Page 71
Chapter
5
Communicating with DeviceNet from Another Network
What This Chapter Contains This chapter describes how to communicate with the DeviceNet network from another network, using the PLC-5 “pass-through” feature. This feature can be used to adjust and fine tune the nodes on your network. Examples are provided for communicating from a ControlNet network, an Ethernet network, and a Data Highway Plus network.
ATTENTION
! IMPORTANT
The pass-through feature is not intended to replace a 1770-KFD, PCD, PCID, or PCIDS connection to the network: •
Pass-through is intended only for fine tuning and adjustment of your network devices. Do not attempt to configure your entire network using a pass-through driver, or a time-out may occur.
•
The pass-through method is not suitable for real time monitoring of your network devices.
To use the pass-through feature you must have the following versions of the RSLinx software and 1771-SDN module firmware: Component
Software/Firmware Version
RSLinx software
2.10 or higher
1771-SDN module
4.003 or higher
You must have previously set up the network you will use to communicate with the DeviceNet network and have installed and configured the appropriate drivers and interface hardware. The 1771 I/O chassis used for these examples was set up with the following hardware mapping: Module
1
Rack
Group
Slot
IP Address
PLC-5C/1785-ENET
0
0
0
192.168.1.1
1771-SDN
0
1
0 n/a
Publication 1771-UM118C-EN-P - June 2003
Page 72
5-2
Communicating with DeviceNet from Another Network
The following table describes what this chapter contains and where to find specific information. For information about
Where to Find More Information
More
For information about: the ControlNet PLC-5 processor the Ethernet interface module TCP/IP protocol and networking in general
Publication 1771-UM118C-EN-P - June 2003
See page
Where to Find More Information
5-2
Communicating with DeviceNet from a ControlNet Network
5-3
Communicating with DeviceNet from an Ethernet Network
5-9
Communicating with DeviceNet from a DH+ Network
5-18
What’s Next?
5-23
Refer to the following publications for information on configuring other networks: See this publication: ControlNet PLC-5 Programmable Controllers User Manual PLC-5 Ethernet Interface Module User Manual Comer, Douglas E., Internetworking with TCP-IP, Volume 1: Protocols and Architecture, 2nd ed. Englewood Cliffs, N.J.:Prentice-Hall, 1995. ISBN 0-13-216987-8. Tannebaum, Andrew S. Computer Networks, 2nd ed. Englewood Cliffs, N.J.: Prentice-Hall, 1989. ISBN 0-13-162959-X.
Publication number: 1785-UM022B-EN-P 1785-6.5.19 n/a n/a
Page 73
Communicating with DeviceNet from Another Network
Communicating with DeviceNet from a ControlNet Network
5-3
Before performing this example the ControlNet network must be configured and running. A ControlNet processor (PLC-5C) is required. In this example the PLC-5C processor is configured as ControlNet node 16. Use your own ControlNet PLC-5C processor’s configuration when performing this example.
Configuring the DeviceNet Pass-Through Driver Before you can communicate with the 1771-SDN module via the ControlNet network, you must first configure the DeviceNet pass-through driver (1771-SDNPT) with a ControlNet port. RSLinx, version 2.10 or higher, is required. To configure the ControlNet pass-through driver perform the following steps: 1. Start RSLinx.
2. From the Communications menu, select Configure Drivers.
3. From the list of Available Driver Types select DeviceNet Drivers and click on Add/New. Publication 1771-UM118C-EN-P - June 2003
Page 74
5-4
Communicating with DeviceNet from Another Network
You will see the following list of drivers.
4. Select the Allen-Bradley 1771-SDNPT driver. The Driver Configuration window will appear.
5. Select a pass-through port to be configured from the pull-down list, e.g., Port 1. IMPORTANT
You must configure each port for each DeviceNet channel on the scanner module. If there are more than two scanner modules (four DeviceNet channels) on your system, you will need more than one driver configured for connection to the PLC-5.
6. Expand your installed ControlNet driver (AB_KTC-1 in the example) and highlight your PLC-5C processor. 7. Select the 1771-SDN Backplane Address Configuration. We used the following configuration for the example application.
Publication 1771-UM118C-EN-P - June 2003
Page 75
Communicating with DeviceNet from Another Network
Rack
0
Group
1
Slot
0
5-5
8. Select the DeviceNet Channel (Channel 1 for the example application). 9. Click on OK. You will see the following warning:
10. Verify that the routing information is accurate and click on the Yes button. You will be prompted to choose a name for the driver.
11. Enter an appropriate driver name (e.g., 1771-SDNPT-1) and click on the OK button.
Publication 1771-UM118C-EN-P - June 2003
Page 76
5-6
Communicating with DeviceNet from Another Network
The new driver will be added to the Configured Drivers in RSLinx. (Your list will contain the drivers you have configured.)
12. Close or Minimize RSLinx.
Communicating with the DeviceNet Network Once you have the ControlNet pass-through driver configured, you can use RSNetWorx for DeviceNet to communicate with the DeviceNet network via the ControlNet network. Perform the following steps: 1. Start RSNetWorx.
Publication 1771-UM118C-EN-P - June 2003
Page 77
Communicating with DeviceNet from Another Network
5-7
2. From the File menu, select New. If you have RSNetWorx for ControlNet installed on your computer you may see the following window. Otherwise, proceed to step 4.
3. Select DeviceNet Configuration and click on OK. 4. Click on the Online button on the toolbar.
The Browse for network window will appear. You will see the drivers you have configured on your system.
5. Highlight your DeviceNet pass-through driver (1771-SDNPT-1 above) and click on OK.
Publication 1771-UM118C-EN-P - June 2003
Page 78
5-8
Communicating with DeviceNet from Another Network
You will receive the following prompt:
6. Click on OK to upload the devices. RSNetWorx for DeviceNet will begin browsing for network devices.
ATTENTION
!
Performing a pass-through browse via the ControlNet network will take longer than browsing using the 1770-KFD DeviceNet driver as described in chapter 4. Note that due to the time required, the pass-through method is not suitable for configuring a network nor for real time monitoring of your network devices.
When RSNetWorx for DeviceNet is finished browsing, the network displayed on your screen should look similar to the one shown below.
You are now communicating with the DeviceNet network via the ControlNet network. See pages 4-6 to 4-17 of this manual for examples of how to use RSNetWorx for DeviceNet to adjust network parameters.
Publication 1771-UM118C-EN-P - June 2003