Page 51 read from a scan by OCR; it may hold reading errors

Page 3-29 Installing Your Processor System

Step 6, Cut the insulation and filler cords.

Insulation / Filler rods Conductor, » | y wires

Drain wire

Step 7, Fold the drain wire back to separate it from the conductor wires.

Conductor_ - ™ *

WIleS er inks

Drain Wir€ ~~-pe ne een

Step 8, Strip about 3/8 inch insulation to expose the end of the wire.

Drain wire, - ___»-.

Exposed wire, - »* ~~

Insulation

Step 9, Loosen a terminal screw and place the wire under the pressure plate of the terminal screw.

Terminal screw

Page 52 read from a scan by OCR; it may hold reading errors

Page 3-30 Installing Your Processor System

Step 10, Repeat steps nine and ten until you wire the appropriate I/O devices to the field wiring arm.

Step 11, Connect the drain wire to ground.

Step 12, Gather all of your wires and neatly bundle them using tie wraps.

Tie wrap

Drain wire, - - »."_

Step 13, Label all of your wires with a 5-digit I/O address code at each wire connection. Chapter 5 describes I/O addressing.

Page 53 read from a scan by OCR; it may hold reading errors

Page 3-31 Installing Your Processor System

Step 14, Make sure that the field wiring arm pivots freely from vertical] to horizontal.

Leave enough slack for pivoting

Step 15, Replace the field wiring arm’s terminal cover.

Page 54 read from a scan by OCR; it may hold reading errors

Page 3-32 Installing Your Processor System

Task 9 Connecting Power to the Processor or Power

Supply

Step 16, Write terminal numbers on the labels next to the terminal’s status indicator and on the terminal cover. These notes aid you during system start-up (chapter 5) and troubleshooting (chapter 6).

Use blank labels to identify your I/O device

Use blank labels i to identify your wire numbers

Henin

Rcreeaiee rT

If your application uses many shielded cables connected to one I/O chassis, then:

® provide a ground bus to connect many wires e solder several drain wires together at a field wiring arm so you route only one drain

You provide the appropriate power cable to connect the 1772-LSP processor or 1771-P3, -P4, -P5 power supplies to their terminal strip. The 1772-LS processor receives its power from the backplane of the I/O chassis.

Page 55 read from a scan by OCR; it may hold reading errors

Page 3-33 Installing Your Processor System

Connecting the Processor

To connect the wires to the 1772-LSP processor’s terminal strip do the following:

Step 1, Strip 3/8 inch insulation from the end of the wire.

Step 2, Loosen each terminal screw and place the appropriate wire under the terminal screw (figure 3.16).

Step 3, Secure each terminal screw.

1.0A 125V SLOW BLOW

C)

12071

Figure 3.16, Connect Your Power Cable to the 1772-LSP Processor’s Terminal Strip

Page 56 read from a scan by OCR; it may hold reading errors

Page 3-34 Installing Your Processor System

Connecting an AC Power To connect the wires to the 1771-P3, -P4 power supplies do the Supply following:

Step 1, Strip 3/8 inch insulation from the end of the wire.

Step 2, Loosen each terminal screw and place the appropriate wire under it (figure 3.17).

Step 3, Secure each terminal screw.

1.5A 125V SLOW BLOW

Power wire connects to L1

Neutral wire connects to N

Ground wire connects to GND

12072

Figure 3.17, Connect Your Power Cable to the AC Power Supply’s Terminal Strip

Page 57 read from a scan by OCR; it may hold reading errors

Page 3-35 Installing Your Processor System

Connecting a DC Power Supply

To connect the wires to the 1771-P5 power supply’s terminal strip do the following:

Step 1, Strip 3/8 inch insulation from the end of the wire.

Step 2, Loosen each terminal screw and place the appropriate wire under it (figure 3.18).

Step 3, Secure each terminal screw.

5A 32V NORM BLOW |

Sel

Power wire connects to +DC

Neutral wire connects COM

Ground wire connects to GND

12073

Figure 3.18, Connect Your Power Cable to the DC Power Supply’s Terminal Strip

Page 58 read from a scan by OCR; it may hold reading errors

Page 3-36 Installing Your Processor System

Connecting More Than One Power Supply

When you use two power supplies (figure 3.19) connect the: ® paralleling cable between each power supply

® incoming power source to the terminal strip of the power supply

To easily remove your I/O modules that are between the two power supplies, place the paralleling cable across the top of the I/O chassis (figure 3.19).

Power Supply Paralleling Cable (Cat. No. 1771-CT)

©

PS Acie ACTIVE eth

PS PRRALLEL PARALLEL a8)

120 VAC Powet POWER ON OW

OFF OFF 1A 125V 1A 125¥ SLOW BLOW SLOW BLOW tl LoL} ' i A Line 120V 1 Mi Neutral f AC oc I . i Equipment Grounding [¢] @ | Conductor Ground Bus

Note: When wiring a 1771-P3 module, connect GND to the ground stud. No 14 AWG is recommended,

12075

Figure 3.19, Connecting More than One Power Supply

Page 59 read from a scan by OCR; it may hold reading errors

Page 3-37 Installing Your Processor System

Task 10 To connect your industrial terminal to the processor do the Connecting the Industrial following (figure 3.20): Terminal

Industrial Terminal

(Backview) 1/0 Chassis {, Pa Tv = (O ©) 9] od Fh Hoe nn L_ | 1a] Ea EL ET EL aL EL GLE oe rz C JC | S1|| WO _ Zo) ae: Channel A

\

Interconnect Cable cat. no. 1772-TC (10 feet, 3.05m)

12076

Figure 3.20, Connecting the Industrial Terminal

Step 1, Plug the AC power cord into the industrial terminal.

Step 2, Plug the AC power cord from the industrial terminal into the incoming AC power source.

Step 3, Connect one end of the PLC-2 program panel interconnect cable to CHANNEL A at the back of the industrial terminal.

Step 4, Connect the other end of the cable to the socket labeled INTFC at the front of the processor.

Step 5, Place the PLC-2 family keytop overlay onto the keyboard.

Step 6, Turn the power switch on the front of the industrial terminal to the ON position.

Step 7, Press the keys 1 1 on the industrial terminal keyboard.

Step 8, Select your processor’s mode of operation.

Page 60 read from a scan by OCR; it may hold reading errors

Page 3-38 Installing Your Processor System

If you want this Then press mode of operation: | these keys: Run/Program SEARCH 590 Remote Test SEARCH 591

Remote Program SEARCH 592

Chapter Summary In this chapter we described the various tasks you must perform when you install your Mini-PLC-2/05 processor system. In the next chapter, we describe how to install, connect, and replace the EEPROM memory module, battery pack, and battery.