The text of a manual · part 2 of 2
AC (24V) Output Module Cat. No. 1771-OND Installation Instructions, pages 7 to 12
Pages 7 to 12 of 12
The original document is the PDF (118 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-OND
Page 7
Installation Instructions AC (24V) Output Module Cat. No. 1771-OND
Replacing the Fuse
The module’s output circuitry is protected from overload or shorts by a fuse. You can replace the fuse as outlined below. 1.
Turn off all power to the I/O chassis and all output device power to the field wiring arm. ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or installing the module. Failure to remove power from the backplane or field wiring arm could cause module damage, degradation of performance, or injury. Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.
Troubleshooting
2.
Pivot the wiring arm away from the module and remove the module from the chassis.
3.
Replace the blown fuse with a 10A, 250V rectifier fuse (1/4 x 1-1/4 inch), Littelfuse part number 322010.
4.
Replace the module in the chassis and attach the field wiring arm.
If a problem occurs, follow the procedure listed below.
Modules with Internal Fuses Only 1.
Turn off all power to the I/O chassis and all output device power to the field wiring arm. ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or installing the module. Failure to remove power from the backplane or field wiring arm could cause module damage, degradation of performance, or injury. Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.
7
Page 8
Installation Instructions AC (24V) Output Module Cat. No. 1771-OND
2.
Pivot the wiring arm away from the module and remove the module from the chassis.
3.
Replace the blown fuse with a 10A, 250V rectifier fuse (1/4 x 1-1/4 inch), Littelfuse part number 322010.
4.
Replace the module in the chassis and attach the field wiring arm.
5.
Turn OFF all outputs to the module.
6.
Turn ON power to the I/O chassis only.
7.
Check that the red status indicators on the front of the module (Figure 4) are off (no outputs on). Make sure the red fuse blown indicator is off.
8.
Turn on output device power to the field wiring arm.
9.
Start with bit 00 and turn on individual outputs one at a time. Turn off the previous output before turning on the next output.
10. If the red fuse blown indicator turns on, note which output is faulty and trace the output wiring to the faulty device. After correcting the fault problem, return to step 1 and begin again. If you cannot locate a faulty output, return to step 9 and turn on 2 or more outputs at the same time. Total output current should not exceed 2A per output, or 8A total per module.
Modules with External Fuses Only
8
1.
Turn off all power to the I/O chassis and all output device power to the field wiring arm.
2.
Pivot the wiring arm away from the module.
3.
Use a continuity checker (meter in low ohms setting) to check fuses for an open (high resistance) reading.
4.
Note if fuse is open and trace the output wiring back to the output device.
5.
Check the remaining fuses (refer to step 3).
6.
After all faulty fuses are replaced and any wiring problems solved, reposition the wiring arm on the module.
7.
Turn off all outputs to the module.
8.
Turn on power to the I/O chassis.
Page 9
Installation Instructions AC (24V) Output Module Cat. No. 1771-OND
9.
Check that the red status indicators on the front of the module are off (no outputs on). Make sure the red fuse blown indicator is off.
10. Turn on output device power to the wiring arm. 11. Start with bit 00 and turn on individual outputs one at a time. Turn off last output before turning on the next output. 12. If the red fuse blown indicator lights, note which output is faulty and trace the output wiring to the faulty device. After correcting the fault problem, return to step 1 and begin again. If you cannot locate a faulty output, return to step 8 and turn on 2 or more outputs at the same time. Total output current should not exceed 2A per output, or 8A per module.
9
Page 10
Installation Instructions AC (24V) Output Module Cat. No. 1771-OND
10
Page 11
Installation Instructions AC (24V) Output Module Cat. No. 1771-OND
11
Page 12
Installation Instructions AC (24V) Output Module Cat. No. 1771-OND
Specifications
Outputs per Module
16
Module Location
17711-A1B thru -A4B or later I/O chassis; 1771-AM1, -AM2
Output Voltage Range
10 to 60V ac @ 47 - 63Hz
Output Current Rating
2A per output - not to exceed 8A per module
Surge Current (maximum)
25A per output for 100ms, repeatable every 1 second 25A per module for 100ms, repeatable every 1 second
Minimum Load Current
50mA per output @ 24V ac, 60Hz
On State Voltage Drop (max.)
1.6V at 2A
Off State Leakage Current (max.)
3mA per output @ 24V ac
Signal Delay
Off to On On to Off
1.0ms; 8.3 to 9.1ms @ 60Hz
Power Dissipation
16.5 Watts (max.), 3.7 Watts (min.)
Thermal Dissipation
56.2 BTU/hr (max.), 12.6 BTU/hr (min.)
Backplane Current
700mA @ 5V dc +5%
Isolation Voltage
Tested at 1500V ac (rms) for 1s
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)
Conductors
Wire Size Category
14 gauge stranded maximum 3/64 inch insulation maximum 11
Keying
Between 20 and 22 Between 32 and 34
Fuse
10A, 250V rectifier fuse (1/4 x 1-1/4 inch), Littelfuse PN 322010
Field Wiring Arm
Standard Optional
Wiring Arm Screw Torque
Catalog Number 1771-WH Catalog Number 1771-WHF (fused) 7-9 inch-pounds
1 Refer to publication 1770-4.1, Programmable Controller Wiring and Grounding Guidelines.
Allen-Bradley has been helping its customers improve productivity and quality for 90 years. A-B designs, manufactures and supports a broad range of control and automation products worldwide. They include logic processors, power and motion control devices, man-machine interfaces and sensors. Allen-Bradley is a subsidiary of Rockwell International, one of the world's leading technology companies.
With major offices worldwide. Algeria • Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • New Zealand • Norway • Oman • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Switzerland • Taiwan • Thailand • The Netherlands • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia World Headquarters, Allen-Bradley, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
12 Publication 1771-2.118 - April 1994 Supersedes publication 1771-2.118 - April 1990
P/N 955112-19
Copyright 1994 Allen-Bradley Co. Inc. Printed in USA