Page 51

- What This Chapter Contains

In this chapter, you will read about:

Reading Data from the Module

For information on

See page

Reading Data from the Module . . . . . . . . .

5-1

Block transfer read (BTR) programming moves status and data from the module to the processor’s data table in one I/O scan. The processor user program initiates the request to transfer data from the module to the processor. The transferred words contain module status, channel status and input data from the module. The maximum BTR data file length required is five words. Figure 5.1 Word Assignment for Block Transfer Read

Decimal Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Word 1

Channel 1 DAC Input Data

2

Channel 2 DAC Input Data

3

Channel 3 DAC Input Data

4

Channel 4 DAC Input Data

5

Not used

I/O Reset

Reserved

Important:

Data Valid

The user program that uses the read block transfer must make sure that Bits 06 and 07 (the write enable and read enable request bits) of the MCB are not set simultaneously.

Publication 1771-6.5.30 - November 1998

Page 52

5-2

Table 5.A Bit/Word Description for Block Transfer Read Word

Decimal Bits (Octal Bits)

1

Bits 00-15 (00-17)

Channel 1 DAC input data.

2

Bits 00-15 (00-17)

Channel 2 DAC input data.

3

Bits 00-15 (00-17)

Channel 3 DAC input data.

4

Bits 00-15 (00-17)

Channel 4 DAC input data.

Bits 00-03

When set, indicate invalid channel data is sent to the module. These bits are not reset until a correct write block transfer is sent. Bit 00 corresponds to Channel 1, Bit 01 to Channel 2, and so on.

Bits 04-13 (04-15)

Reserved

Bit 14 (16)

Is the I/O RESET bit. When set, it indicates that the processor is in TEST or PROGRAM mode (i.e., block transfer data is not being written to the module).

5

Description

The first four words of the block transfer read show the actual 12 bits of data sent to the module’s digital to analog converters (DACs). The first four words in the block transfer read appear in 12-bit binary format regardless of the module’s mode of operation (BCD or 12-bit binary). The fifth word contains the status of each DAC word; that is, whether data is out of range or scaling is improperly programmed. The fifth word also indicates that I/O RESET has been established (when the processor is in the PROG/TEST or RUN mode).

Chapter Summary

Publication 1771-6.5.30 - November 1998

In this chapter, you learned the meaning of the status data the module sends to the processor.

Page 53

Calibrating Your Output Module Chapter Objectives

In this chapter, you will read how to calibrate your output module.

Tools and Test Equipment

For information on

See page

Tools and test equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . Calibrating your module . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage Output version (1771-OFE1) . . . . . . . . . . . . . . . . . . Current Output version (1771-OFE2) . . . . . . . . . . . . . . . . . . . Current Output version (1771-OFE3) . . . . . . . . . . . . . . . . . . .

6-1 6-1 6-2 6-5 6-9

Table 6.A lists tools and test equipment required for module calibration. Table 6.A Test Equipment

Used On: Voltage Versions

Equipment

Description

5-1/2 Digit Voltmeter

0.01% Accuracy Minimum.

4 Load Resistors

1.0K or Greater, 0.25W, 1.0% (P/N 628217-01)

Current Versions

4 Load Resistors

250 ohm or Greater, 0.25W, 0.01% (P/N 940719-01)

Both Voltage and Current

Small Jeweler's Screwdriver or Tweeker" Alignment Tool

Newark Electronics 500 North Pulaski Road Chicago, IL 60624

Backplane Extender Card

Cat. No. 1771-EX

Calibrating Your Module

The analog output module is shipped from the factory already calibrated. If it becomes necessary to recalibrate the analog output module, you must calibrate it in an I/O chassis. The module needs to communicate with the processor. Calibration consists of two tasks: • preparing the module for calibration • calibrating each channel The calibration procedure for the voltage output version module is different from the calibration procedure for the current output version module. Refer to the appropriate section for your module.

!

ATTENTION: Do not attempt calibration without reading and thoroughly understanding all steps in this procedure. Also, do not attempt to calibrate this module in an operating system.

Publication 1771-6.5.30 - November 1998

Page 54

6-2

Voltage Output Version (1771-OFE1)

Preparation for Calibration 1. Turn off the processor and I/O chassis power. 2. Remove the field wiring arm. 3. Remove the analog output module from the I/O chassis. 4. Remove the module covers. 5. Connect the backplane extender card (cat. no. 1771-EX) to the circuit board. 6. Insert the extender card/circuit board assembly in the I/O chassis. 7. Reinstall the field wiring arm. Important:

If you have a spare or unused field wiring arm, you may want to temporarily switch it with the module’s present field wiring arm. You can use this spare arm for test purposes in order to avoid disconnecting your analog device wires.

Important:

The accuracy of this calibration procedure is dependent upon the precision of your load resistors. Use resistors with a tolerance of 1.0%. You should be able to attain voltage readings to +1mV. For greater accuracy, use load resistors with tolerances less than 1.0%.

Use load resistors with values of 1K ohms. For greater accuracy, you can substitute the 1K ohm resistor with a resistor that more closely approximates your actual device load.

Calibration Procedure 1. Disconnect your analog device wires from the module’s field wiring arm if you are not using a spare field wiring arm for calibration.

MAX

2. Attach a resistor with a value of 1K or greater (to approximate your actual load) across Channel 1 (the top two screws in Figure 6.1) of the field wiring arm. 3. Attach three more 1K resistors across the remaining three channels on the field wiring arm just as you did in Step 2 (Figure 6.1). 4. Place the LAST STATE configuration jumpers (Figure 6.2) in the MAX position (if they are not there already). 5. Select the +10V output range by placing the four channel configuration jumpers in the position shown in Figure 6.2.

Page 55

6-3

6. Connect the voltmeter leads across the top two screws on the field wiring arm (Channel 1). The top screw is positive, and the second (lower) screw is negative. 7. Turn on the processor, I/O chassis, and the industrial terminal. Figure 6.1 Resistor Placement on Field Wiring Arm

'*

-

-

-

Figure 6.2 LAST STATE Configuration Jumpers

LAST STATE

*'&, '

($-!+

-#&

1

Page 56

6-4

Figure 6.3 Location of Configuration Jumpers and Resistor Pots

LAST STATE

TP1 TP2 TP3

TP10 TP12

Configuration Jumpers (set for +10V scale) Channel 0

Channel 1

Channel 2

Channel 3

R67 R66

R74 R73

4 5 TP6 TP TP

P7 P8 TP9 T T

Resistor Potentiometers Adjustment Screws

R81 R80

R88 R87 12993

8. Place the processor in the TEST or PROG mode. 9. Output full scale (+10V) either with write block transfer data or by placing the LAST STATE configuration jumpers in the MAX position. MAX

10.Adjust R66 until the reading is 10V +1mV. 11. Output -10V either with write block transfer data or by placing the LAST STATE configuration jumpers in the MIN position.

MIN

12.Adjust R67 until the reading is one-half the difference between -10V and the initial reading. 13.Output full scale (+10V) again, either with write block transfer data or by placing the LAST STATE configuration jumpers in the MAX position.

MAX

Publication 1771-6.5.30 - November 1998

14.Adjust R66 again until the reading is 10V +1mV.

Page 57

6-5

15.Reconnect the voltmeter to the appropriate screws on the field wiring arm. Repeat Steps 9 through 14 for Channels 2, 3, and 4, until you obtain the desired tolerance. Table 6.B lists the appropriate resistor pots for each channel. Table 6.B Resistor Pots Channel

Resistor Pots

1

R66, R67

2

R73, R74

3

R80, R81

4

R87, R88

16.Turn off power to the module. 17.Return the LAST STATE configuration jumpers to the position they were in before you started calibration. 18.Return the channel configuration jumpers to their original positions. 19.Remove the extender card and return the circuit board to the module. 20.Replace the module covers. 21.Return the module to the I/O rack. 22.Replace your analog device wires (or the original field wiring arm if you used a spare for calibration purposes). Your module should now be properly calibrated and ready for use.

Current Output Version (1771-OFE2)

Preparation for Calibration 1. Turn off the processor and I/O chassis power. 2. Remove the analog output module from the I/O chassis. 3. Remove the module covers. 4. Connect the backplane extender card (cat no. 1771-EX) to the circuit board. 5. Insert the extender card/circuit board assembly in the I/O chassis. 6. Reconnect the field wiring arm.

Publication 1771-6.5.30 - November 1998

Page 58

6-6

Channel Calibration 1. Disconnect your analog device wires from the module’s field wiring arm. Important:

If you have a spare or unused field wiring arm, you may want to temporarily switch it with the module’s present field wiring arm. You can use this spare arm for test purposes in order to avoid disconnecting your analog device wires.

Important:

The accuracy of this calibration procedure is dependent upon the precision of your load resistors. We suggest using resistors with a tolerance of 0.01%. You should be able to attain voltage readings to +2mV. (If you use resistors of a value different from 250 ohms, you should be able to attain voltage readings of +0.05% of V out.) If you require greater accuracy, you need to use load resistors with tolerances less than 0.01%.

Use load resistors with values of 250 ohms. For greater accuracy, you can use a resistor that more closely approximates your actual device load. 2. Attach a resistor with a value of 250 ohms across Channel 1 (the top two screws) of the field wiring arm. 3. Attach three more 250 ohm resistors across the remaining three channels on the field wiring arm just as you did in step 2 (Figure 6.4). Figure 6.4 Resistor Placement on Field Wiring Arm

- !

-

-

%

-

Page 59

6-7

4. Place the LAST STATE configuration jumpers (Figure 6.5) in the MAX position (if they are not there already).

MAX

Figure 6.5 LAST STATE Configuration Jumpers in MAX Position

LAST STATE

Front of Module

-#

5. Connect the voltmeter leads across the top two screws on the field wiring arm (Channel 1). The top screw is positive, and the second (lower) screw is negative. 6. Turn on the processor, I/O chassis, and the industrial terminal. 7. Place the processor in the TEST or PROG mode. 8. Output full scale (+20mA) either with write block transfer data or by placing the LAST STATE configuration jumpers in the MAX position. MAX

9. Adjust R66 until the reading is +5V (20mA) +2mV (Figure 6.6). 10.Output +4mA (1V - minimum scale) either with write block transfer data or by placing the LAST STATE configuration jumpers in the MIN position.

MIN

11. Adjust R67 until the reading is 3/4 the difference between 1V and the initial minimum scale reading.

Page 60

6-8

Figure 6.6 Location of Resistor Pots

LAST STATE

TP1 TP2 TP3

TP10 TP12

Configuration Jumpers (set for +10V scale) Channel 0

Channel 1

Channel 2

Channel 3

R67 R66

R74 R73

4 5 TP6 TP TP

P7 P8 TP9 T T

Resistor Potentiometers Adjustment Screws

R81 R80

R88 R87 12993

12.Output full scale (+20mA) again, either with write block transfer data or by placing the LAST STATE configuration jumpers in the MAX position. MAX

13.Adjust R66 until the reading is 5V +2mV. 14.Reconnect the voltmeter to the appropriate screws on the field wiring arm. Repeat Steps 8 through 13 for Channels 2, 3, and 4 until the desired tolerance is obtained. Table 6.C lists the appropriate resistor pots. Table 6.C Resistor Pots

Publication 1771-6.5.30 - November 1998

Channel

Resistor Pots

1

R66, R67

2

R73, R74

3

R80, R81

4

R87, R88