The text of a manual · part 1 of 1
AC (120/220V) 16A Power Supply (Cat. No. 1771-P7 Series C) Installation Instructions, pages 1 to 10
Pages 1 to 10 of 10
The original document is the PDF (277 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Allen-Bradley 1771-PA
Page 1
Installation Instructions
AC (120/220V) 16A Power Supply (Cat. No. 1771-P7 Series C) To the Installer
This document provides you with the following information: For this information compliance European Union Directive preparing to install the power supply installing the power supply connecting ac power to the power supply troubleshooting specifications power ratings
Compliance to European Union Directives
See page 1 2 3 7 8 9 9
ÎÎ ÎÎ
The series C version of this product is marked with the logo, indicating that this version complies with the European Union Directives noted below. If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file:
• EN 50081-2 EMC – Generic Emission Standard, Part 2 – Industrial Environment • EN 50082-2 EMC – Generic Immunity Standard, Part 2 – Industrial Environment This product is intended for use in an industrial environment.
Publication 1771-5.39
December 1995
Page 2
2
AC (120/220V) 16A Power Supply
Low Voltage Directive This product is also tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information that the above EN requires, see the appropriate sections in this publication, as well as the following Allen-Bradley publications:
• Industrial Automation Wiring and Grounding Guidelines (for noise immunity), publication 1770-4.1 • Guidelines for Handling Lithium Batteries, publication AG-5.4 • Automation Systems Catalog, publication B111
Prepare for Installation
The 1771-P7 power supply can power one 1771-A1B, -A2B, -A3B, -A3B1, or -A4B I/O chassis when used with any adapter module or programmable controller (Mini-PLC-2/02, Mini-PLC-2/05, Mini-PLC-2/16, Mini-PLC-2/17, or PLC-5 family processor) that does not have an internal power supply. Important:
!
!
The power supply is not compatible with the 1771-A1, -A2, or -A4 I/O chassis. ATTENTION: The 1771-P7 is a stand-alone power supply. Do not connect it in parallel with any other power supply. Connecting it in parallel could result in processor memory loss or injury due to unexpected machine operation.
ATTENTION: Under some conditions, electrostatic discharge can degrade performance or damage system components. Observe the following precautions to guard against electrostatic damage:
• Touch a grounded object to rid yourself of charge before handling a module. • Do not touch the backplane connector or connector pins. • When not in use, keep modules in their static-shield bags.
Publication 1771-5.39
December 1995
Page 3
AC (120/220V) 16A Power Supply
3
Before installing the power supply, you should: • mount the I/O chassis that the power supply will be connected to. See the Universal I/O Chassis Installation Data (1771-2.210) for information on mounting the I/O chassis. • set the power supply configuration jumper on the I/O chassis. The 1771-P7 is an external power supply. Set the configuration jumper to the N position. Y
N
Using Power Supply Module in the Chassis?
12620-I
Install the 1771-P7 and Connect Backplane Power
A1 A2 1 2 3 4 5
The power supply has a D-shell power connector that provides power to the I/O chassis backplane.
backplane common backplane +5V dc no connection backplane processor enable backplane +5V dc sense backplane signal ground sense no connection
A1 3 4
1
5
2
A2 bottom view of power supply
If you have this I/O chassis 1771-A3B 1771-A1B, -A2B, -A3B1, or -A4B
Use this power cable 1771-CP2 1771-CP1 1771-CP3 (right angle connector)
13445
To connect a 1771-P7 mounted within 1.52m (5ft) of the I/O chassis within 0.32m (1.04ft) on the left-side of the I/O chassis within 1.68m (5.5ft) of the I/O chassis
Publication 1771-5.39
December 1995
Page 4
4
AC (120/220V) 16A Power Supply
If you are mounting the power supply on the left side of a panel-mounted I/O chassis separately from an I/O chassis
Go to next section page 6
Attaching to a Panel-mounted I/O Chassis 1. Attach the mounting screws to the side of the I/O chassis as shown: ATTENTION: Use the mounting screws provided with the 1771-P7. Longer screws may intrude into the I/O chassis and interfere with module insertion.
!
lockwasher shoulder washer large screw
Tighten this screw. left-side of I/O chassis two small screws and lockwashers
Loosely attach these screws.
13446
2. Connect the power cable (ordered separately) to the D-shell connector on the I/O chassis and tighten the connector screws.
D-shell connector left-side of I/O chassis connector screws
1771-CP1 cable
Publication 1771-5.39
December 1995
13447
Page 5
AC (120/220V) 16A Power Supply
5
3. Slide the power supply onto the left side of the chassis, as shown: Place keyhole slot over large screw on I/O chassis.
1771-P7
Slide power supply down.
left side I/O chassis Make sure mounting brackets are behind the small screws.
13448
4. Tighten the small screws to secure the power supply to the I/O chassis.
1771-P7 left side I/O chassis small screws 12629-I
5. Attach the other end of the power cable to the D-shell connector on the bottom of the power supply and tighten the connector screws. 1771-P7 left side I/O chassis D-shell connector connector screws 1771-CP1 cable
Publication 1771-5.39
13449
December 1995
Page 6
6
AC (120/220V) 16A Power Supply
Mounting the Power Supply Separately When mounted separately, the power supply may be mounted above or next to the I/O chassis. It may not be mounted below, since it is necessary to allow convection cooling of both the power supply and the I/O chassis. A minimum vertical distance of 6 inches should be maintained. 1. Mount the power supply vertically, above and within the specified cable-feet (for your cable) of the D-shell connector on the I/O chassis. 1771-P7
Use the rear mounting flanges on the power supply to mount it to a panel.
15.2cm (6")
Allow for a generous bend of the 1771-CP2 or 1771-CP3 cable to reduce stress on the connectors mounted on the chassis and the power supply.
12621-I
2. Connect one end of the power cable (ordered separately) to the D-shell connector located on the bottom of the power supply and tighten the connector screws. 1771-P7 connector screws
Publication 1771-5.39
December 1995
1771-CP2 or 1771-CP3 cable
12622-I
Page 7
AC (120/220V) 16A Power Supply
7
3. Connect the other end of the power cable to the D-shell connector on the I/O chassis and tighten the connector screws. 1771-A1B, -A2B, -A3B1, -A4B I/O chassis
1771-A3B I/O chassis
1771-CP2
1771-CP3
12623-I
Connect ac Power Source to the Power Supply
12624-I
The power supply operates on nominal120V ac or 220V ac input source. 1. Make sure the power switch is set to OFF.
ON POWER OFF
2. Use a 1/8” slotted screwdriver to set the input-voltage selector switch.
! 115V 12625-I
ATTENTION: To avoid damaging the power supply, do not place the screwdriver blade more than 3/8” into the switch slot.
For an input voltage of
Set the voltage selector switch to
97 to 132V ac
115 position
195 to 264V ac
230 position
115V 230V
Publication 1771-5.39
December 1995
Page 8
8
AC (120/220V) 16A Power Supply
3. Connect the ac power line to the terminal strip on the power supply. ATTENTION: You must connect a 14 AWG wire from the GND terminal to the ground bus to provide an adequate safety ground.
!
ac power connectors
Connect high side of the line power➀
L1 low side of the line power
L2/N central ground bus (earth ground)
GND
Line 1 Line 2 or neutral ac power (customer supplied)
Ground Bus
14 AWG Grounding electrode conductor
➀ A 3A 250V normal-blow fuse protects the input line L1 from drawing more than 3 amperes.
Troubleshooting
The power supply has a green P/S ACTIVE LED that provides status indication during power supply operation. Normal operation on
P/S Active Important: 12627-I
Publication 1771-5.39
12626-I
December 1995
If indicator is off
Then it may be due to: • input voltage not within specified range • blown fuse • overcurrent
If a shutdown condition occurs, wait 15 seconds before attempting to apply power.
For additional assistance, contact your local Allen-Bradley representative.
Page 9
AC (120/220V) 16A Power Supply
Specifications
Nominal Input Voltage/Current Input Voltage Range
115mm (4.53")
45mm 1.77"
Input Power (Real/Apparent) External Transformer Frequency Range Isolation Voltage Output Voltage Output Current Power Loss Time Delay Input Power to Processor Disable
315mm (12.40")
Fuse 293mm (11.53")
Screw Torque Weight Dimensions (H x W x D) Environmental Conditions Operating Temperature Storage Temperature Relative Humidity 1771-CP1
Depth is 159mm (6.25")
12628-I
Cables
1771-CP2 1771-CP3
Backplane Load Current (Amps)
13.6msec ±2.9ms 3A, 250V 3AG normal blow (Bussmann AGC 3 Littelfuse 312003) 12 pound-inch 1.95kg (4.3 lbs.) 315mm x 115mm x 159mm (12.40" x 4.53" x 6.25" ) 32 to 140° F (0 to 60° C) -40 to 185° F (-40 to 85° C) 5 to 95%, non-condensing 0.32m (1.04ft) connects panel mounted I/O chassis to chassis mounted 1771-P7 1.52m (5ft) connects rack-mounted I/O chassis to remote 1771-P7 1.68m (5.5ft) connects panel-mounted I/O chassis to remote 1771-P7 marked for all applicable directives
Use these graphs to determine your: • cooling requirements • power cost • transformer size (unless the transformer manufacturer has a recommended multiplier for sizing a transformer for an ac-to-dc power supply)
16
16
16
12
12
12
8
8
8
4
4
4
0 20 input power to chassis ground
ÎÎ
Agency Certification (when product or packaging is marked)
Power Ratings
120V ac @ 2.0A 220V ac @ 1.0A 120V ac: 97-132V ac 220V ac: 195-264V ac 108 Watts/176VA 270VA at full load 47-63Hz 2500V dc for 1s 1800V ac (rms) for 1s 5.06V dc ±3.8% 16A max @ 5V dc
9
60
100
140
Apparent Power (VA)
180
0
0
30
60
90
Real Power (Watts)
120
0
0
75
150
225
300
Transformer Sizing (VA) = Real Power (Watts) x 2.5
PLC-2/02, PLC-2/05, PLC-2/16, and PLC-2/17 are trademarks of Allen-Bradley Company, Inc.
Publication 1771-5.39
December 1995
Page 10
10
AC (120/220V) 16A Power Supply
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the worlds leading technology companies.
Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1771-5.39
December 1995
Publication 1771-5.39
December 1995
PN 955123-01 Copyright 1995 Allen-Bradley Company, Inc. Printed in USA