The text of a manual · part 2 of 10
Mini-PLC-2/05 Assembly and Installation Manual, pages 11 to 20
Pages 11 to 20 of 92
The original document is the PDF (4.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1772-LS A
Page 11
Page 2-3
Mini-PLC-2/05: An Overview
Hardware Features
Figure 2.2 shows the two Mini-PLC-2/05 processors. Table 2.A lists the hardware associated with each processor.
a
RUN ro
© FAULT oDwjo
N
0 ON
INTFC i?) ie)
MINI-PLC-2/05
Mini-PLC-2/05 (cat. no. 1772-LS)
P RUN R
P/S Be FAULT ACTIVE
ON ON
P/S PARALLEL (AB) S77
INTFE: POWER o ON
OFF 1.0A 125 SLOW BLOW
MINI-PLC-2/05 W/POWER SUPPLY
Mini-PLC-2/05 with power supply (cat. no. 1772-LSP)
12049
Figure 2.2, Mini-PLC-2/05 Processor Modules
Page 12
Page 2-4 Mini-PLC-2/05: An Overview
Table 2.A Hardware for the Mini-PLC-2/05 Processor
Hardware Feature 1772-LSP 1772-LS Status Indicators ¢ PROC RUN/FAULT x x ¢ P/S ACTIVE xX, Connector Ports © INTFC xX xX e P/S paralleling xX, Power Switch X _ - Memory Store Switch xX xX Fuse x _ Terminal Strip x Battery x x Industrial Terminal x X Status Indicators Two LED status indicators show: Status Indicator: If the color is: Then the indication represents: PROC RUN/FAULT Green Run/program mode Green for 2 seconds EEPROM memory module being programmed. Off The processor is either in remote program mode, remote test mode; or there is a run time error, memory error, or a program error. Red The watchdog timer is timed out; therefore you should cycle power to reset the processor. P/S ACTIVE Green AC or DC power is available. Off AC or DC power is not available.
MEMORY STORE Switch
If you have our optional memory module, this switch allows you to duplicate programmed memory from the processor’s internal CMOS RAM in the memory module. You can duplicate memory only when the processor is operating in remote program mode.
Page 13
Page 2-5 Mini-PLC-2/05: An Overview
P/S PARALLEL
INTFC Connector
Connect the paralleling cable (cat. no. 1771-CT) between this port on the 1772-LSP processor and one power supply module in the same I/O chassis. Also, connect the paralleling cable between two power supply modules in the same I/O chassis when using the 1772-LS processor.
Chapter 3 describes connection information in detail.
This 15-pin connector provides communication between:
Processor and: Using: Cable Cat. No. Industrial terminal PLC-2 Program Panel Interconnect Cable 1772-TC Data Highway modules Data Highway/Processor Cables 1771-CN, -CO, or -CR PLC-2 report PLC-2 Program Panel Interconnect Cable 1772-TC
(you must use an external ground wire)
POWER Switch
Fuse
Terminal Strip
This is a toggle on/off switch which lets you provide power to your processor (if external power is connected).
We ship the processor with a l-amp “‘slow-blow” fuse in the fuse holder for 120V AC operation.
The 120V AC power source connects to this terminal strip (chapter 3) and provides connections for the power supply module. The terminal strip is labeled:
e Li for the power line (hot) e N for neutral e GND for chassis ground
Page 14
Page 2-6 Mini-PLC-2/05: An Overview
Battery The processor includes an AA size lithium battery containing 0.5 gram of lithium. It retains the processor’s memory after a power loss to the processor. A removable holder located at the rear of your processor (figure 2.3) houses this battery. This battery supports the processor’s stored memory for up to two years even when AC power is not applied to your processor. You should write the date on the label at the side of the processor after you receive your processor so you'll know when to replace this battery every two years.
See chapter 4 for battery replacement instructions.
BLACK
Place battery (Panes installation date - - =w 7 / here > ©
PP l
12050
Figure 2.3, Document the Battery’s Installation Date on the Side of the Processor
Page 15
Page 2-7 Mini-PLC-2/05: An Overview
Industrial Terminal
Use our industrial terminal (figure 2.4) to access the processor’s different modes of operation.
12051
Figure 2.4, Use the Industrial Terminal to Access the Processor’s Different Modes of Operation
We define each mode of operation as:
Run/Program, This is the normal mode of operation. The outputs are controlled by the user program. You can edit your program and make on-line data changes when your processor is operating in this mode.
Remote Test, The program runs, the inputs are scanned, the outputs are disabled, and selected timed interrupts can be executed.
Remote Program, The processor stops scanning and executing its stored program and waits for your commands from the programmer. If an optional EEPROM memory module is installed, the processor must be in the remote program mode when transferring memory contents from the processor’s RAM memory.
If the processor’s power fails (after power up), and switch 6 is on, then the processor returns to the last programmed mode of operation. We discuss switch 6 in chapter 3.
Refer to the Mini-PLC-2/05 Processor Programming and Operations Manual (publication 1772-6.8.6) for instructions on how to program and operate your processor through the industrial terminal.
Page 16
Page 2-8
Mini-PLC-2/05: An Overview
Optional Hardware
EEPROM Memory Module Our EEPROM memory module (figure 2.5) houses an EEPROM chip that stores 3K words of memory. You can transfer your program into this EEPROM memory module for long-term program storage. To read about how to insert and remove the memory module, refer to chapter 4.
CAT. NO. 1772-MJ EEPROM MEMORY MODULE ALLEN-BRADLEY CO,
SERIAL NO
MADE INUS.A.
12052
Figure 2.5, Use the EEPROM Memory Module to Store Your Programs
Power Supplies Table 2.B lists the power supplies used with the Mini-PLC-2/05 processors (figure 2.6).
1771-P3 power supply module 1771-P4 power supply module 1771-P5 power supply module AC power, single-slot AC power, dual-slot DC power, dual-slot
12053
Figure 2.6, Three Power Supply Modules Used with the Mini-PLC-2/05 Processors
Page 17
Page 2-9
Mini-PLC-2/05: An Overview
You can not use the 1771-P1, -P2 power supplies with
Mini-PLC-2/05 processors.
Table 2.B Power Supplies Used with the Mini-PLC-2/05 Processors
Specification 1771-P3 1771-P4 1771-P5 Input source voltage 97 to 97 to 20.5 to 132V AC 132V AC 30V DC Current available for |/O modules without processor 3A 8A 8A Current available for |1/O modules using the 1772-LS processor 1.75A 6.75A 6.75A Current available for 1/O modules using the 1772-LSP processor 5.00A 10.00A We do not recommend using the 1771-P5 power supply with the 1772-LSP processor. * Battery for CMOS RAM backup No No No 1/O chassis slot space required 1 2 2
* The 1772-LSP processor itself provides 2A of current for the I/O modules.
Page 18
Page 2-10 Mini-PLC-2/05: An Overview
PLC-2 Family Report The PLC-2 family report generation module (figure 2.7) Generation Module _ provides bidirectional RS-232-C communication for report generation between a peripheral device and your Mini-PLC-2/05 processor.
12054
Figure 2.7, Use the PLC-2 Family Report Generation Module to Display Messages Stored in the Processor’s Memory
Page 19
Page 2-11 Mini-PLC-2/05: An Overview
Data Cartridge Recorder
You can use this module to: ® enter messages into memory e edit stored messages by a series of keystrokes from the keyboard of the peripheral device
¢ display messages stored in the processor’s memory.
You can display messages either manually by a series of keystrokes (command mode) or automatically through your program (auto report mode).
The data cartridge recorder (figure 2.8) is a portable, high-speed recording device that stores programs. Its magnetic tape cartridge allows you to record, load, and verify the processor’s total memory. Additional data cartridges can be ordered to maintain a library of programs for production requirements.
12055
Figure 2.8, Use the Data Cartridge Recorder to Record, Load and Verify the Processor’s Total Memory
If you have our Digital Cassette Recorder (cat. no. 1770-SA), you can use it with the Mini-PLC-2/05 processor.
Page 20
Page 2-12 Mini-PLC-2/05: An Overview
Hand-Held Terminal The hand-held terminal (figure 2.9) lets you change, monitor, and force I/O bits stored in processor memory. You can access the following information:
12056
Figure 2.9, Use the Hand Held Terminal to Access Data Table Information Stored in the Processor’s Memory status of actual and forced I/O bits accumulated and preset values for timers and/or counters results of math calculations diagnostic data ¢ bit values stored in block instructions’ files
The hand-held terminal connects to the port labeled INTFC on the Mini-PLC-2/05 processor. You can use either the industrial terminal or hand-held terminal to access and/or monitor bits in the data table. However, if you need to access and/or monitor data at several remote sites, use the smaller hand-held terminal.