Manual · Allen-Bradley
AC (24V) Output Module Cat. No. 1771-OND Installation Instructions
Manual12 pagesPDF 118 KB
Installation instructions for the Allen-Bradley 1771-OND AC (24V) output module: fault mode, keying, wiring, fuses and specifications.
What this file really is
The old site listed this file as a manual for the Allen-Bradley 1771-OFC, 1771-ON and 1771-OND. Linked as a 1771-ON manual, this is the installation instructions for the 1771-OND AC (24V) output module; it does not mention the 1771-ON or 1771-OFC.
Names · 1 model
The models it names
Filed with · 2 models
Also filed with these models on the old site
Summary
What is in it
Allen-Bradley installation instructions for the 1771-OND AC (24V) output module, a 16-output module for the 1771 I/O chassis. It covers pre-installation considerations and power requirements, handling to avoid electrostatic damage, setting the fault mode plug, keying the chassis, installing and wiring the module (including driving 1771-IND and 1771-IN input modules), reading the status indicators, replacing the fuse, troubleshooting and specifications.
Its parts
- To The Installer
- Pre installation Considerations
- Power Requirements
- Initial Handling
- Installing Your Module
- Interpreting the Status Indicators
- Replacing the Fuse
- Troubleshooting
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Installation instructions (publication 1771-2.118, April 1994) for the Allen-Bradley 1771-OND AC (24V) output module, a 16-output module for the 1771 I/O chassis. The document covers only the 1771-OND; it does not describe the 1771-ON or 1771-OFC it is also filed under. It shows how to set the fault mode, key the chassis, install and wire the module, read the indicators, replace the fuse and track down a faulty output.
- Outputs
- 16 AC (24V) outputs p. 1, 12
- Output voltage
- 10 to 60V ac at 47 to 63Hz p. 12
- Output current
- 2A per output, not to exceed 8A per module p. 12
- Surge current
- 25A per output for 100ms, repeatable every 1 second p. 12
- Backplane current
- 700mA at 5V dc p. 1, 12
- Compatible chassis
- 1771-A1B thru -A4B or later I/O chassis; 1771-AM1, -AM2 p. 1, 12
- Minimum load
- 50mA per output at 24V ac, 60Hz p. 12
- On and off state
- On-state voltage drop 1.6V at 2A maximum; off-state leakage 3mA per output at 24V ac maximum p. 12
- Power dissipation
- 16.5 Watts maximum, 3.7 Watts minimum p. 12
- Isolation
- Tested at 1500V ac (rms) for 1s p. 12
- Fuse
- 10A, 250V rectifier fuse (1/4 x 1-1/4 inch), Littelfuse 322010 p. 7, 12
- Field wiring arm
- 1771-WH shipped with the module; optional fused 1771-WHF with a fuse for each circuit p. 4
- Keying
- Between 20 and 22, and between 32 and 34 p. 3, 12
- Wiring
- 14 gauge stranded maximum, 3/64 inch insulation maximum; arm screws 7-9 inch-pounds p. 12
What this manual walks you through
- Setting the fault mode plug to last state or reset p. 2
- Keying the I/O chassis slot for this module p. 3
- Installing the module in a 1771 I/O chassis p. 3
- Wiring the outputs on the field wiring arm p. 4
- Driving a 1771-IND or 1771-IN input module from this output module p. 5
- Reading the module active and output status indicators p. 6
- Replacing the fuse p. 7
- Finding a faulty output with internal or external fuses p. 7, 8, 9
Good to know
- Unless a 1771-ASB remote I/O adapter is used, no other output module or single card block transfer module may share the I/O group. p. 1
- All four ac (L1) connections on terminals A through D must be jumpered together to prevent module damage. p. 4
- Driving a 1771-IN input module needs a 250 ohm, 5W resistor between the output terminal and L2, with both modules on the same ac source. p. 5
- Remove power from the chassis backplane and wiring arm before removing or installing the module. p. 3
- The 700mA backplane load must be added to the other modules in the chassis to avoid overloading the power supply. p. 1
Questions this manual answers
How many outputs does the 1771-OND have?
16 outputs, rated 2A per output and no more than 8A per module. p. 12
What fuse does the 1771-OND take?
A 10A, 250V rectifier fuse, 1/4 x 1-1/4 inch, Littelfuse part number 322010. p. 7
Can a 1771-OND drive a 1771-IN input module?
Yes, with a 250 ohm, 5W resistor between the output terminal and L2. It can drive a 1771-IND input module directly. p. 5
Which I/O chassis does the 1771-OND work in?
A 1771-A1B thru -A4B or later I/O chassis; the specifications also list the 1771-AM1 and -AM2. p. 1, 12
How much backplane current does the 1771-OND draw?
700mA from the chassis power supply through the backplane. p. 1
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 2 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file


