What is in it
Allen-Bradley installation instructions for the 1771-P7 Series C, a stand-alone external AC power supply that powers one 1771-A1B, -A2B, -A3B, -A3B1 or -A4B I/O chassis. It covers EU directive compliance, preparing for installation, mounting the supply on the side of a panel-mounted chassis or separately, choosing the 1771-CP1, -CP2 or -CP3 power cable, connecting AC power and setting the voltage selector, troubleshooting with the P/S ACTIVE LED, specifications and power rating graphs.
Its parts
- To the Installer
- Compliance to European Union Directives
- Prepare for Installation
- Install the 1771-P7 and Connect Backplane Power
- Connect ac Power Source to the Power Supply
- Troubleshooting
- Specifications
- Power Ratings
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley installation instructions (publication 1771-5.39, December 1995) for the 1771-P7 Series C AC (120/220V) 16A power supply; the 1771-PA it is filed under is not named in it. It covers preparing the I/O chassis, mounting the supply on the side of the chassis or apart from it, connecting AC power, troubleshooting by the status LED, and specifications.
- Type
- 1771-P7 Series C: stand-alone external AC power supply, 16A, for a 1771 I/O chassis p. 1, 2, 3
- Output
- 16A max at 5V dc p. 9
- Chassis
- Powers one 1771-A1B, -A2B, -A3B, -A3B1 or -A4B chassis; not compatible with 1771-A1, -A2 or -A4 p. 2
- Processors
- Any adapter or processor without an internal power supply: Mini-PLC-2/02, Mini-PLC-2/05, Mini-PLC-2/16, Mini-PLC-2/17 or PLC-5 family p. 2
- Input voltage
- Nominal 120V ac or 220V ac; selector at 115 for 97 to 132V ac, at 230 for 195 to 264V ac p. 7
- Input current
- 120V ac at 2.0A; 220V ac at 1.0A p. 9
- Power cables
- 1771-CP1 when attached to the chassis side; 1771-CP2 or 1771-CP3 when mounted apart; ordered separately p. 4, 5, 6
- Cable lengths
- 0.32m (1.04ft) to a chassis-mounted 1771-P7; 1.52m (5ft) rack-mounted or 1.68m (5.5ft) panel-mounted chassis to a remote 1771-P7 p. 9
- Chassis jumper
- Set the I/O chassis power supply configuration jumper to N p. 3
- Fuse
- 3A 250V 3AG normal blow on line L1 (Bussmann AGC 3, Littelfuse 312003) p. 8, 9
- Weight, size
- 1.95kg (4.3 lbs.); 315mm x 115mm x 159mm p. 9
- Backplane connector
- D-shell connector on the bottom of the supply p. 3, 5
- Status LED
- Green P/S ACTIVE LED, on in normal operation p. 8
- Transformer sizing
- VA = real power (watts) x 2.5 p. 9
What this manual walks you through
- Preparing the I/O chassis and setting its power supply jumper p. 2, 3
- Attaching the power supply to the side of a panel-mounted chassis p. 4, 5
- Mounting the power supply apart from the chassis p. 6, 7
- Setting the input voltage switch and wiring AC power p. 7, 8
- Troubleshooting with the P/S ACTIVE LED p. 8
- Specifications and power rating graphs p. 9
Good to know
- Never connect the 1771-P7 in parallel with another power supply. p. 2
- Mounted apart, it may go above or beside the chassis but not below it, with at least 6 inches vertical clearance. p. 6
- Use only the mounting screws supplied; longer ones can intrude into the chassis. p. 4
- A 14 AWG wire must run from the GND terminal to the ground bus. p. 8
- After a shutdown, wait 15 seconds before applying power again. p. 8
Questions this manual answers
Which I/O chassis can the 1771-P7 power?
One 1771-A1B, -A2B, -A3B, -A3B1 or -A4B chassis. It does not work with the 1771-A1, -A2 or -A4. p. 2
How do I set the 1771-P7 for 220V?
Set the input voltage selector switch to the 230 position for 195 to 264V ac, with the power switch off. p. 7
Why is the P/S ACTIVE light off on a 1771-P7?
The input voltage may be out of range, the fuse may be blown, or there may be an overcurrent. p. 8
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1771-5.39, AC (120/220V) 16A Power Supply, Installation Instructions1
- To the Installer1
- Compliance to European Union Directives1
- Prepare for Installation2
- Install the 1771-P7 and Connect Backplane Power3
- Connect ac Power Source to the Power Supply7
- Troubleshooting8
- Specifications9
- Power Ratings9
- Back Cover10