Page 1 of TTL Output Module, Cat. No. 1771-OG, Installation Instructions

Manual · Allen-Bradley

TTL Output Module, Cat. No. 1771-OG, Installation Instructions

Manual8 pagesPDF 160 KB

Installation instructions for the Allen-Bradley 1771-OG TTL output module: power, logic level setting, keying, wiring and specs.

Download the PDF160 KB

Names · 1 model

The models it names

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Allen-Bradley installation instructions for the 1771-OG TTL output module for the 1771 I/O chassis. They cover preinstallation considerations, backplane and customer +5V dc power requirements, electrostatic discharge handling, selecting HIGH = TRUE or LOW = TRUE logic with the internal switches, keying the chassis, installing the module, wiring with the 1771-WC field wiring arm and shielded cable, driving inputs with outputs, the status indicators and the module specifications.

Its parts

  1. To The Installer
  2. Pre installation Considerations
  3. Power Requirements
  4. Initial Handling
  5. Installing Your Module
  6. Interpreting the Status Indicators
  7. Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Allen-Bradley installation instructions for the 1771-OG TTL Output Module, publication 1771-2.177 from January 1994. It explains the power the module needs, how to choose high-true or low-true logic, key the chassis, install the module, wire and ground the output cable, and read the status indicators, and it ends with the specifications. The 1771-OGC is not named in it.

Module
TTL output module, 8 outputs, for a 1771 I/O chassis p. 8
Logic levels
HIGH = TRUE: 2.0 to 5.25V dc is on; LOW = TRUE: -0.2 to 0.8V dc is on; set by switch SW1 p. 2
Output current
Source 1mA, sink 20mA max.; open-collector outputs with internal 1K pull-up resistors p. 6, 8
Customer supply
Separate +5(+0.25)V dc supply, 250mA, ripple 50mV peak to peak max. p. 1
Backplane current
168mA from the chassis power supply p. 1, 8
Output signal delay
Less than 1ms p. 8
Field wiring arm
1771-WC, shipped with the module p. 4
Cable
Belden 8761 shielded cable, at most 50 cable feet per output device p. 6
Keying
Keying bands between 6 and 8 and between 10 and 12 on the upper backplane connector p. 3
Status indicators
Nine: a HIGH = TRUE indicator and eight output indicators p. 7
Driving TTL inputs
Outputs may drive a 1771-IG TTL input module directly p. 6
Power dissipation
2.2 Watts max., 0.8 Watts min. (7.5 BTU/hr max., 2.7 BTU/hr min.) p. 8
Isolation
Tested at 1500V ac (rms) for 1 second p. 8
Compatible devices
Any TTL device with input levels of -0.2V dc to +0.8V dc (low) and 2.0V dc to 5.25V dc (high) p. 1

What this manual walks you through

  • Choosing high-true or low-true logic with the internal switches p. 2, 3
  • Keying an I/O chassis slot for the module p. 3
  • Installing the module in a Series A or Series B chassis p. 4
  • Attaching the field wiring arm p. 4
  • Preparing and grounding the Belden 8761 cable shield p. 5
  • Wiring TTL output devices and the signal return p. 6
  • Reading the status indicators p. 7
  • Handling the module without electrostatic damage p. 2

Good to know

  • Turn off power to the I/O chassis backplane and field wiring arm before removing or installing the module. p. 4
  • Do not apply ac or reverse dc voltage to the module terminals. p. 4
  • When driving a 1771-IG, connect the cable shield at one end only. p. 6
  • Add the 168mA backplane draw to the other modules' needs so the chassis supply is not overloaded. p. 1
  • The indicators may look dim when outputs pulse rapidly. p. 7

Questions this manual answers

How do I set a 1771-OG for low-true logic?

Remove the side cover and set SW1 off and SW2 on; then -0.2 to 0.8V dc means logic 1 (on). p. 2, 3

What power supply does the 1771-OG need?

A separate +5V dc supply that gives 250mA with no more than 50mV ripple, plus 168mA from the chassis backplane. p. 1

How long can the 1771-OG output cable be?

No more than 50 cable feet to any output device, using Belden 8761 shielded cable. p. 6

Can a 1771-OG drive a 1771-IG input module?

Yes. Its outputs may directly drive the inputs of a 1771-IG TTL input module, with the shield connected at one end only. p. 6

How much current can each 1771-OG output handle?

Up to 1mA source and 20mA sink. p. 8

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1771-2.177, TTL Output Module Installation, Instructions1
  2. To The Installer1
  3. Pre installation Considerations1
  4. Power Requirements1
  5. Initial Handling2
    1. Electrostatic Discharge Damage2
  6. Installing Your Module2
    1. Selecting the Logic Level2
    2. Keying Your I/O Chassis3
    3. Installing the Output Module4
    4. Connecting Wiring to the Output Module4
    5. Driving Inputs with Outputs6
  7. Interpreting the Status Indicators7
  8. Specifications8
  9. Back Cover8

From the PDF’s own bookmarks.

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8

The file