Page 3-9 Installing Your Processor System

Task 2

Setting the Switches within the Switch Group Assembly

Every machine connected to your processor must have an emergency stop switch that stops machine motion whenever the master control relay de-energizes. The master control relay must be a backup circuit to the processor in every case where unexpected machine motion could damage machinery or injure personnel. If a failure occurs in the processor, this backup circuit must be able to stop machine motion.

The master control relay is not a substitute for a power disconnect device. Use the disconnect device to quickly de-energize your I/O devices. To replace any I/O modules, fuses, or when working on the equipment, turn off the power to your I/O chassis backplane as well as the power to the I/O circuits.

The eight switches in this assembly determine the processor’s response for memory protection and power up sequence. This switch group is at the left side of the I/O chassis backplane (figure 3.5).

Switch Group Assembly

Set switches 6 thru 8

Figure 3.5, The Backplane of the I/O Chassis Contains the Switch Group Assembly

Set these switches before you install the processor. This programs the processor to respond appropriately during a power failure.

Page 32 read from a scan by OCR; it may hold reading errors

Page 3-10 Installing Your Processor System

Table 3.C explains how each switch is used with the processor. Switches 1, 2, 3, 4, and 5 are not used.

Table 3.C Meaning of Switch Group Settings

If: And: Then:

Switch 6 is off, Contents of the EEPROM memory module are transferred to CMOS RAM, whether or not CMOS RAN is valid.

Switch 6 is on Switch 7 is on If CMOS RAM is valid, then EEPROM memory does not transfer to CMOS RAM.

If CMOS RAM is not valid, then EEPROM memory does transfer to CMOS RAM.

Switch 6 is on Switch 7 is off Memory transfer does not occur. If CMOS RAM is not valid, a processor fault occurs.

Switch 8 is off, RAM Memory protect is disabled. «

Switch 8 is on, _ RAM Memory protect is enabled. «

* When memory protect is enabled, you can oniy change the status and values of the bits in the first 128 words (word addresses up to 177) of the processor's data table.

Use a ball-point pen to set each switch. Do not use a pencil because the tip can break off and jam the switch.

Page 33 read from a scan by OCR; it may hold reading errors

Page 3-11 Installing Your Processor System

Task 3 Weship plastic keying bands with each I/O chassis. With your Installing Keying Bands __ fingers, insert two keying bands in the top backplane sockets of and Field Wiring Arms the I/O chassis. For the processor, place one keying band in the leftmost slot between pins (figure 3.6):

e 40 and 42 e 54 and 56 \/O Chaissis’ Backplane Connector rs Use these Numbers as a Guide Keying Bands (cat. no. 1777-RK) \ 12062

Figure 3.6, Place the Keying Bands on the Backplane of the !/O Chassis

Use the numbers to the right of the backplane socket as a guide when positioning the keying bands.

Refer to the individual product data publications for the keying position for each I/O module.

CAUTION: If keying bands are not installed, a module inserted into a wrong slot could be damaged by improper voltages connected through the wiring arm. Short circuits on the I/O module can result from misalignment if keying bands are not installed.

Page 34 read from a scan by OCR; it may hold reading errors

Page 3-12 Installing Your Processor System

Snap each field wiring arm onto the lower horizontal bar of the © I/O chassis (figure 3.7). When I/O modules are in place, the field wiring arm pivots and connects to the module.

Leave enough slack for pivoting

12063

Figure 3.7, Placement of Field Wiring Arm

Do not place any I/O modules in the leftmost slot. Your processor goes there.

Page 35 read from a scan by OCR; it may hold reading errors

Page 3-13 Installing Your Processor System

Task 4 = Insert each I/O module into its corresponding keyed slot by Installing 1/O Modules _ sliding it onto the plastic tracks of the I/O chassis (figure 3.8). Snap the module locking latch over the I/O module.

1/O Module Locking Latch

Field Wiring Arm Locking Tab

Plastic Tracks Guide I/O Moduies into Position

12064

Figure 3.8, Place each I/O Module into its Corresponding Keyed Slot in the I/O Chassis

CAUTION: Do not force an I/O module into a backplane connector. Forcing an I/O module can damage the backplane connector or the I/O module.

Page 36 read from a scan by OCR; it may hold reading errors

Page 3-14 Installing Your Processor System

Calculate the total current requirement for all installed modules to ensure that the sum does not exceed the limit of the I/O chassis’ power supply. The 1772-LSP processor provides 2A to power the I/O modules. If you need additional power, we have three power supply modules that you can choose from:

Catalog Input

Number Voltage Current 1771-P3 120V AC 3A 1771-P4 120V AC BA 1771-P5 24V DC BA

WARNING: In order to enhance power supply reliability, the processor supply modules, and 1772-LS processor use a controlled “soft start” power-up or power-down feature. During soft start, the following outputs can momentarily change state:

Catalog

Number Product Series 1771-OD Isolated AC (120V) Output Module Assembly | B or earlier 1771-OY Contact Output Module Assembly B or earlier 1771-OZ Contact Output Module B or earlier

Disconnect all power from apparatus that can cause damage to equipment or injure personnel during power-up and power down of the power supply modules and 1772-LS processor.

Products labeled Series C or later are not affected.

If you need more information on these power supplies, refer to the appropiate publication, or consult our Publications Index (publication SD499). Task 6 describes where to install your power supply within the I/O chassis.

Page 37 read from a scan by OCR; it may hold reading errors

Page 3-15 Installing Your Processor System

Task 5 Slide your processor into the left most slot of the I/O chassis Installing Your Processor (figure 3.9).

Left-Most Slot

12065

Figure 3.9, Place the Mini-PLC-2/05 Processor(s) in the Left-Most Slot of the I/O Chassis

CAUTION: Do not place your processor in the I/O chassis without keying bands. Short circuits can result from misalignment.

Page 38 read from a scan by OCR; it may hold reading errors

Page 3-16 Installing Your Processor System

Task 6 Installing Your Power

Supply

Skip task 6 if you have a 1772-LSP processor and do not need additional current for your I/O modules.

Figures 3.10, 3.11, and 3.12 show you where to locate a power supply within the I/O chassis. Table 3.D summarizes their location within the I/O chassis. Location depends upon I/O chassis size, not the type of power supply.

We do not recommend using the 1771-P5 power supply with the 1772-LSP processor.

1772-LS Processor System

Is | 0 7 2 aS

We show the 1771-P3 power supply for demonstration purposes

12066

Figure 3.10, Locating a Power Supply in the 1771-A1 I/O Chassis

Page 39 read from a scan by OCR; it may hold reading errors

Page 3-17

Installing Your Processor System

1772-LS Processor System he Gf dencencese:

raceiy ug

=I

We show the 1771-P3 power supply for demonstration purposes acl ls

12067

Figure 3.11, Locating a Power Supply in the 1771-A2 I/O Chassis

Page 40 read from a scan by OCR; it may hold reading errors

Figure 3.12, Locating a Power Supply in the 1771-A4 I/O Chassis

12068

We show the 1771-P3 power supply for demonstration purposes eeesseocces

2600000600)

ebeeese000

Le eucestesee!

eeesess eee:

L

CL

PRE Olen 2 ae [Saba Sa FET eocccecese!.

LC senecccece

Le

S0eccccces eeeccesces

S60Coeess

1772-LSP Processor System cocceseces!

[

Le eeccceeece

1772-LS Processor System

Installing Your Processor System