The text of a manual · part 11 of 19
PLC-5 DeviceNet Scanner Module 1771-SDN User Manual: 5 - Communicating with DeviceNet from Another Network, pages 87 to 94
Pages 87 to 94 of 149, from PLC-5 DeviceNet Scanner Module 1771-SDN User Manual
The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-SDN
Page 87
Communicating with DeviceNet from Another Network
5-17
You will receive the following prompt:
6. Click on OK to upload the devices. RSNetWorx for DeviceNet will begin browsing for network devices.
ATTENTION
!
Performing a pass-through browse via the Ethernet network will take longer than browsing using the 1770-KFD DeviceNet driver as described in chapter 4. Note that due to the time required, the pass-through method is not suitable for configuring a network nor for real time monitoring of your network devices.
When RSNetWorx for DeviceNet is finished browsing, the network displayed on your screen should look similar to the one shown below.
You are now communicating with the DeviceNet network via the Ethernet network. See pages 4-6 to 4-17 of this manual for examples of how to use RSNetWorx for DeviceNet to adjust network parameters.
Publication 1771-UM118C-EN-P - June 2003
Page 88
5-18
Communicating with DeviceNet from Another Network
Communicating with DeviceNet from a DH+ Network
Before performing this example the DH+ network must be configured and running. In this example, the PLC-5 processor’s DH+ channel A is configured as node 1. Use your own DH+ configuration when performing this example.
Configuring the DeviceNet Pass-Through Driver Before you can communicate with the 1771-SDN module via a DH+ network, you must first configure the DeviceNet pass-through driver (1771-SDNPT) with a DH+ port. RSLinx, version 2.10 or higher, is required. Perform the following steps. 1. Start RSLinx.
2. From the Communications menu, select Configure Drivers. The Configure Drivers window will appear.
3. Select DeviceNet Drivers from the Available Driver Types pull-down list and click on Add/New.
Publication 1771-UM118C-EN-P - June 2003
Page 89
Communicating with DeviceNet from Another Network
5-19
You will see the following list of drivers.
4. Select the Allen-Bradley 1771-SDNPT driver. The Driver Configuration window will appear.
5. Select a pass-through port to be configured from the pull-down list, e.g., Port 3. 6. Expand your DH+ driver (AB_KT-1 above) and highlight the PLC-5 processor. 7. Select the 1771-SDN Backplane Address Configuration. We used the following configuration for the example application. Rack
0
Group
1
Slot
0
8. Select the DeviceNet Channel (Channel 1 for the example application). Publication 1771-UM118C-EN-P - June 2003
Page 90
5-20
Communicating with DeviceNet from Another Network
9. Click on OK. You will see the following warning:
10. Verify that the routing information is accurate and click on the Yes button. You will be prompted to enter a name for the driver.
11. Enter an appropriate driver name (e.g., 1771-SDNPT-3) and click on the OK button. The new driver will be added to the Configured Drivers in RSLinx. (Your list will contain the drivers you have configured.)
12. Close or Minimize RSLinx.
Publication 1771-UM118C-EN-P - June 2003
Page 91
Communicating with DeviceNet from Another Network
5-21
Communicating with the DeviceNet Network Once you have the DH+ pass-through driver configured, you can use RSNetWorx for DeviceNet to communicate with the DeviceNet network via the DH+ network. Perform the following steps: 1. Start RSNetWorx.
2. From the File menu, select New. If you have RSNetWorx for ControlNet installed on your computer you may see the following window. Otherwise, proceed to step 4.
3. Select DeviceNet Configuration and click on OK. 4. Click on the Online button on the toolbar.
Publication 1771-UM118C-EN-P - June 2003
Page 92
5-22
Communicating with DeviceNet from Another Network
The Browse for network window will appear. You will see the drivers you have configured on your system.
5. Highlight the 1771-SDNPT-3 driver and click on OK. You will receive the following prompt:
6. Click on OK to upload the devices. RSNetWorx for DeviceNet will begin browsing for network devices.
ATTENTION
!
Publication 1771-UM118C-EN-P - June 2003
Performing a pass-through browse via the DH+ network will take longer than browsing using the 1770-KFD DeviceNet driver as described in chapter 4. Note that due to the time required, the pass-through method is not suitable for configuring a network nor for real time monitoring of your network devices.
Page 93
Communicating with DeviceNet from Another Network
5-23
When RSNetWorx for DeviceNet is finished browsing, the network displayed on your screen should look similar to the one shown below.
You are now online to the DeviceNet network via the Data Highway Plus network. See pages 4-6 to 4-17 of this manual for examples of how to use RSNetWorx for DeviceNet to adjust network parameters.
What’s Next?
The next chapter describes how to create and run the example application program to test the DeviceNet Network.
Publication 1771-UM118C-EN-P - June 2003
Page 94
5-24
Communicating with DeviceNet from Another Network
Notes
Publication 1771-UM118C-EN-P - June 2003