For the Allen-Bradley 1771-P4S
Page 1
Installation Data Power Supply Modules (Cat. No. 1771-P4S, -P6S, -P6S1, -P6S1)
Allen-Bradley Power Supply Modules (cat. no. 1771-P4S, -P6S, -P4S1, -P6S1)
To the Installer
This document provides you with the following information: what this package contains tasks on installing your power supply module interpreting the power supply indicators troubleshooting your power supply
What This Power Supply Package Contains
When you receive your power supply, you should see the following components in the box: one 1771-P4S, -P6S, -P4S1, or -P6S1 power supply module one 5-position terminal block (attached to module)
Installing the Power Supply Module
To install your power supply, you need to know how to perform the following tasks: set the jumpers place the power supply in a chassis connect a paralleling cable (if using a second supply) connect input power
Set the Jumpers Each power supply module has two jumpers located at the back edge of the module near the gold-plated edge connectors. The jumper selection provides the proper voltage regulation for the different power supply configurations. The power supply can be configured to support local or remote sensing by setting the jumpers.
1
Page 2
Installation Data Power Supply Modules (Cat. No. 1771-P4S, -P6S, -P6S1)
To configure the supply: 1.
Position the power supply module so that the jumpers and pins are facing upward as shown in figure 1.
Figure 1 Power Supply Jumpers
2.
Set the jumpers as shown in table A. Use needle nose pliers to set the jumpers.
Table A Jumper Settings For This Configuration
Set Jumpers to:
A single power supply in a power-supply chassis connected to an I/O chassis through a power cable.
right position
All other configurations. (Power supplies are shipped with jumpers in this position.)
left position
Place the Power Supply in a Chassis WARNING: Turn off all power-supply modules before removing modules from or inserting modules into a chassis. Failure to observe this warning could alter processor memory, damage module circuitry, and cause unintended operation which could possibly cause injury to personnel.
2
Page 3
Installation Data Power Supply Modules (Cat. No. 1771-P4S, -P6S, -P6S1, -P6S1)
You can place these power-supply modules into any I/O module slot in any current chassis (1771-A1B, -A2B, -A3B, -A4B, -A3B1, -PSC). However, to place these power-supply modules into a superseded I/O chassis (1771-A1, -A2, -A4), you must follow the restrictions in table B. Table B Placement Restrictions in Superseded I/O Chassis (1771-A1, -A2, -A4) Adapter or In-chassis processor
I/O Chassis
1st Power Supply1
2nd Power Supply1
Without
A4
I/O-slot 0
I/O-slot 10 an integral
A2
I/O-slot 0
I/O-slot 4
A1
I/O-slot 0 not applicable
With an integral
A4 not applicable
I/O-slot 8 power supply
A2 not applicable
I/O-slot 3 power supply
1 I/O module slots are numbered 0 through 15, left to right.
Connect a Paralleling Cable You can use two power supplies in the same I/O chassis to produce more power by connecting them with a Power-Supply Paralleling Cable (1771-CT). This connection is for communication between the two supplies. If one supply has to shut down, it tells the second to turn off its indicator. Although the adapter or in-chassis processor will be disabled, the second supply will continue trying to operate until its DC output limits are exceeded. Because the adapter or in-chassis processor is disabled, paralleling two supplies does not provide redundancy. To connect the paralleling cable: 1.
Connect the paralleling cable between the P/S PARALLEL connectors on the two supplies (figure 2).
2.
Loop the paralleling cable over the top of the I/O chassis to avoid picking up signals induced from I/O wiring.
3.
Turn on the supplies simultaneously. If you don’t, the first supply you turn on may shut down due to an overcurrent condition.
3
Page 4
Installation Data Power Supply Modules (Cat. No. 1771-P4S, -P6S, -P6S1)
Figure 2 Paralleling Cable and AC Power Connections
Connect Input Power Figure 2 shows the overall configuration of the ac power connections. To make ac power connections:
4
1.
Connect the high side of the power source to the L1 terminal of the power supply.
2.
Connect the low side of the power source to the L2 or N (neutral) terminal of the power supply.
3.
Connect the GND (ground) terminal of the power supply to the central ground bus in the enclosure.
Page 5
Installation Data Power Supply Modules (Cat. No. 1771-P4S, -P6S, -P6S1, -P6S1)
Figure 3 shows details of how to connect a wire to a terminal on the terminal block. You can connect these wires while the terminal block is plugged into the supply, or you can remove the block to lay it on a flat surface to connect these wires. To remove the block, pull it straight out out from the receptacle on the module. The 2 undesignated terminals do not connect to any electrical circuit on the module and are not used. Each of the three functional terminals accepts a single 14-AWG wire max. To connect a wire to a terminal: 1.
Strip 0.35 inches of insulation off the wire.
2.
Spring the clip open to insert the wire, using a wedge-tipped tool such as a small screwdriver. If you leave the terminal block plugged into the supply, insert the tool parallel to the wire (push straight in). If you remove the terminal block and lay it on a flat surface, insert the tool perpendicular to the wire (push straight down).
3.
After making the wiring connections, re-insert the terminal block into the front plate. Be sure that the plug is completely inserted and that the locking prongs are engaged.
Figure 3 Connecting a Wire to a Terminal
Interpreting the Power Supply Indicators
Your power supply has an indicator located in the upper half of the module front panel labeled P/S ACTIVE. Table C shows how to interpret the P/S ACTIVE indicator.
5
Page 6
Installation Data Power Supply Modules (Cat. No. 1771-P4S, -P6S, -P6S1)
Table C Interpreting the P/S ACTIVE Indicator If the indicator Is:
Then:
On
The power supply (and any supply connected through a paralleling cable) is operating normally. However, it could still have a poor connection to the backplane.
Off
The supply has detected one of the following conditions:
G dc overvoltage (the supply shuts down) G dc undervoltage (the supply shuts down) G dc overcurrent (the supply shuts down) G power switch turned off (the supply is turned off) G ac undervoltage G the paralleled supply is shut down With ac undervoltage or a paralleled supply shut down, the supply will still attempt to generate the output. When dc limits are exceeded, the supply shuts down until you turn power off (for 5 seconds minimum) and then back on.
Troubleshooting a Single Power Supply
6
If you have a single power supply installed in an I/O chassis and its P/S ACTIVE indicator is off, verify the ground connection to the supply; then follow this troubleshooting flow chart.
Page 7
Installation Data Power Supply Modules (Cat. No. 1771-P4S, -P6S, -P6S1, -P6S1)
Troubleshooting Parallel Power Supplies
If you have a pair of power supplies installed in parallel in an I/O chassis and the P/S ACTIVE indicators are off, verify the ground connection to each supply; then follow this troubleshooting flow chart.
7
Page 8
Installation Data Power Supply Modules (Cat. No. 1771-P4S, -P6S, -P6S1)
Specifications 1771-P4S
1771-P6S
1771-P4S1
1771-P6S1
Input Voltage
120V ac
220V ac
100V ac
200V ac
Input Range
97- 132V ac rms
194 - 264V ac rms
85 - 120V ac rms
170 - 240V ac rms
Frequency
47 - 63 Hz
47 - 63 Hz
47 - 63 Hz
47 - 63 Hz
Fuse
1.5A 250V Slow-blow
Output Voltage (Backplane)
5V dc
Output Current (max)
8A
Wire Size
14 AWG max (single wire only)
Environmental Conditions
Operational Temperature: 0 to 60°C (32 to 140 °F) Storage Temperature: -40 to 85° C (-40 to 185 °F) Relative Humidity: 5 to 95% (without condensation)
Physical Width
1 I/O chassis slot
Weight
1.85 lbs (0.84 kg)
5-position Terminal Block
A-B P/N 941274-05, Wago 1 P/N 231-205/000-008 (1 included with each power supply)
1Wago Corporation 9085 N. Deerbrook Trail, Brown Deer WI 53223
With offices in major cities worldwide WORLD HEADQUARTERS Allen-Bradley 1201 South Second Street Milwaukee, WI 53204 USA Tel: (1) 414 382-2000 Telex: 43 11 016 FAX: (1) 414 382-4444
EUROPE/MIDDLE EAST/AFRICA HEADQUARTERS Allen-Bradley Europe B.V. Amsterdamseweg 15 1422 AC Uithoorn The Netherlands Tel: (31) 2975/43500 Telex: (844) 18042 FAX: (31) 2975/60222
Publication 1771–2.135–February 1990 Supersedes Publication 1771–2.135–Febuary 1989
8
As a subsidiary of Rockwell International, one of the world’s largest technology companies, Allen-Bradley meets today’s challenges of industrial automation with over 85 years of practical plant-floor experience. More than 11,000 employees throughout the world design, manufacture and apply a wide range of control and automation products and supporting services to help our customers continuously improve quality, productivity and time to market. These products and services not only control individual machines but integrate the manufacturing process, while providing access to vital plant floor data that can be used to support decision-making throughout the enterprise. ASIA/PACIFIC HEADQUARTERS Allen-Bradley (Hong Kong) Limited Room 1006, Block B, Sea View Estate 28 Watson Road Hong Kong Tel: (852) 887-4788 Telex: (780) 64347 FAX: (852) 510-9436
CANADA HEADQUARTERS Allen-Bradley Canada Limited 135 Dundas Street Cambridge, Ontario N1R 5X1 Canada Tel: (1) 519 623-1810 FAX: (1) 519 623-8930
LATIN AMERICA HEADQUARTERS Allen-Bradley 1201 South Second Street Milwaukee, WI 53204 USA Tel: (1) 414 382-2000 Telex: 43 11 016 FAX: (1) 414 382-2400
PN 955106–86 Copyright 1992 Allen-Bradley Company, Inc. Printed in USA