For the Allen-Bradley 1772-LS A
Page 21
Page 2-13 Mini-PLC-2/05: An Overview
Battery Pack
Chapter Summary
Figure 2.10 shows the battery pack (cat. no. 1771-BB) consisting of:
If the battery housing has a different configuration, correct polarity will be clearly labeled in the battery holder. = 3 ar
Orientation
= O - Alkaline Alkaline Battery ie Li :
Exchange Clips
\ anutranapon cable (cat. no. 1772-CD)
Figure 2.10, Battery Pack with Two Alkaline Batteries Installed
® metal battery housing ® mounting hardware set e two D-size alkaline batteries
The battery pack supports RAM memory. Use our mini-transport cable (cat. no. 1772-CD) to connect the battery pack when you replace the processor’s internal battery (chapter 4).
Contact your local Allen-Bradley sales engineer or distributor for additional information on our optional hardware.
In this chapter you read about the hardware associated with your Mini-PLC-2/05 processor. In the next chapter, we describe how to install your processor system.
Page 22
Page 23
Chapter
Installing Your Processor System
Chapter Objectives
Related Hardware
In this chapter you will read about:
e what hardware you need to install your processor system
@ where to install your processor system
© how to install your processor system
To install and replace the Mini-PLC-2/05 processor’s hardware, see chapter 4.
Table 3.A lists the hardware needed to install your processor system.
Hardware for Your Processor System
Allen-Bradley Hardware
Catalog Number
I/O Chassis
I/O Modules
Industrial Terminal
Power Supply Moduies Emergency Stop Switches Master Control Relay Disconnects
Suppression devices
1771-A1, -A2, -A4
1771 product line
1770-T3
1771-P3, -P4, -P5
800 product line
700 product line
1494 product line
599-K04, 700-N24, 1401-N10
Quantity of the hardware depends upon your application. Consult your local Allen-Bradley sales engineer or distributor for more information concerning these items.
Page 24
Page 3-2 Installing Your Processor System
Where to Install Your Processor System
Location
In addition to our hardware, we recommend:
© a metal enclosure to protect your processor from EMI noise and airborne contaminants e enclosure backpanel
¢ isolation transformers or constant-voltage transformers ® power supplies for I/O devices
¢ 6.35-mm (0.25-inch) mounting bolts
* equivalent to Belden cable 8761 (single twisted-pair shielded cable)
® power cable for AC input power © electrical tape or shrink tubing
® tie wraps for wires
Refer to the Programmable Controller Wiring and Grounding Guidelines (publication 1770-980) before you begin actually installing hardware.
A well-planned layout is essential for the installation of the Mini-PLC-2/05 processor. You should consider the following factors when planning installation of the Mini-PLC-2/05 processor at your facility:
¢ where to locate your processor system
¢ how to integrate your processor system with other plant machinery
® how to protect your processor system
Let’s look at each of these factors.
Determining the proper environment should be your primary concern. We specify:
* operating temperature: 0 to 60°C (32 to 140°F) © storage temperature: -40 to 85°C (-40 to 185°F) ¢ relative humidity: 5 to 95% (without condensation)
We also recommend noise suppressors. Special considerations should be given to possible electrical noise interference.
Page 25
Page 3-3 Installing Your Processor System
Noise Generators Potential noise generators include inductive devices such as relays, solenoids, motors and motor starters when they are operated by pushbuttons and selector switches. You'll need suppression for noise generators when inductive devices are connected:
© as output devices ® along the same AC power line that powers your processor
Figure 3.1 shows what suppressors you need to reduce electric noise. Table 3.B lists each suppressor that complements our equipment.
230/460V AC eq!
$$ 120 AC >, . eo o-
3-Phase
Electro Cube Inc. Motor
Part No. RG 1676-13
Allen-Bradley §=£ - - aei i Catalog No. 1691-N2
Suppressor for 3-phase apparatus Suppressor for small aparatus fname mn, - 1 20 AG | at
Voc Lael
_li oo oc
Part No. RG 1676-14
Suppressor for large appartus Suppressor for DC relays
12057
Figure 3.1, Use the Noise Suppression Equipment to Reduce Electric Noise
Table 3.B Allen-Bradley Suppressors Suppressor Allen-Bradley Cat. No. Equipment
599-K04* Motor Starter 509 1401-N10** | Motor Starter 709 700-N24** | Relay 700 Type N or P 700-N24 Miscellaneous
*For starters with 120V AC coils.
**The 700-N24 is a universal surge suppressor. It can be used on electromagnetic devices with the limitation of 35 sealed VA, 150V.
Page 26
Page 3-4 Installing Your Processor System
Integration
Protection
The Mini-PLC-2/05 processor system should be separated from other equipment and plant walls to allow for convection cooling. Convection cooling draws a vertical column of air upward over the processor. This cooling air must not exceed 60°C (140°F) at any point immediately below the processor. If the air temperature exceeds 60°C then install:
e fans (which bring in filtered air or recirculate internal air) inside the enclosure, or
® air conditioning/heat exchangers Follow these guidelines when installing your processor system:
¢ Allow six vertical inches above and below all processor components. When you use more than one processor in the same area, allow six vertical inches between each processor.
¢ Allow four horizontal inches on the sides of each processor component. When you use more than one processor in the same area, allow six horizontal inches between each processor.
e Allow two inches (vertical and horizontal) between the processor and the wiring duct or terminal strips.
© Mount the I/O chassis horizontally to allow for convection cooling.
You provide the enclosure for your processor system. This enclosure is the primary means of protecting your processor system from atmospheric contaminants such as oil, moisture, dust, and corrosive materials, or other harmful airborne substances. We suggest that you use an enclosure that conforms to the National Electrical Manufacturer’s Association (NEMA) standard.
Mount the enclosure in a position that lets you fully open the doors. You need easy access to the processor’s wiring and related components so that troubleshooting is convenient.
When choosing the enclosure size, allow extra space for isolation transformers, fusing, disconnect switch, master control relay, and terminal strips. Your processor requires a minimum of eight inches of space from the rear of the chassis to the innermost surface of the enclosure.
Page 27
Page 3-5 Installing Your Processor System
How to Install Your Now that you’ve planned your production site, you can install Processor System _your new system. Figure 3.2 gives the names and shows location for each piece of hardware. This manual provides general installation guidelines. The input and output devices that control your manufacturing operations determine the specifics of your installation.
Mini-PLC-2/05 Processor |} >. “a || Mini-PLC-2/05 Processor (cat. no. 1772-LS) or |_| (cat. no. 1772-LSP)
i I/O Chassis Assembly | (cat.no. 1771-A1, A2,A4) | 32/0 64 1/0 | 128 1/0 oleé LS _ LS AA “|| /O Module = <_E Field Wiring = Arm ote <
12058
Figure 3.2, I/O Chassis Location of the Mini-PLC-2/05 Processor System
Page 28
Page 3-6 Installing Your Processor System
Task 1
Mounting and Grounding Hardware to the Backpanel
Installing your processor involves ten tasks. Perform these tasks in order.
e Task 1- Mounting and grounding hardware to the backpanel e Task 2- Setting the switches within the switch group assembly e Task 3- Installing keying bands and field wiring arms Task 4- Installing I/O modules e Task 5- Installing your processor e Task 6- Installing your power supply(ies)
e Task 7- Mounting the backpanel
¢ Task 8- Wiring field wiring arms e Task 9- Connecting the power cable to the terminal strip e Task 10- Installing the industrial terminal
Use 6.35-mm or 0.25-inch mounting bolts to attach the I/O chassis to the enclosure backpanel. For component spacing and dimensions see figures 3.3 and 3.4.
Grounding is an important safety measure in electrical installations. It helps to reduce the effects of electromagnetic noise.
Before grounding your processor system, consult the following sources of information:
¢ Allen-Bradley Programmable Controller Wiring and Grounding Guidelines (publication 1770-980)
¢ National Electrical Code, published by the National Fire Protection Association of Boston, Massachusetts e local codes and ordinances
Page 29
Page 3-7 Installing Your Processor System
Area reserved for disconnect, constant voltage transformer, control relays, motor starters or other user devices
\ LO
Processor 9" (5.08¢m), »| _ - S 1772-LSP Processor hi 4" (with $i | | \$|| | $$ tae, (10.16m) power supply) SUPE ELE anal | *|L | Ls * e - - (10.16¢m) - - _»> 6 Wiring D (15.24cm) iring Duct 2" (5.08¢m) 12059
Figure 3.3, Minimum Component Spacing for the Mini-PLC-2/05 Processor System
Page 30
Page 3-8
Installing Your Processor System
23.4" mee. (59.44em) gg 9 13.4” +, - - - ___ (34.04em), - - - - - | 64 1/0 8.4" “ (21.34cm), Om] 82:0 ® cm A By i | iT i 114.25" LU 10.0” (28.5cm) @ ro) (25:4cm) Tl a | LS ) oe ® @ © J Y a ~ yh eg 6.75" « 9.00" x] 32 1/0 (17.15¢m) (24.74 cm) < - $ - - 351°, - - - - - , « 14.15 _ ~ 64 |/ (21.62cm) (35.94cm) 64 1/0 - 24.15" _p| 128 1/0 (61.34cm) 12060
Figure 3.4, Dimensions for 1/0 Chassis (cat. no. 1771-A1, -A2, -A4)
Master Control Relay
You supply and install the master control relay and emergency stop switches. Place an emergency stop switch at each operator station and at an accessible point on the machine. Locate each emergency stop switch so it is easy for you to reach; wire them in series. Make certain that the master control relay contacts have sufficient rating for your particular application.
Any emergency stop switch should turn off all machine power, by turning off the master control relay.
WARNING: Do not program your processor to control the master control relay. Damage to your equipment or injury to your personnel can occur. Instead provide a hard-wired emergency stop circuit.