Manual · Allen-Bradley
Analog Output Module User Manual (Cat. No. 1771-OFE Series B)
Manual84 pagesPDF 555 KB
User manual for the Allen-Bradley 1771-OFE Series B analog output module (1771-OFE1 voltage, -OFE2 and -OFE3 current versions).
Covers · 1 model
The models it covers
Summary
What is in it
Allen-Bradley user manual for the 1771-OFE Series B Analog Output Module, a four-channel block transfer module for the 1771 I/O chassis. It covers the three versions (1771-OFE1 voltage, 1771-OFE2 and 1771-OFE3 current), installation and configuration jumpers, wiring, configuration and scaling, block transfer programming for PLC-2, PLC-3 and PLC-5 processors, reading status data, calibration, troubleshooting with indicator lights, specifications and data table formats.
Its parts
- Overview of the Analog Output Module
- Module Installation
- Module Configuration
- Module Programming
- Module Status and Input Data
- Calibrating Your Output Module
- Diagnostics and Troubleshooting
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
User manual for the Allen-Bradley 1771-OFE Series B analog output module, covering the 1771-OFE1 voltage version and the 1771-OFE2 and 1771-OFE3 current versions. It explains installing, configuring, programming, calibrating and troubleshooting the four-channel module in a 1771 I/O chassis.
- Module type
- Intelligent block transfer module that turns binary or four-digit BCD values from the processor into analog outputs p. 11
- Outputs
- 4 individually isolated differential outputs p. 12
- Voltage ranges
- 1771-OFE1: +1 to +5V DC, 0 to +10V DC or -10 to +10V DC, set per channel by jumpers p. 17, 69
- Power
- Drawn from the 1771 I/O chassis backplane; no external supply needed p. 12
- Chassis and slots
- Any 1771 I/O chassis; uses one I/O slot p. 6, 12
- Resolution
- 12-bit binary, 1 part in 4095 p. 69
- Current ranges
- 1771-OFE2: +4 to +20mA; 1771-OFE3: 0 to +50mA; both factory set p. 12, 69
- Max output current
- 1771-OFE1: 10mA per channel in voltage mode p. 69
- Isolation
- 1000V rms between output channels p. 69
- Block transfer
- Write of up to 13 words; read of 5 words for diagnostics p. 11
- Wiring arm
- 1771-WC field wiring arm; screw torque 7-9 pound-inches (0.6-1.1Nm) p. 23, 70
- Signal cable
- Belden 8761 shielded twisted pair, shield grounded at the chassis end only p. 24
- Indicators
- Green RUN and red FLT (fault) p. 25
- Environment
- Operating 0 to +60°C (+32 to +140°F); humidity 5% to 95% non-condensing p. 70
What this manual walks you through
- Choosing a slot and module group in the I/O chassis p. 17
- Setting the last state jumpers for loss of communication p. 17, 18, 19, 20
- Setting the voltage range jumpers on the 1771-OFE1 p. 20, 21
- Installing the keying bands p. 21
- Installing the module and the 1771-WC wiring arm p. 22
- Wiring analog devices to the field wiring arm p. 23
- Grounding the cable shield at the chassis p. 24
- Troubleshooting with the RUN and FLT indicators p. 65, 66
- Reading the five-word status block transfer p. 66, 67
- Block transfer with Mini-PLC-2 and PLC-2/20 processors using multiple GET instructions p. 71, 72, 73
Good to know
- Do not insert or remove the module while system power is on; it can damage the module circuitry. p. 16
- The module is open equipment and must be mounted in an enclosure during operation. p. 16
- Do not place the module in the same module group as a discrete high-density module. p. 17
- A read block transfer for more or fewer than five words is not performed. p. 66
- Outputs are protected against short circuits lasting no more than one minute. p. 69
Questions this manual answers
What voltage ranges does the 1771-OFE1 output?
+1 to +5V DC, 0 to +10V DC or -10 to +10V DC, chosen per channel with configuration jumpers. It ships with the jumpers in the +10V position. p. 17, 69
What do 1771-OFE outputs do when communication with the processor is lost?
Depending on the LAST STATE jumpers and rack switch 1, they go to the minimum, middle or maximum of the range or hold the last value. Modules ship with the jumpers in MID. p. 17, 18
Which wiring arm and cable does the 1771-OFE use?
The 1771-WC field wiring arm, with Belden 8761 shielded twisted-pair cable whose shield is grounded at the chassis end only. p. 23, 24
Does the 1771-OFE1 need an external power supply?
No. It takes its power through the 1771 I/O chassis backplane from the chassis power supply. p. 16
The whole text · 9 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file