PLC-5 Programmable Controllers Selection Guide 1785 and 1771, pages 1 to 8

Pages 1 to 8 of 60: PLC-5 Selection Guide - 1785 and 1771; PLC-5 Comparison; Introduction

The original document is the PDF (4.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Allen-Bradley 1771-OGC

Page 1 read from a scan by OCR; it may hold reading errors

LISTEN. THINK.

PLC-5 PROGRAMMABLE CONTROLLERS

SELECTION GUIDE 1785 and 1771

Rockwell Allen-Bradley - RockwellSoftwae Mutomation

Page 2

PLC-5 Programmable Controllers Comparison Category

Controller

Catalog Number

User Memory Words, Max

Total I/O, Max

Number of Communication Ports (mode)

Standard

PLC-5/11

1785-L11B

8000

512

1 DH+ or Remote I/O (Adapter or Scan)

PLC-5/20

1785-L20B

16,000

512

1 DH+ and 1 DH+ or Remote I/O (Adapter or Scan)

PLC-5/30

1785-L30B

32,000

1024

2 DH+ or Remote I/O (Adapter or Scan)

PLC-5/40

1785-L40B

48,000

2048

4 DH+ or Remote I/O (Adapter or Scan)

PLC-5/40L

1785-L40L

48,000

2048

2 DH+ or Remote I/O (Adapter or Scan) and 1 Extended Local I/O

PLC-5/60

1785-L60B

64,000

3072

4 DH+ or Remote I/O (Adapter or Scan)

PLC-5/60L

1785-L60L

64,000

3072

2 DH+ or Remote I/O (Adapter or Scan) and 1 Extended Local I/O

PLC-5/80

1785-L80B

100,000

3072

4 DH+ or Remote I/O (Adapter or Scan)

PLC-5/26

1785-L26B

16,000

512

1 DH+ and 1 DH+ or Remote I/O (Adapter or Scan)

PLC-5/46

1785-L46B

48,000

2048

4 DH+ or Remote I/O (Adapter or Scan)

PLC-5/86

1785-L86B

100,000

3072

4 DH+ or Remote I/O (Adapter or Scan)

PLC-5/20C

1785-L20C15

16,000

512

1 ControlNet (Dual Media) and 1 DH+

PLC-5/40C

1785-L40C15

48,000

2048

1 ControlNet (Dual Media) and 2 DH+ or Remote I/O (Adapter or Scan)

PLC-5/80C

1785-L80C15

100,000

3072

1 ControlNet (Dual Media) and 2 DH+ or Remote I/O (Adapter or Scan)

ControlNet with Protected Memory

PLC-5/46C

1785-L46C15

48,000

2048

1 ControlNet (Dual Media) and 2 DH+ or Remote I/O (Adapter or Scan)

Ethernet

PLC-5/20E

1785-L20E

16,000

512

1 Ethernet, 1 DH+ and 1 DH+ or Remote I/O (Adapter or Scan)

PLC-5/40E

1785-L40E

48,000

2048

1 Ethernet, 2 DH+ or Remote I/O (Adapter or Scan)

PLC-5/80E

1785-L80E

100,000

3072

1 Ethernet, 2 DH+ or Remote I/O (Adapter or Scan)

Standard with Protected Memory

ControlNet

Page 3

Introduction

1

Introduction

1785 PLC-5 Programmable Controller: The Foundation of Control Architecture

The PLC-5 programmable controller stands at the center of a control architecture that brings together existing and future systems by means of networks such as EtherNet/IP, ControlNet and DeviceNet, and offers connectivity among SLC 500, ControlLogix, and MicroLogix controllers. Because they include embedded network connections, PLC-5 controllers enable your control architecture to be flexible enough to include cost-effective connections to a wide range of devices.

I/O Modules Many Choices to Meet Your Exact Requirements

Software Tools Program in Structured Text, Function Block, Sequential Function Charts or Ladder Logic Languages

Controllers Information, Control, and Device Communication Capability

Topic PLC-5 System Overview Lay Out the System Select I/O Modules Select Network Communications Select Controllers Select Chassis Select Power Supplies Select Software ViewAnyWare Products Summary

Page 2 4 7 19 31 37 39 43 50 53

Publication 1785-SG001B-EN-P - June 2006

Page 4

2

Introduction

PLC-5 System Overview

A PLC-5/1771 control system, at minimum, consists of a programmable controller and I/O modules in a single 1771 chassis with a power supply. You choose the controller with the on-board communication ports you need. A simple system can consist of only a standalone controller and I/O modules all in a single chassis.

PLC-5 Programmable Controller

1771 I/O Chassis Backplane

1771 I/O modules in the I/O chassis in which the PLC-5 controller resides. A maximum of 512 I/O.

On-board remote I/O scanner ports are available on all PLC-5 controllers. On-board extended-local I/O scanner ports are available on some PLC-5 controllers. On-board ControlNet ports are available on some PLC-5 controllers. To provide a DeviceNet I/O scanner port to the system, you must add a 1771-SDN DeviceNet Scanner Module.

Publication 1785-SG001B-EN-P - June 2006

Page 5

Introduction

3

In the typical configuration illustration, a ControlNet port on the controller interfaces the processor to the ControlNet link. In each of the two chassis remote from the controller, a 1771-ACN15 I/O Adapter Module provides I/O modules in those chassis with an interface to the ControlNet link. In this configuration, the PLC-5 controller monitors/controls the I/O in its local I/O chassis as well as the I/O in the remote locations. Multiple controllers can communicate across networks; and I/O in multiple platforms can be distributed in many locations connected over multiple I/O links • Computers • Controllers • Internet Browsers (Ethernet only)

• Ethernet • ControlNet • Data Highway Plus • RS-232-C (DF1)

• Ethernet

Ethernet Interface Module DeviceNet Scanner Module 1771 I/O Chassis Backplane

1771 I/O modules in the I/O chassis in which the PLC-5 controller resides. A maximum of 512 I/O. ControlNet Link

PLC-5 Programmable Controller

DeviceNet Link

• 1734 I/O Modules • 1769 I/O Modules • 1790 I/O Blocks • 1791D I/O Blocks • 1792D I/O Blocks • 1794 I/O Modules • 1798 I/O Modules • Other devices • 1734 I/O Modules • 1746 I/O Modules • 1771 I/O Modules • 1794 I/O Modules • 1797 I/O Modules • Other devices

Universal Remote I/O Link

• 1746 I/O Modules • 1771 I/O Modules • 1791 I/O Blocks • 1794 I/O Modules • Other devices

Extended-local I/O Link

• 1771 I/O Modules

Plug a 1771 power supply module into an I/O module slot, or connect a standalone 1771 power supply into the left end of each chassis. Depending on the communication ports available on your particular PLC control system, you can select operator interfaces that are compatible with those particular ports.

Publication 1785-SG001B-EN-P - June 2006

Page 6

4

Introduction

Lay Out the System

Lay out the system by determining the network configuration and the placement of components in each location. Decide at this time whether each location will have its own controller. Place each controller’s I/O on an isolated network to maximize the performance and to more easily accommodate future network or system configuration changes. If you plan to share I/O, make sure the I/O is on a network that each controller can access. Assume that Network A and Network B both require a controller and its I/O. Both controllers interact with time-critical information. RSView Network C Panel C

Network B

Network A Panel A Chassis

Panel A Chassis 2

Panel A Chassis 3

Panel B Chassis

Panel B Chassis

Panel View

Panel View

For a PLC-5 controller to control I/O modules, both the controller and the I/O modules must be directly attached to the same network. I/O Location

Controller in Panel A, Chassis 1

Controller in Panel B, Chassis 1

Panel A, chassis 1

Yes

Yes

Panel A, chassis 2

Yes

No

Panel A, chassis 3

Yes

No

Panel B, chassis 1

Yes

Yes

Panel B, chassis 2

No

Yes

Panel C, chassis 1

Yes

Yes

Evaluate what communications need to occur between controllers. If there is sporadic information that is not time-critical, use a message-based network such as an EtherNet/IP (the information portion), Data Highway Plus, or the unscheduled portion of the ControlNet network. If the information is time-critical, such as producer/consumer tags between controllers, use the ControlNet or EtherNet/IP network.

Publication 1785-SG001B-EN-P - June 2006

Page 7

Introduction

5

Apply Backup Solutions The ControlNet Hot Backup Module, 1785-CHBM, provides backup of ControlNet I/O. A secondary controller qualifies critical-control information with the primary controller. Both controllers consume information from inputs and connect to outputs, but only the primary controller controls the outputs. The secondary controller establishes control of outputs if the primary controller shuts down. For more information, see page 23. ControlNet PLC-5 Controller with 1785-CHBM Cartridge Installed

PanelView Plus or Other Interface Device

ControlNet PLC-5 Controller with 1785-CHBM Cartridge Installed

Redundant ContolNet Network

1794 FLEX I/O and/ or and/ or 1746 I/O

1771 I/O

The PLC-5 Backup Communication Module, 1785-BCM, helps increase the fault tolerance of PLC-5 programmable controller systems controlling I/O on a remote I/O link by providing backup of the PLC-5 programmable controller.

PLC-5 Controller

1785-BCM Module PLC-5 Controller

1785-BCM Module

High-speed Serial Link

Local I/O Chassis

DH+ Link

Local I/O Chassis

Remote I/O Link

DH+ Link Remote I/O Chassis

Remote I/O Chassis

Terminator

1771-ASB Remote I/O Link

1771-ASB

Cat. No.

Connections

Customer Relay

Design Considerations

Power Dissipation

Backplane Current Load

1785-BCM

1771-WG wiring arm (included)

0.25 A @ 24V dc (resistive)

Place in local I/O chassis

10 W max

1A

Publication 1785-SG001B-EN-P - June 2006

Page 8

6

Introduction

Use the following checklist as a guide to completing your own system specification. The inside of the back cover of this selection guide is a worksheet you can use to record your selections. 9

Step 1

For more information, see Select I/O Modules

Select I/O based on: • type of information to send/receive. • application requirements. • electrical requirements. 2

Select Network Communications Select Networks based on: • type of information to send/receive. • system performance. • distance/size of application. • available networks. • future expansion.

3

Select Controllers Select a controller based on: • I/O requirements. • memory requirements. • communication requirements.

4

Select Chassis Select a chassis based on: • the number of slots you need.

5

Select Power Supplies

1771 I/O Modules ................................................. page 8 1746 I/O Modules ................................................. page 13 1794 I/O Modules ................................................. page 14 1797 I/O Modules ................................................. page 15 1791D I/O Modules............................................... page 16 1734 I/O Modules ................................................. page 17 NetLinx Architecture ............................................. page 19 Select a Network .................................................. page 20 EtherNet/IP Protocol.............................................. page 21 ControlNet ............................................................ page 23 DeviceNet............................................................. page 25 Serial Network...................................................... page 26 Data Highway Plus................................................ page 29 Remote I/O ........................................................... page 30 Enhanced Controllers............................................ page 32 Ethernet Controllers.............................................. page 33 ControlNet Controllers........................................... page 34 Protected Controllers ............................................ page 35 Backing Up Memory ............................................. page 36 Battery Replacement ............................................ page 36 1771 Chassis ....................................................... page 37 Mounting Dimensions........................................... page 38

1771 Power Supplies............................................ page 39 Power Requirements and Transformer Sizing........ page 40

Select a power supply based on: • input voltage. • output current. • number of slots required. 7

Select Software Select software based on: • computer platform. • operating environment. • programming language.

Publication 1785-SG001B-EN-P - June 2006

Select Software .................................................... page 43 Programming Software......................................... page 44 RSLinx Software ................................................... page 45 Network Configuration Software ........................... page 46 RSLogix Emulate 5 Software................................. page 47 PLC-5 and Training Software ................................ page 48 ViewAnyWare Products......................................... page 50