Manual · Allen-Bradley
Power Supply Modules Cat. No. 1771-P3, P4, P5 and P5E Installation Instructions
Manual12 pagesPDF 114 KB
Installation instructions for the Allen-Bradley 1771-P3, 1771-P4, 1771-P5 and 1771-P5E power supply modules for 1771 I/O chassis.
Covers · 1 model
The models it covers
Summary
What is in it
Allen-Bradley installation instructions for the 1771-P3, -P4, -P5 and -P5E power supply modules used in series A and B 1771 I/O chassis. They cover chassis and processor compatibility, available backplane current, input power wiring, the 1771-P5E power loss time delay jumper, installing and paralleling supplies with the 1771-CT cable, the P/S ACTIVE indicator, step-by-step troubleshooting and specifications.
Its parts
- To The Installer
- Preinstallation Considerations
- Connecting Input Power
- Paralleling Power Supplies
- Module Indicators
- Troubleshooting
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Installation instructions for Allen-Bradley 1771 I/O chassis power supply modules, covering the 1771-P3, -P4, -P5 and -P5E. They explain where each module may sit in series A and B chassis, how to wire input power, parallel two supplies, read the status indicator and troubleshoot a supply or its paralleling cable.
- What it is
- 1771-P4: 2-slot power supply module for 1771 I/O chassis p. 1
- Input voltage
- 1771-P4: 120V ac (97-132V ac) p. 3
- Output current
- 1771-P4: up to 8A @ 5V p. 3
- Paralleling cable
- 1771-CT power supply paralleling cable p. 3, 7
- Parallels with
- 1771-P4: another 1771-P3 or -P4, or a 1772-LSP, -LWP or -LXP processor p. 7
- Status indicator
- Green P/S ACTIVE light p. 8
- Self-protection
- Shuts down on overvoltage, undervoltage or overcurrent p. 8
- Restart wait
- 1771-P4: off at least 15 seconds after a shutdown p. 8
- Input dropout
- 1771-P4: indicator turns off below 97V ac (for 13.6+2.96ms) p. 8
- Input terminals
- 1771-P4: L1 at top, neutral (N) in the middle, GND at bottom to the ground bus p. 6
- Series B chassis slot
- Any slot except the left-most, which is reserved for the processor p. 1
- Publication
- 1771-2.111, February 1994 p. 12
What this manual walks you through
- Placing a power supply in a series A or series B 1771 I/O chassis p. 1
- Matching power supplies with processors and adapters p. 2
- Setting the 1771-P5E power loss time delay jumper p. 4
- Installing the power supply in the I/O chassis p. 5, 6
- Making input power connections p. 6
- Paralleling two power supply modules p. 7, 8
- Reading the P/S ACTIVE indicator p. 8
- Troubleshooting a supply that does not come on p. 9, 10
- Checking the 1771-CT paralleling cable for an open or short p. 10, 11
Good to know
- Paralleling two modules does not give redundancy, even with different power sources. p. 7
- Two paralleled supplies must be turned on at the same time, or the first may shut down on overcurrent. p. 8
- During power-up or power-down, outputs of certain older discrete output modules may briefly change state. p. 3
- Turn the supply and the I/O chassis power off before inserting the module. p. 5
- Route the paralleling cable around the top of the I/O chassis to avoid induced voltages. p. 7
Questions this manual answers
What input voltage does the 1771-P4 need?
The 1771-P4 takes 120V ac, within 97 to 132V ac. p. 3
How much current does the 1771-P4 supply?
Up to 8A at 5V. p. 3
What cable parallels two 1771 power supplies?
The 1771-CT power supply paralleling cable, run between the P/S Parallel ports of the two modules. p. 7
Why did the P/S ACTIVE light on my 1771-P4 go out?
The module shuts down on overvoltage, undervoltage or overcurrent; the light also goes out if the input drops below 97V ac. p. 8
How long should a 1771-P4 stay off before restarting?
At least 15 seconds after a shutdown. p. 8
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 2 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file