 27
Configuring Your Output Module What This Chapter Contains
In this chapter, you will read about:
Configuring Your Module
For information on
See page
Configuring Your Module . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Default Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Procedure for Configuring Your Module . . . . . . . . . . . . . . . . .
3-1 3-3 3-4 3-4 3-6 3-9
Because of the many analog devices available and the wide variety of possible applications, you must configure the module to conform to the analog device and specific application that you have chosen. You do this with a block transfer write instruction (BTW). The write block can be up to 13 words long and contains output data and information on data format and scaling. Word Assignment for Block Transfer Write
Word/Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word/Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
1
Channel 1 Data Value
2
Channel 2 Data Value
3
Channel 3 Data Value
4
Channel 4 Data Value
5
Data Format
Reserved
Minimum/Maximum Scaling Value Polarity
6
Channel 1 Minimum Scaling Value
7
Channel 1 Maximum Scaling Value
8
Channel 2 Minimum Scaling Value
9
Channel 2 Maximum Scaling Value
10
Channel 3 Minimum Scaling Value
11
Channel 3 Maximum Scaling Value
12
Channel 4 Minimum Scaling Value
13
Channel 4 Maximum Scaling Value
Important:
Data Polarity
A block transfer write length of 0 will result in a default length of 13. A block transfer read length of 0 will result in a default length of 5. Publication 1771-6.5.30 - November 1998
Page 28
3-2
Note: Programmable controllers that use 6200 software programming tools can take advantage of the IOCONFIG utility to configure this module. IOCONFIG uses menu-based screens for configuration without having to set individual bits in particular locations. Refer to your 6200 software literature for details. Programmable controllers that use process configuration and operation software (cat. no. 6190-PCO) can take advantage of those development and runtime tools used for the application of programmable controllers in process control. The PCO worksheets and the menu-driven configuration screens and faceplates let you configure, test/debug and operate the I/O module. Refer to your 6190-PCO software literature for details. The first four words in the BTW contain the actual data in binary or four-digit BCD format, which is converted by the module into voltage or current signals. When using the PLC-5, the 2’s complement binary can be used provided the +10V range is not used. Word
Decimal Bit (Octal Bit)
1
00-15 (00-17)
Channel 1 Data Value
2
00-15 (00-17)
Channel 2 Data Value
3
00-15 (00-17)
Channel 3 Data Value
4
00-15 (00-17)
Channel 4 Data Value
5
Description
Configuration Word Ć refer to Figure 3.1 below.
6
00-15 (00-17)
Channel 1 Minimum scaling value
7
00-15 (00-17)
Channel 1 Maximum scaling value
8
00-15 (00-17)
Channel 2 Minimum scaling value
9
00-15 (00-17)
Channel 2 Maximum scaling value
10
00-15 (00-17)
Channel 3 Minimum scaling value
11
00-15 (00-17)
Channel 3 Maximum scaling value
12
00-15 (00-17)
Channel 4 Minimum scaling value
13
00-15 (00-17)
Channel 4 Maximum scaling value
Word 5 in the BTW is the module configuration word. Information that you enter in this word tells the module what data format to expect and the polarity of the data and scaling values. The remaining eight words (words 6 through 13) in the BTW are reserved for minimum and maximum scaling values. You enter these values if you wish to scale a particular channel.
Publication 1771-6.5.30 - November 1998
Page 29
3-3
Configuration Word
Word 5 of the block transfer write is the module configuration word (Figure 3.1). It contains information on:
• data polarity • scaling polarity • data format Figure 3.1 Configuration Block Transfer Write Word 5 Word/Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word/Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
4
4
3
3
2
2
1
1
4
3
2
1
Word 5
1 = Channel 1 2 = Channel 2 3 = Channel 3 4 = Channel 4
Data Format 1 = Binary 0 = BCD
Data Sign Polarity 1 = Negative 0 = Positive
Reserved
Maximum Scaling Value Polarity 1 = Negative 0 = Positive
Minimum Scaling Value Polarity 1 = Negative 12883 0 = Positive
Table 3.A Bit/Word Descriptions for Configuration Block Transfer Write Word 5 Word
Decimal Bit (Octal Bit)
Description
00-03
Data polarity bits. When set (1), indicate negative data. When reset (0), indicate positive data. Bit 00 corresponds to channel 1, bit 01 to channel 2, etc.
04
When set (1), indicates negative minimum scaling value for Channel 1. When reset (0), indicates positive minimum scaling value for channel 1.
05
When set (1), indicates negative maximum scaling value for Channel 1. When reset (0), indicates positive maximum scaling value for channel 1.
06
When set (1), indicates negative minimum scaling value for Channel 2. When reset (0), indicates positive minimum scaling value for channel 2.
07
When set (1), indicates negative maximum scaling value for Channel 2. When reset (0), indicates positive maximum scaling value for channel 2.
08 (10)
When set (1), indicates negative minimum scaling value for Channel 3. When reset (0), indicates positive minimum scaling value for channel 3.
5
Publication 1771-6.5.30 - November 1998
Page 30
3-4
Word
Word 5 continued
Decimal Bit (Octal Bit)
Description
09 (11)
When set (1), indicates negative maximum scaling value for Channel 3. When reset (0), indicates positive maximum scaling value for channel 3.
10 (12)
When set (1), indicates negative minimum scaling value for Channel 4. When reset (0), indicates positive minimum scaling value for channel 4.
11 (13)
When set (1), indicates negative maximum scaling value for Channel 4. When reset (0), indicates positive maximum scaling value for channel 4.
12-14 (14-16) Reserved 15 (17)
Default Configuration
When set (1), tells the module to expect binary data. When reset (0), signifies fourĆdigit BCD data.
At power-up, the module’s microprocessor assumes default conditions of:
• positive data words • no scaling • BCD data The module’s microprocessor receives these values if you do not enter data into the configuration word:
Data Format
The voltage or current value at one of the module’s outputs is directly proportional to the value specified in that channel’s data word. The output scale is divided into 4095 parts, which means that as the data word is incremented or decremented, the output signal is incremented or decremented 1/4095 of the full scale. Table 3.B shows the incremented voltage or current assigned to each bit for the four different output scales. For example, if the data word for Channel 1 contains the value 0000 0111 1111 1111 (2047 decimal), the output for Channel 1 would be 2047/4095 or approximately 1/2 of the full scale. Table 3.B Output Ranges and Resolution
Publication 1771-6.5.30 - November 1998
Nominal Range
Unscaled Code Range
Actual Output Range
∆ V/Bit or ∆ I/Bit
1 to 5 volts
0 to 4095
1 to 5.00V +0.1%
0.976 mV/Bit
0 to 10 volts
0 to 4095
0 to 10.00V +0.1%
2.44 mV/Bit
Ć10 to +10 volts
Ć4095 to +4095
Ć10 to +10.00V +0.1%
4.88 mV/Bit
4 to 20 mA
0 to 4095
4 to 20.00 mA +0.1%
0.0039 mA/Bit
0 to 50 mA
0 to 4095
0 to 50.00 mA +0.1%
0.0122 mA/Bit