Page 1

AC (24V) Output Module Cat. No. 1771-OND Installation Instructions

To The Installer

This document provides information on: important pre-installation considerations power supply requirements installing the module setting the fault mode using the indicators for troubleshooting replacing the fuses module specifications

Pre-installation Considerations

This module must be used with a 1771-A1B thru -A4B or later I/O chassis. If you are using a 1771-ASB remote I/O adapter you may use any combination of I/O modules. Otherwise, make sure no other output module or single card block transfer module is placed in the same I/O group.

Power Requirements

Your module receives its power through the 1771 I/O chassis backplane from the chassis power supply. The module requires 700mA from the output of this supply. Add this to the requirements of all other modules in the I/O chassis to prevent overloading the chassis backplane and/or backplane power supply.

Page 2

Installation Instructions AC (24V) Output Module Cat. No. 1771-OND

Initial Handling

The ac output module is shipped in a static-shielded bag to guard against electrostatic discharge damage. Observe the following precautions when handling the module.

Electrostatic Discharge Damage ATTENTION: Under some conditions, electrostatic discharge can degrade performance or damage the module. Observe the following precautions to guard against electrostatic damage.

Wear an approved wrist strap grounding device, or touch a grounded object to discharge yourself before handling the module. Do not touch the backplane connector or connector pins. If you configure or replace internal components, do not touch other circuit components inside the module. If available, use a static-free work station. When not in use, keep the module in a static-shielded bag.

Installing Your Module

In this section we tell you how to set the fault mode selection plug, key your I/O chassis, install your module and make your wiring connections.

Fault Mode Selection You may select one of two output-failure configurations (last state or reset) by positioning a configuration plug on the bottom edge of the printed circuit board. This configuration plug is independent of the last state switch on the I/O chassis backplane. To set the fault mode selection, proceed as follows: 1.

Locate the fault mode selection plug at the bottom edge of the module circuit board (Figure 1).

Figure 1 Fault Mode Selection Plug

LS Bottom edge of circuit board

2

RESET Fault Mode Selection Plug (shown in last state position)

10673-I

2.

Using your finger, slide the plug off the two posts.,

3.

Carefully position the plug on two of the three posts that correspond to your requirement.

Page 3

Installation Instructions AC (24V) Output Module Cat. No. 1771-OND

Keying Your I/O Chassis Use the plastic keying bands, shipped with each I/O chassis, to key the I/O slots to accept only this type of module. The module circuit board is slotted in two places on the rear edge. The position of the keying bands on the backplane connector must correspond to these slots to allow insertion of the module. You can key any connector in an I/O chassis to receive this module except for the left-most connector reserved for adapter or processor modules. Place keying bands between the following numbers labeled on the backplane connector: Between 20 and 22 Between 32 and 34 You can change the position of these keys if system redesign and rewiring makes insertion of a different module necessary.

Installing the Output Module To install the ac output module in your 1771 I/O chassis, follow the steps listed below. ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or installing an I/O module. Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

1.

Turn off power to the I/O chassis.

2.

Place the module in the plastic tracks on the top and bottom of the slot that guides the module into position.

3.

Do not force the module into its backplane connector. Apply firm, even pressure on the module to seat it properly.

4.

Snap the chassis latch over the top of the module to secure its position.

5.

Connect the wiring arm to the module.

6.

Make wiring connections to the field wiring arm as indicated in Figure 2. 3

Page 4

Installation Instructions AC (24V) Output Module Cat. No. 1771-OND

Connecting Wiring to the Output Module Connections to the output module are made to the field wiring arm (cat. no. 1771-WH) shipped with the module. An optional fused wiring arm is available (cat. no. 1771-WHF) which provides individual fusing for each circuit. Attach the wiring arm to the pivot bar on the bottom of the I/O chassis. The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires. You must supply ac (L1) at terminals A through D on the wiring arm. You need four ac connections to accommodate the total required surge rating on the module without overstressing any single connection on the field wiring arm. Jumper all ac (L1) connections together to prevent module damage. Figure 2 Connection Diagram

L1 24V ac Terminal A Terminal B Terminal C Terminal D Output 00 Output 01 Output 02 Output 03 Output 04 Output 05 Output 06 Output 07 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Output 17 Terminal E

A B C D 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 E

(Actual wiring runs in this direction.) 4

Output Device

L2 ac Low

10674-I

Page 5

Installation Instructions AC (24V) Output Module Cat. No. 1771-OND

Important: You can use an AC (24V) Output Module (cat. no. 1771-OND) to directly drive terminals on an AC (24V) Input Module (cat. no. 1771-IND) (Figure 3). You can also use a 1771-OND Output module to drive an AC (24V) Input Module (cat. no. 1771-IN) but you must connect a 250 ohm, 5W resistor between the output terminal and L2 (common) as shown in Figure 3. Use the same ac power source to power both modules to ensure proper phasing and prevent module damage. Figure 3 Driving an Input Module with an Output Module AC (24V) Input Module (Cat. No. 1771-IND)

AC (24V) Output Module (Cat. No. 1771-OND)

AC (24V) Output Module (Cat. No. 1771-OND)

AC (24V) Input Module (Cat. No. 1771-IN)

L1 24V ac High

L1 24V ac High

250 ohm 5W resistor L2

L2 ac Low Note: 1771-OND output voltage range is 10-60V ac. However, the on-state voltage range of the 1771-IND is 19-29V ac.

L2 ac Low Note: 1771-OND output voltage range is 10-60V ac. However, the on-state voltage range of the 1771-IN is 12-28V ac. 10675-I

5

Page 6

Installation Instructions AC (24V) Output Module Cat. No. 1771-OND

Interpreting the Status Indicators

The front panel of your module contains one green, module active indicator, and 16 red status indicators (Figure 4). The 1771-OND performs diagnostics in a handshaking mode when first powered up. Upon successful completion of the diagnostics, the green module active indicator lights. It turns off if a fault occurs in the data paths or the opto-isolators. The red status indicators are provided for system logic side indication of individual inputs. When a red indicator lights, voltage is present on the terminal. The module transfers this information to the backplane for the processor to read.

Figure 4 Status Indicators

Module Active Indicator (green) ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17

00 to 17 Status Indicators (red)

10676-I

6