Page 1 of Mini-PLC-2/05 Assembly and Installation Manual

Manual · Allen-Bradley

Mini-PLC-2/05 Assembly and Installation Manual

Manual92 pagesPDF 4.0 MB

Assembly and installation manual for the Allen-Bradley Mini-PLC-2/05 processor, catalog numbers 1772-LS and 1772-LSP (with power supply).

Download the PDF4.0 MB

Covers · 1 model

The models it covers

Summary

What is in it

A procedure-oriented manual that tells an installer how to set up a Mini-PLC-2/05 processor system, part of the PLC-2 family. It covers the 1772-LS processor and the 1772-LSP version with an integral power supply. Inside: an overview of the processor's features, status indicators and optional hardware, installation of the backpanel, switches, field wiring arms and power supplies, installing the EEPROM memory module and battery, system start-up and testing, and troubleshooting.

Its parts

  1. Before You Begin
  2. Mini-PLC-2/05: An Overview
  3. Installing Your Processor System
  4. Installing and Replacing the Mini-PLC-2/05 Processor's Hardware
  5. System Start-Up
  6. Troubleshooting Your Processor System
  7. Glossary

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

Assembly and installation manual for the Allen-Bradley Mini-PLC-2/05 processor, a PLC-2 family processor. It covers two versions: the 1772-LS without a power supply and the 1772-LSP with an integral power supply. It explains the hardware, power supply choices, backplane switch settings, battery replacement and troubleshooting.

Read for this summary: pages 1 to 7, 9 to 21, 31 to 32, 63 to 65 and 81 to 87 of 92.

Device
Mini-PLC-2/05 processor for the PLC-2 family; 1772-LS has no power supply, 1772-LSP has one built in p. 9
Memory
3K CMOS RAM; data table up to 2944 words p. 10
Timers and I/O
488 timers; 128 I/O device capability; full I/O forcing p. 10
Memory backup battery
AA size lithium battery (0.5 gram of lithium), holds memory up to two years p. 14
Power supplies
1771-P3, 1771-P4 or 1771-P5 power supply modules; not 1771-P1 or -P2 p. 16, 17
I/O current, 1772-LS
1.75A with a 1771-P3; 6.75A with a 1771-P4 or 1771-P5 p. 17
INTFC port
15-pin connector; 1772-TC cable to an industrial terminal or PLC-2 report module; 1771-CN, -CO or -CR to Data Highway modules p. 13
EEPROM module
1772-MJ EEPROM memory module, optional, stores 3K words p. 16
Instruction set
Mini-PLC-2/15 instruction set, expanded math, selectable timed interrupts, Data Highway compatibility p. 10
Status indicator
PROC RUN/FAULT: green in run/program mode; red when the watchdog timer has timed out p. 12
Paralleling cable
1771-CT; with the 1772-LS it joins two power supply modules in the same I/O chassis p. 13
1772-LSP power
1772-LSP: 120V AC on a terminal strip, 1-amp slow-blow fuse, 2A for I/O modules p. 10, 13
Transport cable
1772-CD mini-transport cable connects the battery pack during a battery change p. 21
Backplane switches
Switches 6 to 8 set EEPROM transfer and memory protect; switches 1 to 5 are not used p. 32

What this manual walks you through

  • Understanding the processor system and its parts p. 9, 10
  • Choosing a power supply module p. 16, 17
  • Setting the backplane switch group p. 31, 32
  • Using the run/program, remote test and remote program modes p. 15
  • Troubleshooting by symptom p. 81, 82

Good to know

  • Replace the internal lithium battery every two years. p. 64
  • The 1771-P5 power supply is not recommended with the 1772-LSP processor. p. 17
  • With memory protect enabled, only the bits and values in the first 128 words of the data table can be changed. p. 32
  • Set the backplane switches with a ball-point pen, not a pencil, whose tip can break off and jam the switch. p. 32
  • The EEPROM module can be written only with the processor in remote program mode. p. 12

Questions this manual answers

What battery does the Mini-PLC-2/05 1772-LS use?

An AA size lithium battery in a holder at the rear of the processor; it holds memory for up to two years. p. 14

What is the difference between the 1772-LS and the 1772-LSP?

The 1772-LS has no power supply; the 1772-LSP has an integral power supply. p. 9

Which power supplies work with the Mini-PLC-2/05?

The 1771-P3, 1771-P4 and 1771-P5 power supply modules. The 1771-P1 and -P2 cannot be used. p. 16, 17

What does a red PROC RUN/FAULT light mean on a 1772-LS?

There is a processor fault or the watchdog timer timed out; cycle power to reset the processor. p. 82

Which cable connects an industrial terminal to the 1772-LS?

The 1772-TC PLC-2 Program Panel Interconnect Cable, on the 15-pin INTFC connector. p. 13

The whole text · 10 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 7061-70
  8. Pages 71 to 8071-80
  9. Pages 81 to 9081-90
  10. Pages 91 to 9291-92

The file

Revision and size

RevisionPublication 1772-6.6.6, October 1984
PublisherAllen-Bradley
Pages92
PDF4.0 MB
TextThe pages are scans; their text was read by OCR, which may hold reading errors.

The first pages · 3 of 92

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 92
Page 2
Page 2of 92
Page 3
Page 3of 92