The text of a manual · part 1 of 2
Power Supply Modules Cat. No. 1771-P3, P4, P5 and P5E Installation Instructions, pages 1 to 6
Pages 1 to 6 of 12
The original document is the PDF (114 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-P4
Page 1
Power Supply Modules Cat. No. 1771-P3, -P4, -P5 and -P5E Installation Instructions
To The Installer
This document provides information on: pre-installation information connecting input power setting the power loss time delay (1771-P5E only) installing the power supplies paralleling power supplies indicator lights troubleshooting specifications
Pre-installation Considerations
The 1771-P3 power supply is a single-slot module; and the 1771-P4, -P5 and -P5E power supplies are 2-slot modules. These power supply modules can be used in both series A and B 1771 I/O chassis, subject to the conditions listed below. Series A 1771 I/O chassis – You are restricted to the following: Processor
I/O Chassis
1st Power Supply
2nd Power Supply
Without an integral power supply
1771-A4
1771-P3 - 1st slot group 0 1771-P4, -P5, -P5E - slots 0 and 1
1771-P3 - 1st slot of group 5 1771-P4, -P5, -P5E - slots 8 and 9
1771-A4 With an integral power supply
Not Applicable 1771-A2
1771-P3 - 1st slot of group 4 1771-P4 - group 4 1771-P5, -P5E - not applicable 1771-P3 - 1st slot of group 3 1771-P4 - group 3 1771-P5, -P5E - not applicable
Series B (or later) 1771 I/O chassis – You may place this module in any slot of a series B (or later) I/O chassis, except the left-most slot which is reserved for the processor.
Page 2
Installation Instructions Power Supply Modules Cat. No. 1771-P3, -P4, -P5 and -P5E
Important: Do not parallel a 1771-P5 or -P5E power supply and an ac powered processor. Use the same voltage source to power two paralleled units. 1772-LSP, -LWP and -LXP processors contain an integral ac input power supply. Therefore, you can add only one additional power supply module. 1772-LS, -LW and -LX processors do not contain an integral power supply. You can install up to two additional power supply modules. Refer to Table A. Table A Power Supply/Processor Usage 1771-AL 1771-AR2 1771-ASB
Power Supply Cat. No.
1772-LN1, -LN2, -LN3, -LV
1771-AS
1772-LS 1772-LW 1772-LX
1772-LSP1 1772-LWP1 1772-LXP1
1771-P3 1771-P4 1771-P5, -P5E
Where: The two components are compatible for use together in a series A or B I/O chassis The two components are compatible for use together only in a series B I/O chassis Not compatible 1 Power supply and backup battery included 2 Switch 7 of I/O chassis must be turned on. Refer to Remote I/O Adapter Module publication 1771-2.17.
Refer to Table B.You can parallel the power supplies with processors and each other. Table B Power Supply Module Current Capabilities Total Available Backplane Current for I/O Modules
Power Supply Paralleled with
1771-P3
1771-P4
1771-P3
6A
11A
1771-P4
11A
16A
1771-P5, -P5E1
1
2
1772-LSP
5A
10A
1772-LXP
7A
12A
1772-LWP
7A
12A
1771-P5
1771-P5E
16A
16A
The 1771-P5 or -P5E power supply is designed to operate in parallel only with another 1771-P5 power supply. The total current capability would be 16A.
Page 3
Installation Instructions Power Supply Modules Cat. No. 1771-P3, -P4, -P5 and -P5E
To parallel power supply modules, use the power supply paralleling cable, cat. no. 1771-CT. ATTENTION: Power supply modules have a controlled “soft-start” feature to enhance power supply reliability. During power-up or power-down periods, outputs of certain discrete modules may momentarily change operating state. These modules are: Isolated AC (120V) Output Module, cat. no. 1771-OD series A or B Isolated AC (220V) Output Module, cat. no. 1771-OR series A Contact Output Module cat. no. 1771-OY series A or B Contact Output Module cat. no. 1771-OZ series A or B DC (5V) Multiplexer Input Module cat no. 1771-IS Later series of these modules do not change state during power-up or power-down. Failure to observe this warning may damage equipment and/or injure personnel.
Connecting Input Power
The 1771-P3, -P4, -P5 and -P5E power supply modules require power from an external power source. Refer to Table C for input voltage requirements and output current capability for the individual power supply modules. Table C Power Supply Module Input Voltage Requirements Power Supply Module
Input Voltage Requirements
Output Current
1771-P3
120V ac (97-132V ac)
3A @ 5V
1771-P4
120V ac (97-132V ac)
up to 8A @ 5V
1771-P5
24V dc (20.5-30V dc)
up to 8A @ 5V
1771-P5E
24V dc (20.5-30V dc)
up to 8A @ 5V
Refer to Figure 1 and Figure 2 for input power connections.
3
Page 4
Installation Instructions Power Supply Modules Cat. No. 1771-P3, -P4, -P5 and -P5E
Setting the Power Loss Time Delay (1771-P5E only) The 1771-P5E power supply has a selectable power loss time delay which helps prevent unnecessary I/O chassis resets due to input power supply dropouts Power loss time delay is the time period from when the power supply input voltage drops below 20.5V dc to when the power supply resets the processor enable signal on the I/O backplane. When this signal is reset, the resident PLC processor or adapter module stops processing data to/from the modules in the I/O chassis. You set the configuration jumper as follows:
Set the jumper to this position
For this power loss time delay
JPR1 Standard (factory default position)
13.6 ms ±3.6 ms
JPR2
60 ms
Extended
Extended power loss time delay bottom of power supply module
Standard power loss time delay 19648
If your input modules and power supply use power from the same source and the input module time delay is greater than the power loss time delay of the power supply module, input module data integrity is preserved. ATTENTION: Exercise care when you configure your system for possible power loss. You should consider: input module time delay power loss time delay incoming power quality control system response to input information
4
Page 5
Installation Instructions Power Supply Modules Cat. No. 1771-P3, -P4, -P5 and -P5E
Figure 1 Features of the Power Supply Modules Cat. No. 1771-P5 and 1771-P5E
Status Indicator - Keeps you informed of module operating conditions.
P/S ACTIVE
P/S Parallel - Makes paralleling connections between 2 power supplies easy.
P/S Parallel
24V dc POWER ON OFF 5A 32V NORM BLOW
24V DC +DC COM GND
Cat. No. 1771-P3
Power Switch - Turns the power supply on or off. Input Fuse - Protects input voltage source and wiring. Terminal Strip - Make input power connections at this terminal strip.
P/S ACTIVE
P/S Parallel
120V ac POWER ON OFF 1A 125V SLOW BLOW 120V AC L1 N G N D
12228-I
Installing the Power Supply To install the power supply module in the I/O chassis, proceed as follows: ATTENTION: Turn the power supply OFF before inserting into the I/O chassis. Turn off power to the I/O chassis before inserting this module into the chassis. Failure to remove power from the backplane could cause module damage, degradation of performance, or injury. Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.
1.
Turn off power to the I/O chassis
2.
Turn the power supply module power switch OFF.
3.
Place the printed circuit board on the rear of the module into the plastic tracks on the top and bottom of the I/O chassis which guide the module into the chassis. 5
Page 6
Installation Instructions Power Supply Modules Cat. No. 1771-P3, -P4, -P5 and -P5E
4.
Do not force the module into the backplane connectors. Apply firm, even pressure on the module to seat it properly.
5.
Snap the chassis latch over the top of the module to secure its position.
6.
Make power connections as described in “Making Input Power Connections” below.
Making Input Power Connections Refer to Figure 2. Proceed as follows. 1.
Remove the protective cover from the terminal block by squeezing the prongs and lifting the protective cover.
2.
1771-P3 and -P4 – Connect the L1 (high) line to the top (L1) connection on the terminal block. 1771-P5, -P5E – Connect the positive dc line to the top terminal (DC).
3.
1771-P3 and -P4 – Connect the neutral (low) line to the middle (N) connection on the terminal block. 1771-P5, -P5E – Connect the negative dc line to the middle terminal (COM).
4.
1771-P3 and -P4 – Connect the bottom terminal labeled GND to the ground bus (equipment ground). 1771-P5, -P5E – Connect the bottom terminal (labeled GND) to the ground bus.
5.
Replace the protective cover on the terminal block.
Figure 2 Input Power Connections
120V AC
24V DC
L1
Line
DC dc Positive connects to DC
N
Neutral
COM
GND
Ground Bus
GND dc Negative connects to COM
Equipment Ground
1771-P4
6
Grounding Electrode Conductor
1771-P5, -P5E
Connect central ground bus to GND
12229-I