For the Allen-Bradley 1771-P4

Page 7

Installation Instructions Power Supply Modules Cat. No. 1771-P3, -P4, -P5 and -P5E

Paralleling Power Supplies

The power supply modules are designed to operate in parallel with: another 1771-P3, -P4, -P5 or -P5E power supply (Note: The 1771-P5, -P5E power supplies are designed to operate in parallel only with another 1771-P5.) a 1772-LSP, -LWP or -LXP processor Note: Paralleling two modules, even when using different power sources, does not provide redundancy. To parallel two modules, proceed as follows: 1.

Make certain that both power supply module power switches are off.

2.

Connect the power supply paralleling cable (cat. no. 1771-CT) from the P/S Parallel port on the first power supply module to the P/S Parallel port on the second module. Note: Route the cable around the top of the I/O chassis to avoid induced voltages.

Figure 3 Paralleling Two Power Supply Modules

Power Supply Paralleling Cable Cat. No. 1771-CT

P/S ACTIVE

P/S ACTIVE

P/S Parallel

P/S Parallel

24V dc POWER ON

24V dc POWER ON

OFF

OFF

5A 32V NORM BLOW

5A 32V NORM BLOW

24V DC

24V DC

+DC

+DC

COM

COM

GND

GND dc Positive dc Negative

24V dc

Ground Bus 12230-I

7

Page 8

Installation Instructions Power Supply Modules Cat. No. 1771-P3, -P4, -P5 and -P5E

3.

Turn on both power supplies simultaneously. ATTENTION: To avoid driving the first of two paralleled power supplies into an overcurrent condition that would shutdown the module, you must simultaneously turn on both power supplies.

Module Indicators

The power supply module has a green indicator light (labeled P/S ACTIVE). It indicates the operating condition of the module, and can be used for diagnosing faults. The module monitors itself for: overvoltage undervoltage overcurrent Any of these conditions will shut down the power supply. Following a shutdown, turn the power supply off for at least 15 seconds (-P3 and -P4) or 45 seconds (-P5, -P5E) before you turn it on again.

If the P/S ACTIVE Indicator

Then:

is on

Normal operation. The indicator lights as long as the module is supplied with power even if it is not seated in its chassis slot.

None required.

is off

The module is turned off.

Turn the module on.

turns off

The input voltage to the supply could be below: 97V ac (for 13.6+2.96ms) for a -P3 or -P4 power supply. 20.5V dc (for 13.6+2.96ms) for a -P5 or -P5E power supply.

Allow input power to recover to: 97V ac or above for a -P3 or -P4 power supply 20.5V dc or above for a -P5 or -P5E power supply turns off and shuts down

The dc output has an overvoltage or overcurrent condition.

turns off and a paralleled The ac input voltage to one of the paralleled power power supply shuts supplies has failed due to loose wire, blown fuse, or down the supply has been shut off. remains off and at least one power supply shuts down

8

Corrective Action

The two supplies were not turned on simultaneously.

1. Turn the power supply off. 2. Wait 15 seconds (-P3 or -P4) or 45 seconds for a -P5 or -P5E.

3. Turn the power supply on.

Page 9

Installation Instructions Power Supply Modules Cat. No. 1771-P3, -P4, -P5 and -P5E

Troubleshooting

Follow the procedure below to isolate and correct possible faults. 1.

Turn the power supply off and wait at least 15 seconds (-P3 and -P4) or 45 seconds (-P5, -P5E) before you turn it on again.

2.

Turn the power supply on.

3.

If the system operates properly, you are finished. If the indicator does not turn on, turn the power supply off and wait 15 seconds (-P3 and -P4) or 45 seconds (-P5, -P5E).

4.

Remove the paralleling cable (if equipped) to verify independent operation of each power supply. ATTENTION: Remove input power to the I/O chassis before removing the power supply module from the chassis. Failure to do this may result in injury to personnel and/or damage to equipment.

5.

Pull the power supplies halfway out of the chassis to test them under no load conditions.

6.

Turn on one power supply.

If the P/S ACTIVE indicator is:

Then:

On

One or more of the following has occurred: - Input voltage was not within acceptable limits - Backplane is overloaded or has a short circuit. Add up the backplane currents of all modules. Verify power supply limits have not been exceeded. - Check for fault in paralleling cable (if used). - Internal power supply could have faulted.

Off

Verify that input voltage is within acceptable limits. If input voltage is correct, replace the power supply.

7.

If you have two power supplies in your chassis, repeat step 6 for the other power supply.

8.

If you have only one power supply in your chassis and it passed step 7 (the P/S ACTIVE light turned on), verify that the power supply is not overloaded by performing steps 9 through 11.

9.

Turn the power supply off and wait 15 seconds (-P3 and -P4) or 45 seconds (-P5, -P5E).

10. Firmly seat the power supply in the chassis.

9

Page 10

Installation Instructions Power Supply Modules Cat. No. 1771-P3, -P4, -P5 and -P5E

11. Restore power to the I/O chassis, and turn the power supply module on. If the P/S ACTIVE indicator is:

Then:

On

The power supply is operating correctly and the system should operate normally.

Off

Replace the power supply module with a known good operating supply. The system should operate normally.

Checking for Open or Shorted Paralleling Cable Important: Continue with this procedure only if you are using two power supply modules in the same chassis. This procedure checks for an open or shorted 1771-CT paralleling cable. Before you begin, turn I/O chassis power off. Both power supply modules should be turned off and partially pulled out of the chassis. ATTENTION: Remove input power to the I/O chassis before removing the power supply module from the chassis. Failure to do this may result in injury to personnel and/or damage to equipment.

1.

Test the 1771-CT paralleling cable by verifying the ground connection between power supplies.

2.

Test for a short circuit by performing steps 3 through 5.

3.

Plug one end of the paralleling cable into one of the power supply modules (the other end should not be connected).

4.

Turn the power supply on. If the P/S ACTIVE indicator turns on this end of the cable is okay.

5.

Unplug the cable, and plug the other end of the cable into the power supply.

If the P/S ACTIVE indicator : Turns On Does not turn On

6.

10

Then: This end of the cable is all right. The paralleling cable has a short circuit. Replace the cable.

Perform steps 7 through 9 to test for an open circuit in the paralleling cable.

Page 11

Installation Instructions Power Supply Modules Cat. No. 1771-P3, -P4, -P5 and -P5E

7.

Turn both power supply modules off. Connect the paralleling cable to each supply.

8.

Turn one power supply module on. The P/S ACTIVE indicators on both supplies should not turn on.

9.

Turn the first power supply off and the other power supply module on. The P/S ACTIVE indicators on both supplies should not turn on. If either of the P/S ACTIVE indicators turn on, the paralleling cable has an open circuit. Replace the cable.

10. To test for a paralleling fault, turn both power supply modules off and wait 15 seconds (-P3 and -P4) or 45 seconds (-P5, -P5E). 11. Verify that the paralleling cable is properly connected, and then turn both power supplies on simultaneously. The P/S ACTIVE indicators on both supplies should turn on. 12. If the P/S ACTIVE indicators on both supplies do not turn on, replace both supplies, one at a time, with known good power supplies in order to isolate the faulty power supply module. 13. If all tests have passed up to this point, turn both power supply modules off simultaneously and wait 15 seconds (-P3 and -P4) or 45 seconds (-P5, -P5E). Check for backplane loading by performing steps 14, 15 and 16. 14. Firmly seat the power supplies in the chassis. 15. Restore power to the I/O chassis, and turn both power supply modules on simultaneously. If the P/S ACTIVE indicator : Turns On Does not turn On

Then: The power supply modules are operating correctly and the system should operate normally. Recheck backplane loading.

16. Check for proper dual power supply module operation. If backplane loading is within acceptable limits and the P/S ACTIVE indicators do not turn on, replace both power supply modules, one at a time, with known good power supply modules in order to isolate the faulty module. The system should operate normally.

11

Page 12

Installation Instructions Power Supply Modules Cat. No. 1771-P3, -P4, -P5 and -P5E

Specifications

1771-P3 Module Location

1771-P4

1 slot in a 1771 I/O chassis

1771-P5

1771-P5E

2 adjacent slots in a 1771 I/O chassis

Nominal Input Voltage

120V ac

24V dc

Input Voltage Range

97 to 132V ac rms

20.5 to 30V dc1

Input Power

23 Watts

57 Watts

Frequency Range

57 Watts

50/60Hz

Not applicable

Isolation Voltage

2160V dc for 1s, 1500V rms for 1s (input line to chassis ground)

Output Voltage

5.06V dc (+3.8%)

Output Current

3A @ 5V dc maximum 1A 125V slow blow Bussman MDL1.0 Littelfuse 313001

Fuse Power Loss Time Delay Input Power Loss to Processor Disable

8A @ 5V dc maximum 1.5A 125V slow blow Bussman MDX1.5 Littelfuse 31301.5

UL, CSA

UL, CSA/H, EMI/RFI Standard Conformance2

UL, CSA/H

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF) 5 to 95% without condensation 1.6 lbs (0.73 kg)

2.3 lbs (1.04 kg)

Paralleling Cable Keying - right hand slot

Adjustable 13.6ms (+3.6ms) or 60ms

13.6ms (+3.6ms)

Agency Approval

Weight

5A 32V normal blow Bussman MTH5 Littelfuse 312005

2.6 lbs (1.18 kg)

Cat. No. 1771-CT Between 12 and 14 Between 18 and 20

Between 12 and 14 Between 20 and 22

Between 12 and 14 Between 22 and 24

60VA

150VA

Not applicable

External Transformer (if used)

1 Input voltage range includes ripple. Full wave rectified and filtered dc is acceptable if peak to peak ripple is less then 10% of the input voltage. 2 Conforms to CISPR 11 Class A Radiated Emissions, CISPR 11 Class A Conducted Emissions, 10V/M Radiated Immunity

With offices in major cities worldwide WORLD HEADQUARTERS Allen-Bradley 1201 South Second Street Milwaukee, WI 53204 USA Tel: (1) 414 382-2000 Telex: 43 11 016 FAX: (1) 414 382-4444

EUROPE/MIDDLE EAST/AFRICA HEADQUARTERS Allen-Bradley Europe B.V. Amsterdamseweg 15 1422 AC Uithoorn The Netherlands Tel: (31) 2975/43500 Telex: (844) 18042 FAX: (31) 2975/60222

As a subsidiary of Rockwell International, one of the world’s largest technology companies, Allen-Bradley meets today’s challenges of industrial automation with over 85 years of practical plant-floor experience. More than 11,000 employees throughout the world design, manufacture and apply a wide range of control and automation products and supporting services to help our customers continuously improve quality, productivity and time to market. These products and services not only control individual machines but integrate the manufacturing process, while providing access to vital plant floor data that can be used to support decision-making throughout the enterprise. ASIA/PACIFIC HEADQUARTERS Allen-Bradley (Hong Kong) Limited Room 1006, Block B, Sea View Estate 28 Watson Road Hong Kong Tel: (852) 887-4788 Telex: (780) 64347 FAX: (852) 510-9436

Publication 1771-2.111 – February 1994 Supersedes publication 1771-2.111 – November 1992 and 1771-2.111-RN1 – May 1993 12