Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 4 of 7

PLC-5 Programmable Controllers Selection Guide 1785 and 1771: Select Controllers

Pages 33 to 38 of 60, from PLC-5 Programmable Controllers Selection Guide 1785 and 1771

The original document is the PDF (4.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Allen-Bradley 1771-OGC

Page 33

31

Select Controllers

Step 3 - Select: • Enhanced PLC-5 Controllers • Ethernet PLC-5 Controllers • ControlNet PLC-5 Controllers • Protected PLC-5 Controllers • EEPROM Memory Modules • Replacement Batteries

Select Controllers

PLC-5 controllers are high-speed, single-slot controllers you can use for control and information processing. PLC-5 controllers are designed for larger sequential and regulatory control applications with specialized I/O requirements and/or the need to coordinate with other controllers and devices. PLC-5 controllers come with different memory sizes and network connections. The Enhanced PLC-5 controllers offer a standard set of functions and communication options. The other PLC-5 controllers offer different communication options, while maintaining the same functions. Choose the controller that best meets your needs.

Publication 1785-SG001B-EN-P - June 2006

If your application requires

Select from

• Connectivity to a large number of Remote I/O devices • Connectivity to a large number of DH+ devices

Enhanced PLC-5 Controllers see page 32

• EtherNet/IP connectivity • Communication with other Ethernet PLC-5 controllers and host computers

Ethernet PLC-5 Controllers see page 33

• High-speed communication for control and information processing • Deterministic, repeatable data transfers • ControlNet connectivity

ControlNet PLC-5 Controllers see page 34

• Limited access to critical or proprietary areas of programs • Selectively access to processor memory and I/O elements • Restricted use of processor operations

Protected PLC-5 Controllers see page 35

Page 34

32

Select Controllers

Enhanced PLC-5 Controllers Every PLC-5 controller offers built-in, configurable ports for Data Highway

Plus (DH+) or Remote I/O. A DH+ connection supports remote programming and information access, in addition to peer-to-peer communication between the PLC-5, other controllers, and devices. A Remote I/O connection supports real-time data exchange for I/O, operator interface, and other third-party devices.

Cat. No.

User Memory (words), Max

Total I/O, Max

1785-L11B

8000

512 any mix or 384 in + 384 out (complement)

1785-L20B

16,000

1785-L30B

Channels

Number of I/O Chassis, Max

Power Backplane Dissipation, Current ControlNet Max Load

Total

Extended Remote -local

1 DH+/remote I/O

5

0

4

0

12 W

2.3 A

512 any mix or 512 in + 512 out (complement)

1 DH+ 1 DH+/remote I/O

13

0

12

0

12 W

2.3 A

32,000

1024 any mix or 1024 in + 1024 out (complement)

2 DH+/remote I/O

29

0

28

0

12 W

2.3 A

1785-L40B

48,000

2048 any mix or 2048 in + 2048 out (complement)

4 DH+/remote I/O

61

0

32 max/link

0

17.3 W

3.3 A

1785-L60B

64,000

3072 any mix or 3072 in + 3072 out (complement)

4 DH+/remote I/O

93

0

32 max/link

0

17.3 W

3.3 A

1785-L80B

100,000

3072 any mix or 3072 in + 3072 out (complement)

4 DH+/remote I/O

93

0

32 max/link

0

17.3 W

3.3 A

Publication 1785-SG001B-EN-P - June 2006

Page 35

33

Select Controllers

Ethernet PLC-5 Controllers

The Ethernet PLC-5 controller integrates the Allen-Bradley architecture into an industry-standard EtherNet/IP system, offering a flexible and open solution. With the Ethernet PLC-5 controller’s built-in communication capabilities, your entire enterprise can use standard Ethernet or Internet connectivity to control and monitor production. Using the Internet and Web browser, you can create your own custom Web pages to provide executive summaries of process information. These pages are accessible to any Internet user who has network access to the PLC-5 controller. The embedded Web server provides access to PLC-5 diagnostics. Domain Name Service (DNS) and Simple Network Management Protocol (SNMP) are also supported.

Cat. No.

User Memory (words), Max

Total I/O, Max

1785-L20E

16,000

512 any mix or 512 in + 512 out (complement)

1785-L40E

48,000

1785-L80E

100,000

Total

Extended -local

Remote

Power Backplane Dissipation, Current ControlNet Max Load

1 Ethernet 1 DH+ 1 DH+/remote I/O

13

0

12

0

19 W

3.6 A

2048 any mix or 2048 in + 2048 out (complement)

1 Ethernet 2 DH+/remote I/O

61

0

60

0

19 W

3.6 A

3072 any mix or 3072 in + 3072 out (complement)

1 Ethernet 2 DH+/remote I/O

65

0

64

0

19 W

3.6 A

Publication 1785-SG001B-EN-P - June 2006

Channels

Number of I/O Chassis, Max

Page 36

34

Select Controllers

The ControlNet PLC-5 controller offers embedded ControlNet communication capabilities for control and information processing. The ControlNet network provides both I/O control and peer-to-peer communications on a 5 Mbps network, with repeatability and determinism.

ControlNet PLC-5 Controllers

You can have multiple ControlNet PLC-5 controllers on one ControlNet network, with each controller handling its own I/O on the network, and at the same time communicating with each other. Multiple controllers can receive input data from one I/O or device node.

Cat. No.

User Memory (words), Max

Total I/O, Max

1785-L20C15

16,000

512 any mix or 512 in + 512 out (complement)

1785-L40C15

48,000

1785-L46C15 Protected 1785-L80C15

Total

Extended Remote -local

ControlNet Power Backplane I/O Map Dissipation, Current Entries Max Load

1 ControlNet 1 DH+ 1 DH+/remote I/O

77

0

12

64

15.8 W

3.0 A

2048 any mix or 2048 in + 2048 out (complement)

1 ControlNet 2 DH+/remote I/O

125

0

60

96

15.8 W

3.0 A

48,000

2048 any mix or 2048 in + 2048 out (complement)

1 ControlNet 2 DH+/remote I/O

125

0

60

96

15.8 W

3.0 A

100,000

3072 any mix or 3072 in + 3072 out (complement)

1 ControlNet 2 DH+/remote I/O

125

0

92

128

15.8 W

3.0 A

Publication 1785-SG001B-EN-P - June 2006

Channels

Number of I/O Chassis, Max

Page 37

35

Select Controllers

Protected PLC-5 Controllers The Protected PLC-5 controller lets you limit access to critical or proprietary areas of programs, selectively guard controller memory and I/O, or restrict use of controller operations. The distinctive safety-yellow labels on the controller identify the protected PLC-5 controller. Use the programming software to assign class privileges to specific user accounts or a user’s job function, such as system administrator, plant engineer, maintenance engineer, or operator. Using four privilege classes and associated passwords, you can limit access to critical areas of programs and restrict access to: • communication channels. • remote nodes attached to the ControlNet or DH+ network. • program files. • data files. The protected PLC-5 controller expands system validity and security beyond that provided by the password-and-privilege feature of the other PLC-5 controllers. The Rockwell Automation clutch/brake application package combines the protected PLC-5 controller with specially-designed software to support stamping press applications.

Cat. No.

User Memory (words), Max

Total I/O, Max

1785-L26B

16,000

512 any mix or 512 in + 512 out (complement)

1785-L46B

48,000

1785-L46C15 Protected 1785-L86B

Channels

Number of I/O Chassis, Max

ControlNet Power Backplane I/O Map Dissipation, Current Entries Max Load

Total

Extended Remote -local

1 DH+ 1 DH+/remote I/O

13

0

12

0

12 W

2.3 A

2048 any mix or 2048 in + 2048 out (complement)

4 DH+/remote I/O

61

0

32 max/link

0

17.3 W

3.3 A

48,000

2048 any mix or 2048 in + 2048 out (complement)

1 ControlNet 2 DH+/remote I/O

125

0

60

96

15.8 W

3.0 A

100,000

3072 any mix or 3072 in + 3072 out (complement)

4 DH+/remote I/O

93

0

32 max/link

0

17.3 W

3.3 A

Publication 1785-SG001B-EN-P - June 2006

Page 38

36

Back Up Controller Memory You can back up program files using an EEPROM module. Cat. No. (1)

1785-ME16 1785-ME32 1785-ME64 1785-CHBM

Provides this amount of backup memory 16,000 words 32,000 words 64,000 words 100,000 words

(1)Not for use with ControlNet PLC-5 controllers.

Battery Replacement and Life Estimates Cat. No.

Applies to

When used in this controller

At this temperature

1770-XYC

All PLC-5 Programmable Controllers

PLC-5/11, -5/20 and -5/20E

60 oC (140 oF)

Battery Life Estimate Power off 100% Power off 50% 256 days 1.4 years

25 oC (77 oF)

2 years

4 years

60 oC (140 oF)

84 days

150 days

25 oC (77 oF)

1 year

1.2 years

All Others