Page 31
Page 3-9 Installing Your Processor System
Task 2
Setting the Switches within the Switch Group Assembly
Every machine connected to your processor must have an emergency stop switch that stops machine motion whenever the master control relay de-energizes. The master control relay must be a backup circuit to the processor in every case where unexpected machine motion could damage machinery or injure personnel. If a failure occurs in the processor, this backup circuit must be able to stop machine motion.
The master control relay is not a substitute for a power disconnect device. Use the disconnect device to quickly de-energize your I/O devices. To replace any I/O modules, fuses, or when working on the equipment, turn off the power to your I/O chassis backplane as well as the power to the I/O circuits.
The eight switches in this assembly determine the processor’s response for memory protection and power up sequence. This switch group is at the left side of the I/O chassis backplane (figure 3.5).
Switch Group Assembly
Set switches 6 thru 8
Figure 3.5, The Backplane of the I/O Chassis Contains the Switch Group Assembly
Set these switches before you install the processor. This programs the processor to respond appropriately during a power failure.
Page 32
Page 3-10 Installing Your Processor System
Table 3.C explains how each switch is used with the processor. Switches 1, 2, 3, 4, and 5 are not used.
Table 3.C Meaning of Switch Group Settings
If: And: Then:
Switch 6 is off, Contents of the EEPROM memory module are transferred to CMOS RAM, whether or not CMOS RAN is valid.
Switch 6 is on Switch 7 is on If CMOS RAM is valid, then EEPROM memory does not transfer to CMOS RAM.
If CMOS RAM is not valid, then EEPROM memory does transfer to CMOS RAM.
Switch 6 is on Switch 7 is off Memory transfer does not occur. If CMOS RAM is not valid, a processor fault occurs.
Switch 8 is off, RAM Memory protect is disabled. «
Switch 8 is on, _ RAM Memory protect is enabled. «
* When memory protect is enabled, you can oniy change the status and values of the bits in the first 128 words (word addresses up to 177) of the processor's data table.
Use a ball-point pen to set each switch. Do not use a pencil because the tip can break off and jam the switch.
Page 33
Page 3-11 Installing Your Processor System
Task 3 Weship plastic keying bands with each I/O chassis. With your Installing Keying Bands __ fingers, insert two keying bands in the top backplane sockets of and Field Wiring Arms the I/O chassis. For the processor, place one keying band in the leftmost slot between pins (figure 3.6):
e 40 and 42 e 54 and 56 \/O Chaissis’ Backplane Connector rs Use these Numbers as a Guide Keying Bands (cat. no. 1777-RK) \ 12062
Figure 3.6, Place the Keying Bands on the Backplane of the !/O Chassis
Use the numbers to the right of the backplane socket as a guide when positioning the keying bands.
Refer to the individual product data publications for the keying position for each I/O module.
CAUTION: If keying bands are not installed, a module inserted into a wrong slot could be damaged by improper voltages connected through the wiring arm. Short circuits on the I/O module can result from misalignment if keying bands are not installed.
Page 34
Page 3-12 Installing Your Processor System
Snap each field wiring arm onto the lower horizontal bar of the © I/O chassis (figure 3.7). When I/O modules are in place, the field wiring arm pivots and connects to the module.
Leave enough slack for pivoting
12063
Figure 3.7, Placement of Field Wiring Arm
Do not place any I/O modules in the leftmost slot. Your processor goes there.
Page 35
Page 3-13 Installing Your Processor System
Task 4 = Insert each I/O module into its corresponding keyed slot by Installing 1/O Modules _ sliding it onto the plastic tracks of the I/O chassis (figure 3.8). Snap the module locking latch over the I/O module.
1/O Module Locking Latch
Field Wiring Arm Locking Tab
Plastic Tracks Guide I/O Moduies into Position
12064
Figure 3.8, Place each I/O Module into its Corresponding Keyed Slot in the I/O Chassis
CAUTION: Do not force an I/O module into a backplane connector. Forcing an I/O module can damage the backplane connector or the I/O module.
Page 36
Page 3-14 Installing Your Processor System
Calculate the total current requirement for all installed modules to ensure that the sum does not exceed the limit of the I/O chassis’ power supply. The 1772-LSP processor provides 2A to power the I/O modules. If you need additional power, we have three power supply modules that you can choose from:
Catalog Input
Number Voltage Current 1771-P3 120V AC 3A 1771-P4 120V AC BA 1771-P5 24V DC BA
WARNING: In order to enhance power supply reliability, the processor supply modules, and 1772-LS processor use a controlled “soft start” power-up or power-down feature. During soft start, the following outputs can momentarily change state:
Catalog
Number Product Series 1771-OD Isolated AC (120V) Output Module Assembly | B or earlier 1771-OY Contact Output Module Assembly B or earlier 1771-OZ Contact Output Module B or earlier
Disconnect all power from apparatus that can cause damage to equipment or injure personnel during power-up and power down of the power supply modules and 1772-LS processor.
Products labeled Series C or later are not affected.
If you need more information on these power supplies, refer to the appropiate publication, or consult our Publications Index (publication SD499). Task 6 describes where to install your power supply within the I/O chassis.
Page 37
Page 3-15 Installing Your Processor System
Task 5 Slide your processor into the left most slot of the I/O chassis Installing Your Processor (figure 3.9).
Left-Most Slot
12065
Figure 3.9, Place the Mini-PLC-2/05 Processor(s) in the Left-Most Slot of the I/O Chassis
CAUTION: Do not place your processor in the I/O chassis without keying bands. Short circuits can result from misalignment.
Page 38
Page 3-16 Installing Your Processor System
Task 6 Installing Your Power
Supply
Skip task 6 if you have a 1772-LSP processor and do not need additional current for your I/O modules.
Figures 3.10, 3.11, and 3.12 show you where to locate a power supply within the I/O chassis. Table 3.D summarizes their location within the I/O chassis. Location depends upon I/O chassis size, not the type of power supply.
We do not recommend using the 1771-P5 power supply with the 1772-LSP processor.
1772-LS Processor System
Is | 0 7 2 aS
We show the 1771-P3 power supply for demonstration purposes
12066
Figure 3.10, Locating a Power Supply in the 1771-A1 I/O Chassis
Page 39
Page 3-17
Installing Your Processor System
1772-LS Processor System he Gf dencencese:
raceiy ug
=I
We show the 1771-P3 power supply for demonstration purposes acl ls
12067
Figure 3.11, Locating a Power Supply in the 1771-A2 I/O Chassis
Page 40
Figure 3.12, Locating a Power Supply in the 1771-A4 I/O Chassis
12068
We show the 1771-P3 power supply for demonstration purposes eeesseocces
2600000600)
ebeeese000
Le eucestesee!
eeesess eee:
L
CL
PRE Olen 2 ae [Saba Sa FET eocccecese!.
LC senecccece
Le
S0eccccces eeeccesces
S60Coeess
1772-LSP Processor System cocceseces!
[
Le eeccceeece
1772-LS Processor System
Installing Your Processor System
Page 3-18