The text of a manual · part 7 of 10
Mini-PLC-2/05 Assembly and Installation Manual, pages 61 to 70
Pages 61 to 70 of 92
The original document is the PDF (4.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1772-LS A
Page 61
Chapter
Installing and Replacing the Processor’s Hardware
Chapter Objectives
How to Install Your EEPROM Memory Module
In this chapter you will read how to:
® install the EEPROM memory module ® connect the battery pack
® replace the processor’s battery
Chapter 6 describes troubleshooting your processor system.
To install your EEPROM memory module do the following:
If you have a 1772-LSP processor, start at step 1. If you havea 1772-LS processor, start at step 5.
Step 1 - Move the POWER switch to the off position.
Step 2, Turn off the incoming power source.
Step 3, Disconnect the power cable from the terminal strip. Step 4, Remove the power cable from the processor.
Step 5, Lift the latch of the I/O chassis that holds your processor.
Step 6, Slide the processor out of the I/O chassis.
Step 7, Place the processor on a clean flat surface with the bottom of the module facing you.
Page 62
Page 4-2 Installing and Replacement the Processor’s Hardware
Step 8, Position the EEPROM memory module in the memory module slot with its label facing upward. Insert and press firmly for proper connection (figure 4.1).
12077
Figure 4.1, Inserting the EEPROM Memory Module into the Processor
Step 9, Slide the processor into the I/O chassis. Step 10, Secure the I/O chassis latches. Step 11, Connect the power cable to the terminal strip.
Step 12, Apply power to the processor.
How to Remove the Repeat steps 1 through 7 given in the previous procedure, then EEPROM Memory Module insert a coin into the slot so that it engages the lip on the EEPROM memory module. Carefully rotate the coin upward to start removing the EEPROM memory module from its slot (figure 4.2). Grasp and remove the EEPROM memory module.
Page 63
Page 4-3 Installing and Replacement the Processor’s Hardware
12078
Figure 4,2, Removing the EEPROM Memory Module from the Processor
How to Connect the You should connect our battery pack to maintain memory Battery Pack contents when you install a new battery into the processor. To connect the battery pack do the following (figure 4.3):
1772-LS Processor 1772-LSP Processor
Z or
Tt
Battery Pack
(cat. no. 1771-BB)
\
Mini-processor transport cable (cat. no. 1772-CD)
MUM Pez 20 wea Powe SUPPLY
12079
Figure 4.3, Connect the External Battery Pack when Replacing the Processor’s Battery
Page 64
Page 4-4
Installing and Replacement the Processor’s Hardware
How to Replace the Processor’s Battery
Step 1, Connect one end of the mini-processor transport cable to the INTFC port of the processor.
Step 2, Connect the other end of the cable to the battery pack port.
Step 3, Remove the processor from the I/O chassis and set the processor and the battery pack onto a flat surface.
Now that the processor’s memory contents are maintained, you can replace the battery.
Connect the 1771-BB external battery pack before replacing the battery.
The Mini-PLC-2/05 processor is a solid state device. There is virtually no maintenance required for this processor module. However, we recommend that you replace the internal lithium battery every two years.
To install a new battery do the following:
If you have a 1772-LSP processor, start at step 1. If you havea 1772-LS processor, start at step 5.
Step 1, Move the POWER switch to the off position.
Step 2, Turn off the incoming power source.
Step 3, Disconnect the power cable from the terminal strip. Step 4, Remove the power cable from the processor.
Step 5, Lift the I/O chassis latch that holds your processor. Step 6, Slide the processor out of the I/O chassis.
Step 7, Place your processor on a clean flat surface, such as a table.
Page 65
Page 4-5 Installing and Replacement the Processor’s Hardware
Step 8, Loosen the phillips screw that secures the battery holder.
Loosen this screw
Step 10, Replace the battery in the battery holder. The positive (+) end of the battery should contact the positive (+) end of the battery holder. The negative (-) end of the battery should contact the negative (-) end of the battery holder.
Page 66
Page 4-6
Installing and Replacement the Processor’s Hardware
How to Dispose the Battery
Chapter Summary
Step 11, Replace the battery holder.
Step 12, Secure the screw.
Step 13, Slide your processor into the I/O chassis. Step 14, Snap the I/O chassis latch onto the processor. Step 15, Connect the power cable to the terminal strip.
Step 16, Apply power to the processor.
We recommend the following procedures to ensure proper disposal of the processor’s battery:
¢ Do not incinerate or expose the battery to high temperatures.
¢ Do not attempt to solder the battery or leads. An explosion could result.
© Do not open, puncture, crush, or mutilate the battery. A possibility of an explosion exists and/or toxic, corrosive, and flammable chemicals would be exposed.
¢ Do not charge the battery. An explosion could result or the cell could overheat causing burns.
© Do not short positive or negative terminals together. The battery will heat up.
Now that you read how to install and replace the Mini-PLC-2/05 processor’s hardware, you’re ready to start-up your processor system. We describe start-up in the next chapter.
Page 67
Chapter
System Start-Up
Chapter Objectives
Author’s Conventions
Verify Your System’s Addresses
In this chapter you will read how to: ¢ document your Mini-PLC-2/05 processor system
¢ check the operation of the Mini-PLC-2/05 processor before you supply AC power
® test your output devices
® test your input devices test the operation of your ladder diagram program
Chapter 6 describes troubleshooting.
Conventions used in this chapter are:
Words enclosed in: Indicate:
[] key name, key symbol, or group of key symbols
<> variable information you must provide, such as an instruction address
If you do not understand how to operate the industrial terminal to program your processor, refer to the Mini-PLC-2/05 Processor Programming and Operations Manual (publication 1772-6.8.6).
Verify your I/O devices and field wiring arms wire numbers using the Connection Diagram Addressing Worksheet (publication 5039). These worksheets are available upon request from your local Allen-Bradley distributor or sales engineer. Figure 5.1 shows a modified worksheet form.
Page 68
Figure 5.1, Complete This Worksheet So Troubleshooting Will Be Easy
(AB) ALLEN-BRADLEY Bulletin 1771 1/0 Chassis
SA (Publication 5039, September, 1984)
PROJECT NAME
Cleveland, Ohio 44143 CONNECTION DIAGRAM ADDRESSING WORKSHEET
PAGE
OF
DATE
DESIGNER
00-07 10-17
These labels
2
3
00-07 at identify
; module groups. 10-17
[ 0 1 a] 00-07 10-17 OO-17 10-17
PeRUN
© 'to
\.
These labels are color coded and
P/S FAULT ACTIVE PROE, = |_] =
[ l identify the type of module.
MEMORY STORE ©)
TF eeeccccece \ ro eeccccoes,
Label your I/O devices here.
7) eeeeccece ial)
ajo
Label your z1o lm wire numbers aTo]>-[a}to here,
" z
-lalote fd ry
©
ASGCESHSL
SSOWIIa Soa siciolo op epr]
ISHDESZOIG adoDacsielelo
DBEIGeDGIPe SOGESOSEus
SCO)
‘ z X 2, Ae
~ MiNLPLC-2/05 ‘W/POWER SUPPLY
S
Note: The 1772-LSP processor module is shown. On the worksheet this area is blank and can be substituted with any
Mini-PLC-2 Family processor module.
12080
Page 5-2
System Start-Up
Page 69
Page 5-3 System Start-Up
Status Indicators for I/O Modules
Most I/O modules have status indicators on the front panel. Each indicator corresponds with a terminal on the I/O module’s field wiring arm (figure 5.2). These indicators on output modules light when the appropriate bit in memory is on. Status indicators on input modules light when the appropriate input device is on.
|e ea Status indicator e 4 e @ 4 @ @ e Corresponds to e v
Terminal
=
STslaselaqga
+
12081
Figure 5.2, Each 1/0 Module’s Status Indicator Corresponds to the Field Wiring Arm’s Terminal
Status indicators for the I/O modules help to isolate the source of a fault in your hardware. A hardware fault can originate from:
¢ improper I/O device operation ® wiring error ® loss of power from the I/O devices
The user’s manual or product data for each I/O module explains the operation of the module’s status indicators.
Page 70
Page 5-4 System Start-Up
Module Group and Terminal Numbers
We number module groups in an I/O chassis from left to right. | The first pair of slots is module group 0, the second pair is module group 1, and so on. Module group numbering for the three I/O chassis sizes is (figure 5.3):
1772-LSP Processor an anon < - 22 /0 - >|
64 1/0 eeseeeeece
- ebeese: sesceee see:
ensccecese: L_, _ - __.
CL
|
PST | eS? tee
128 1/0 seseeoseco.
uA
Seentesoeg e@ececeseceee
CL
LL
( fa Tz} iz y
12082
Figure 5.3, I/O Chassis Expansion for Module Group Numbering
Size of 1/O Chassis
Has
And are numbered
32 64 128
2 module groups 4 module groups 8 module groups
Oand1 Othru3 O thru 7
An I/O module group can contain either two single slot I/O modules or one dual-slot I/O module. Each module group generally contains 16 I/O terminal points. This organization parallels the 16 bit structure in the processor’s memory (figure 5.4). Refer to the Mini-PLC-2/05 Controller Programming and Operations Manual (publication 1772-6.8.6) for additional information on processor memory organization.