Analog Output Module User Manual (Cat. No. 1771-OFE Series B), pages 61 to 70

Pages 61 to 70 of 84

The original document is the PDF (555 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-OFE1

Page 61

6-9

15.Remove the extender card and return the circuit board to the module. 16.Replace the LAST STATE configuration jumpers to their original position. 17.Replace the module covers. 18.Return the module to the I/O rack. 19.Replace your analog device wires (or the original field wiring arm if you used a spare for calibration procedures). Your module should now be properly calibrated and ready for use.

Current Output Version (1771-OFE3)

Preparation for Calibration 1. Turn off power to the processor and I/O chassis. 2. Remove the analog output module from the I/O chassis. 3. Remove the module covers. 4. Connect the backplane extender card (cat. no. 1771-EX) to the circuit board and insert the extender card into the I/O chassis. 5. Reconnect the wiring arm to the circuit board.

Channel Calibration 1. Disconnect your analog device wiring from the module’s wiring arm. Important:

If you have a spare or unused field wiring arm, you may want to temporarily switch it with the module’s present wiring arm. Use the spare wiring arm for test and calibration purposes to eliminate disconnecting your device wiring.

Important:

The accuracy of this calibration procedure depends on the precision of the load resistors used. Use resistors with a tolerance of 0.01%. You should be able to obtain voltage readings to +5mV. (If you use resistors of a value different from 250 ohms, you should be able to obtain voltage readings of +0.05% of V out). If you require greater accuracy, use load resistors with tolerances less than 0.01%.

If greater accuracy is required, substitute resistors that more closely approximate your actual device load.

Page 62

6-10

2. Attach 250 ohm resistor across Channel 1 (the top two screws) on the field wiring arm. Figure 6.7 Resistor Placement on Field Wiring Arm

- !

-

-

-

3. Attach three more 250 ohm resistors across Channels 2, 3, and 4 (Figure 6.7). 4. Place the LAST STATE configuration jumpers in the MAX position (if they are not there already). MAX

5. Connect a voltmeter across the top two screws on the field wiring arm (top screw is positive, and second screw is negative). 6. Turn processor, I/O chassis, and industrial terminal ON. 7. Place processor in the TEST or PROG mode. 8. Output full scale (+50mA) with write block transfer data. 9. Adjust R66 (Figure 6.6) until the reading is +12.5V (50mA) +5mV. 10.Repeat steps 8 and 9 for channels 2, 3 and 4. Adjust as necessary until the desired tolerance is obtained. Associated resistor potentiometers are shown in Table 6.D.

%

Page 63

6-11

Table 6.D Resistor Potentiometers Channel

Resistor Potentiometer

-

11. Remove the extender card and circuit board from chassis. 12.Replace Last State configuration jumpers to their original position. 13.Replace the module covers and insert the module into the I/O chassis. 14.Replace field wiring on field wiring arm (or position original wiring arm on module if you used a spare field wiring arm for this calibration procedure). Your module is now properly calibrated and ready for use.

Chapter Summary

In this chapter, you learned how to calibrate your module using simple test equipment.

Page 64 read from a scan by OCR; it may hold reading errors

6-12

Publication 1771-6.5.30 - November 1998

Page 65

Diagnostics and Troubleshooting Chapter Objectives

Interpreting the Indicator Lights

In this chapter, you will read how to troubleshoot your output module using indicator lights and diagnostic bits. For information on

See page

Interpreting the indicator lights . . . . . . . . . . . . . . . . . . . . . . . Read Block Transfer words . . . . . . . . . . . . . . . . . . . . . . . . .

7-1 7-2

The front panel of the module contains a green RUN and a red FLT (fault) indicator (Figure 7.1). At power-up, the red FLT indicator lights and remains ON during an initial module self-check . If a fault is found initially or occurs later, the red FLT indicator stays lit. If a fault is not found, the red indicator will turn off and the green RUN indicator will turn on and remain on. Possible module fault causes and corrective actions are shown in Table 7.A. Figure 7.1 Diagnostic Indicators

ANALOG OUT (12 BIT)

RUN FLT

17948

Publication 1771-6.5.30 - November 1998

Page 66

7-2

Table 7.A Troubleshooting Chart Condition

Possible Cause

Recommended Action

• Check I/O chassis for power. • Turn off power to I/O chassis. Remove

Green RUN indicator does not No Power to Module come on. Bad internal fuse and reinsert module into chassis. Return power to I/O chassis.

Red FAULT indicator is on continuously with the processor in program and run modes.

Unsuccessful Power-Up • EPROM Fault • Checksum Error

• Cycle power. • Replace faulty module if necessary.

Block transfers are not being performed.

• Block Transfer

• Check user program .

Read Block Transfer Status Words

Instructions Programmed Incorrectly • Module has failed selfĆdiagnostics.

• Cycle power. • Replace faulty module if necessary.

The module allows a five-word read block transfer for rudimentary program or hardware debugging (Figure 7.2). If a read block transfer request is for more or less than five words, the module will not perform a read block transfer. Figure 7.2 Word Assignment for Read Block Transfer

Decimal Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Word 1

Channel 1 DAC Input Data

2

Channel 2 DAC Input Data

3

Channel 3 DAC Input Data

4

Channel 4 DAC Input Data

5

Not used

I/O Reset

Reserved

Important:

Data Valid

The user program that utilizes the read block transfer must make sure that bits 06 and 07 (the write enable and read enable request bits) of the MCB are not set simultaneously.

The first four words of the read block transfer show the actual 12 bits of data sent to the module’s digital-to-analog converters (DACs). The first four words in the read block transfer appear in 12-bit binary format regardless of the module’s mode of operation (BCD or 12-bit binary).

Publication 1771-6.5.30 - November 1998

Page 67

7-3

The fifth word contains the status of each DAC word; that is, whether data is out of range or scaling is improperly programmed. The fifth word also indicates that I/O RESET has been established (when the processor is in the PROG/TEST or RUN mode). Word

Bits

Description

Bits 00-03

When set, indicate invalid channel data is sent to the module. These bits are not reset until a correct write block transfer is sent. Bit 03 corresponds to Channel 4, Bit 02 to Channel 3, and so on.

Bit 16

Is the I/O RESET bit. When set, it indicates that the processor is in TEST or PROGRAM mode (i.e., block transfer data is not being written to the module).

5

Chapter Summary

In this chapter you learned how to use the indicator lights and word 5 in the BTR for troubleshooting your module.

Publication 1771-6.5.30 - November 1998

Page 68 read from a scan by OCR; it may hold reading errors

7-4

Publication 1771-6.5.30 - November 1998

Page 69

Outputs per Module

4 Individually Isolated

Module Location

Bulletin 1771 I/O Chassis - One Slot

Output Voltage Ranges (Nominal) 1771-OFE1

+1 to +5V DC -10 to +10V DC 0 to +10V DC

Output Current (maximum)

10mA per Channel in Voltage Mode (1771-OFE1)

Output Current Ranges (Nominal)

+4 to +20mA (1771-OFE2) 0 to +50mA (1771-OFE3)

Digital Resolution

12-Bit Binary - 1 Part in 4095

Output Capacitance

0.01µF (Voltage Outputs) 0.022µF (Current Outputs)

Output Impedance

<0.25 ohms for Voltage Outputs Exclusive of Contact Wiring Resistance >1.5 megohms for Current Outputs

Max Loop Impedance in the Current Mode

1771-OFE2 - Up to 1200 ohms Load Resistance 1771-OFE3 - Up to 400 ohms Load Resistance

Output Overload Protection

All outputs are protected against short circuit load conditions not to exceed one minute.

Backplane Power

1771-OFE1 1771-OFE2 1771-OFE3

1.50A 1.50A 2.50A

Power Dissipation

1771-OFE1 1771-OFE2 1771-OFE3

7.9W 7.9W 13.1W

Thermal Dissipation

1771-OFE1 1771-OFE2 1771-OFE3

26.9 BTU/hr 26.9 BTU/hr 44.5 BTU/hr

Isolation

1000V rms Between Output Channels Tested at 1500V (Transient) for 1s Between the Output Circuit and the Control Logic (System Side)

D/A Converter Specifications Settling Time

0.8 ms Maximum for a Resistive Load

Internal Scan Rate

8.0 ms for All Channels Using BCD Data and Scaling 1.6 ms for All Channels Using Binary Data and No Scaling

Accuracy (Including Linearity, Gain, and Offset at 25oC)

+0.1% of Full Scale +1/2 LSD (BCD Mode) +1/2 LSB (BINARY Mode)

Temperature Coefficient

+50 ppm/oC of Full Scale Range

Specifications continued on next page

Publication 1771-6.5.30 - November 1998

Page 70

Publication 1771-6.5.30 - November 1998

Environmental Conditions Operational Temperature: Storage Temperature: Humidity Rating:

0oC to +60oC (+32oF to +140oF) -40oC to +85oC (-40oF to +185oF) 5% to 95% (Non-Condensing)

Field Wiring Arm

Catalog No. 1771-WC

Field Wiring Arm Screw Torque

7-9 poundĆinches (0.6-1.1Nm)

Agency Certification (when product or packaging is marked)

• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified Hazardous or nonĆhazardous locations • UL listed • UL Class I, Division 2, Groups A, B, C, D certified Hazardous or nonĆhazardous locations • CE marked for all applicable directives