Page 1 of Installation Data: Power Supply Modules (Cat. No. 1771-P4S, -P6S, -P4S1, -P6S1)

Manual · Allen-Bradley

Installation Data: Power Supply Modules (Cat. No. 1771-P4S, -P6S, -P4S1, -P6S1)

Manual8 pagesPDF 136 KB

Installation data for Allen-Bradley 1771-P4S, -P6S, -P4S1 and -P6S1 power supply modules: jumpers, placement, wiring, indicators and specs.

Download the PDF136 KB

Covers · 1 model

The models it covers

Summary

What is in it

Installation data for the Allen-Bradley 1771-P4S, -P6S, -P4S1 and -P6S1 power supply modules that plug into a 1771 I/O chassis slot. It covers setting the sensing jumpers, placing the supply in current and superseded chassis, connecting a 1771-CT paralleling cable for two supplies, wiring AC input power, reading the P/S ACTIVE indicator, troubleshooting single and parallel supplies, and specifications.

Its parts

  1. To the Installer
  2. What This Power Supply Package Contains
  3. Installing the Power Supply Module
  4. Interpreting the Power Supply Indicators
  5. Troubleshooting a Single Power Supply
  6. Troubleshooting Parallel Power Supplies
  7. Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Allen-Bradley installation data (publication 1771-2.135, February 1990) for the 1771 power supply modules, cat. no. 1771-P4S, -P6S, -P4S1 and -P6S1. It explains setting the jumpers, placing the supply in a 1771 I/O chassis, paralleling two supplies, wiring input power, reading the P/S ACTIVE indicator and troubleshooting, and it lists the specifications of all four models.

What it is
Power supply module that fits an I/O module slot of a 1771 I/O chassis p. 1, 3
Output
5V dc to the backplane, 8A max p. 8
1771-P4S input
1771-P4S: 120V ac, range 97-132V ac rms, 47-63 Hz p. 8
Fuse
1.5A 250V slow-blow p. 8
Compatible chassis
1771-A1B, -A2B, -A3B, -A4B, -A3B1, -PSC; superseded 1771-A1, -A2, -A4 with slot limits p. 3
Paralleling cable
1771-CT, for two supplies in one I/O chassis p. 3
Terminal block
5-position, A-B P/N 941274-05 (Wago 231-205/000-008), one included p. 8
Wire size
14 AWG max, single wire only; strip 0.35 inches p. 5, 8
Operating temperature
0 to 60°C (32 to 140 °F); storage -40 to 85° C p. 8
Humidity
5 to 95% without condensation p. 8
Size and weight
1 I/O chassis slot wide, 1.85 lbs (0.84 kg) p. 8
Indicator
One P/S ACTIVE indicator on the front panel p. 5

What this manual walks you through

  • Setting the jumpers for local or remote sensing p. 1, 2
  • Placing the supply in current and superseded I/O chassis p. 3
  • Connecting a paralleling cable between two supplies p. 3
  • Wiring ac input power to L1, L2/N and GND p. 4
  • Connecting a wire to the terminal block p. 5
  • Interpreting the P/S ACTIVE indicator p. 5, 6
  • Troubleshooting a single supply or a parallel pair p. 6, 7

Good to know

  • Paralleling two supplies gives more power but no redundancy, because the adapter or processor is disabled if one shuts down. p. 3
  • Turn paralleled supplies on at the same time, or the first may shut down on overcurrent. p. 3
  • Turn off all power supplies before removing or inserting modules in a chassis. p. 2
  • After a dc limit shutdown, power must be off for at least 5 seconds before turning it back on. p. 6
  • The two undesignated terminals of the terminal block are not connected and not used. p. 5

Questions this manual answers

What does the 1771-P4S output?

5V dc to the chassis backplane, at up to 8A. p. 8

What input voltage does the 1771-P4S take?

The 1771-P4S is the 120V ac model, with an input range of 97-132V ac rms at 47-63 Hz. p. 8

Why is the P/S ACTIVE light off on my 1771 power supply?

The supply has seen dc overvoltage, undervoltage or overcurrent, ac undervoltage, a paralleled supply shut down, or its power switch is off. p. 6

Which cable connects two 1771-P4S supplies in parallel?

The 1771-CT Power-Supply Paralleling Cable, run between the P/S PARALLEL connectors. p. 3

What fuse does the 1771-P4S use?

A 1.5A 250V slow-blow fuse. p. 8

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1771-2.135, Allen-Bradley Power Supply Modules1
  2. To the Installer1
  3. What This Power Supply1
  4. Installing the Power Supply1
    1. Set the Jumpers1
    2. Place the Power Supply in a Chassis2
    3. Connect a Paralleling Cable3
    4. Connect Input Power4
  5. Interpreting the Power Supply Indicators5
  6. Troubleshooting a Single Power Supply6
  7. Troubleshooting Parallel Power Supplies7
  8. Specifications8
  9. Back Cover8

From the PDF’s own bookmarks.

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8

The file

Revision and size

RevisionPublication 1771-2.135, February 1990
PublisherAllen-Bradley
Pages8
PDF136 KB
TextText from the PDF itself.