Manual · Allen-Bradley
Mini-PLC-2/05 Assembly and Installation Manual
Manual92 pagesPDF 4.0 MB
Assembly and installation manual for the Allen-Bradley Mini-PLC-2/05 processor, catalog numbers 1772-LS and 1772-LSP (with power supply).
Covers · 1 model
The models it covers
Summary
What is in it
A procedure-oriented manual that tells an installer how to set up a Mini-PLC-2/05 processor system, part of the PLC-2 family. It covers the 1772-LS processor and the 1772-LSP version with an integral power supply. Inside: an overview of the processor's features, status indicators and optional hardware, installation of the backpanel, switches, field wiring arms and power supplies, installing the EEPROM memory module and battery, system start-up and testing, and troubleshooting.
Its parts
- Before You Begin
- Mini-PLC-2/05: An Overview
- Installing Your Processor System
- Installing and Replacing the Mini-PLC-2/05 Processor's Hardware
- System Start-Up
- Troubleshooting Your Processor System
- Glossary
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Assembly and installation manual for the Allen-Bradley Mini-PLC-2/05 processor, a PLC-2 family processor. It covers two versions: the 1772-LS without a power supply and the 1772-LSP with an integral power supply. It explains the hardware, power supply choices, backplane switch settings, battery replacement and troubleshooting.
- Device
- Mini-PLC-2/05 processor for the PLC-2 family; 1772-LS has no power supply, 1772-LSP has one built in p. 9
- Memory
- 3K CMOS RAM; data table up to 2944 words p. 10
- Timers and I/O
- 488 timers; 128 I/O device capability; full I/O forcing p. 10
- Memory backup battery
- AA size lithium battery (0.5 gram of lithium), holds memory up to two years p. 14
- Power supplies
- 1771-P3, 1771-P4 or 1771-P5 power supply modules; not 1771-P1 or -P2 p. 16, 17
- I/O current, 1772-LS
- 1.75A with a 1771-P3; 6.75A with a 1771-P4 or 1771-P5 p. 17
- INTFC port
- 15-pin connector; 1772-TC cable to an industrial terminal or PLC-2 report module; 1771-CN, -CO or -CR to Data Highway modules p. 13
- EEPROM module
- 1772-MJ EEPROM memory module, optional, stores 3K words p. 16
- Instruction set
- Mini-PLC-2/15 instruction set, expanded math, selectable timed interrupts, Data Highway compatibility p. 10
- Status indicator
- PROC RUN/FAULT: green in run/program mode; red when the watchdog timer has timed out p. 12
- Paralleling cable
- 1771-CT; with the 1772-LS it joins two power supply modules in the same I/O chassis p. 13
- 1772-LSP power
- 1772-LSP: 120V AC on a terminal strip, 1-amp slow-blow fuse, 2A for I/O modules p. 10, 13
- Transport cable
- 1772-CD mini-transport cable connects the battery pack during a battery change p. 21
- Backplane switches
- Switches 6 to 8 set EEPROM transfer and memory protect; switches 1 to 5 are not used p. 32
What this manual walks you through
- Understanding the processor system and its parts p. 9, 10
- Choosing a power supply module p. 16, 17
- Setting the backplane switch group p. 31, 32
- Using the run/program, remote test and remote program modes p. 15
- Troubleshooting by symptom p. 81, 82
Good to know
- Replace the internal lithium battery every two years. p. 64
- The 1771-P5 power supply is not recommended with the 1772-LSP processor. p. 17
- With memory protect enabled, only the bits and values in the first 128 words of the data table can be changed. p. 32
- Set the backplane switches with a ball-point pen, not a pencil, whose tip can break off and jam the switch. p. 32
- The EEPROM module can be written only with the processor in remote program mode. p. 12
Questions this manual answers
What battery does the Mini-PLC-2/05 1772-LS use?
An AA size lithium battery in a holder at the rear of the processor; it holds memory for up to two years. p. 14
What is the difference between the 1772-LS and the 1772-LSP?
The 1772-LS has no power supply; the 1772-LSP has an integral power supply. p. 9
Which power supplies work with the Mini-PLC-2/05?
The 1771-P3, 1771-P4 and 1771-P5 power supply modules. The 1771-P1 and -P2 cannot be used. p. 16, 17
What does a red PROC RUN/FAULT light mean on a 1772-LS?
There is a processor fault or the watchdog timer timed out; cycle power to reset the processor. p. 82
Which cable connects an industrial terminal to the 1772-LS?
The 1772-TC PLC-2 Program Panel Interconnect Cable, on the 15-pin INTFC connector. p. 13
The whole text · 10 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file