What is in it
The Allen-Bradley PLC-5 selection guide for 1785 controllers and 1771 I/O. It opens with a comparison table of PLC-5 controllers by memory, I/O and ports, then steps through laying out a system and selecting I/O modules (1771, 1746, FLEX, POINT and others), network communications, controllers, chassis, power supplies and software. The 1771 section lists digital and analog module catalog numbers with their points, voltages and backplane current.
Its parts
- PLC-5 Comparison
- Introduction
- Select I/O Modules
- Select Network Communications
- Select Controllers
- Select Chassis
- Select Power Supplies
- Select Software
- Summary
From the manual
Key facts from this manual
Each line names its page in the PDF.
An Allen-Bradley selection guide (publication 1785-SG001B-EN-P, June 2006) for PLC-5 programmable controllers (1785) and the 1771 chassis, power supplies and I/O modules, with the networks and software that go with them. It does not list the 1771-OGC; its 1771 digital output table names the TTL modules 1771-OG and 1771-OGD. It helps the reader lay out a PLC-5 system and pick controllers, I/O modules, chassis and power supplies.
- Document type
- Selection guide for 1785 PLC-5 controllers with 1771 I/O, chassis, power supplies, networks and software p. 3
- Minimum system
- A controller and I/O modules in one 1771 chassis with a power supply; up to 512 I/O in the controller's chassis p. 4
- Controller range
- PLC-5/11 (1785-L11B): 8000 words, 512 I/O, up to PLC-5/80 (1785-L80B): 100,000 words, 3072 I/O p. 2
- Ethernet controllers
- PLC-5/20E (1785-L20E), PLC-5/40E (1785-L40E), PLC-5/80E (1785-L80E), each with 1 Ethernet port p. 2
- ControlNet controllers
- PLC-5/20C (1785-L20C15), PLC-5/40C (1785-L40C15), PLC-5/80C (1785-L80C15), PLC-5/46C (1785-L46C15) p. 2
- TTL output modules
- 1771-OG: 8, 5.0...5.3V, 168 mA backplane current; 1771-OGD: 16, 5.0...5.3V, 230 mA p. 11
- TTL input module
- 1771-IG: 8 inputs, 122 mA backplane current p. 10
- DeviceNet
- Needs a 1771-SDN DeviceNet Scanner Module p. 4
- Memory backup
- EEPROM modules 1785-ME16, 1785-ME32, 1785-ME64, 1785-CHBM; not for ControlNet PLC-5 controllers p. 38
- Battery
- 1770-XYC for all PLC-5 programmable controllers p. 38
- Chassis
- 1771-A1B (4 slots), 1771-A2B (8), 1771-A3B and 1771-A3B1 (12), 1771-A4B (16) p. 39
- Power supplies
- 5V dc to the backplane, up to 8 A per supply, one or two chassis slots; can be paralleled p. 41
- Power supply models
- 1771-P4S: 120V ac, 8 A @ +5V dc, 1 slot; 1771-P5: 24V dc, 8 A, 2 slots; 1771-P7: 16 A @ +5V dc, standalone p. 41
- Chassis spacing
- Mount horizontally; 153 mm (6 in.) above and below, 102 mm (4 in.) at the sides p. 40
What this manual walks you through
- Choosing a PLC-5 controller by memory, I/O count and ports p. 2
- Laying out controllers, I/O and networks p. 6
- Selecting 1771 digital, analog and intelligent I/O modules p. 10, 11, 12, 13, 14
- Backing up controller memory and estimating battery life p. 38
- Choosing a 1771 chassis and spacing it in the enclosure p. 39, 40
- Choosing power supplies and sizing the transformer p. 41, 42
Good to know
- A PLC-5 controller can control only I/O modules attached directly to the same network. p. 6
- A transformer that is too small clips the sine wave and can make the power supply shut down modules early. p. 42
- Leave any excess enclosure space at the top, where the temperature is highest. p. 40
- Each ac power supply signals a backplane shutdown when line voltage drops below its lower limit. p. 42
Questions this manual answers
How much backplane current does the 1771-OG TTL module draw?
168 mA; the guide lists it with 8 points at 5.0...5.3V. p. 11
Which battery does a PLC-5 controller use?
The 1770-XYC, which applies to all PLC-5 programmable controllers. p. 38
How much current can a 1771 power supply provide?
Up to 8 A per supply at 5V dc to the backplane; the standalone 1771-P7 gives 16 A @ +5V dc. p. 41
How many I/O can a PLC-5/80 handle?
3072 I/O, with 100,000 words of user memory. p. 2
What sizes do 1771 chassis come in?
1, 2, 4, 8, 12 and 16 module slots. p. 39
Contents
Chapters and sections
Each line opens the PDF at its page.
- PLC-5 Selection Guide - 1785 and 17711
- PLC-5 Comparison2
- Introduction3
- Select I/O Modules9
- Select Network Communications21
- Select Controllers33
- Select Chassis39
- Select Power Supplies41
- Select Software45
- Summary55
1 more line, from page 60 on
The whole text · 7 parts