Page 3-19

Installing Your Processor System

Table 3.D

Location of the Power Supply in Each I/O Chassis

Then Slide the Power

If You Have: And: And: Supply in 1/0 Chassis in: 1772-L8 One power 1771-A1 Any slot processor supply /O chassis 1772-LS One power 1771-A2 Module Group 0 processor supply 1/0 chassis 1772-LS One power 1771-A4 Module Group 0 processor supply 1/0 chassis 1772-LS Two power 1771-A1 Any slot processor supplies 1/0 chassis 1772-LS Two power 1771-A2 Module groups 0 and 2 processor supplies 1/0 chassis 1772-LS Two power 1771-A4 Module groups 0 and 5 processor supplies 1/0 chassis 1772-LSP One power 1771-A1 Any slot processor supply 1/0 chassis 1772-LSP One power 1771-A2 Module group 2 processor supply 1/0 chassis 1772-LSP One power 1771-A4 Module group 4 processor supply 1/0 chassis

Page 42 read from a scan by OCR; it may hold reading errors

Page 3-20 Installing Your Processor System

Task 7 Mounting the Backpanel

Figure 3.13 shows:

¢ stud mounting of a backpanel to the back wall of an enclosure

© bolt mounting of an I/O chassis or ground bus to the backpanel

© stud mounting of an I/O chassis or ground bus to the backpanel ra

Stud mounting of the back panel to < the back wall of the enclosure

Bolt mounting of a

Stud mounting of ground bus to the chassis or back panel ground bus ora q chassis to the back panel ‘ ‘ ; g / Ground H Bus or 4 Star Ground Mounting H Washer Lug Bracket j Welded i cae

Backpanel

Use a wire brush to remove paint from threads to allow a ground connection

WRRRAANY vi Se WANN et

Scrape paint and use a star washer

Flat Washer

AWE _-- AVANAWARAANUER REL EARERR REA

Stud

ARRAY >

FAVARREREES

Flat Washer

Scrape Paint

PR URURUREBEL LLRRERLLELEEn ee mEateseneuueuauen:

Back Wall

Sct

Welded Stud mut ig a Q Cc n o. + a star washer

< - Wen eu

WEB Lwaaae of Enclosure

12068

Figure 3.13, Hardware Needed for Mounting the Backpanel Inside Your Enclosure

Page 43 read from a scan by OCR; it may hold reading errors

Page 3-21 Installing Your Processor System

Remember these guidelines when mounting the I/O chassis on the backpanel:

e If the mounting brackets of an I/O chassis do not lie flat before the nuts are tightened, use additional washers as shims so that the chassis will not be warped by tightening the nuts.

e Warping an I/O chassis could damage the backplane and cause poor connections.

@ Make good electrical connections between each I/O chassis, the back panel, and the enclosure.

@ Remove paint or other nonconductive finish from studs and the back panel so that good electrical contact is made at each bolt or stud.

Use either copper braid or copper wire to connect between: ® each chassis e backpanel

® enclosure

® ground bus that connects to earth ground (the grounding electrode system) through a grounding electrode conductor.

We define earth ground as the central ground for all electrical equipment and AC power within any facility.

All ground connections must be permanent and continuous to provide a low-impedence path to earth ground for induced noise currents and fault currents. Remember, observe all applicable codes and ordinances when making these grounding connections. Figure 3.14 shows a ground bus connection through one mounting bracket of an I/O chassis.Here are some general guidelines when connecting a ground bus:

® connect the chassis in vertical groups

® connect each vertical group to a ground bus mounted on the back panel of the enclosure

¢ connect the ground bus to the grounding electrode system through a grounding electrode conductor

Page 44 read from a scan by OCR; it may hold reading errors

Page 3-22 Installing Your Processor System

Task 8 Wiring Field Wiring Arms

How to Wire Your I/O Devices to a Field Wiring Arm

Ground Bus

Ground Bus Mounting one

O9°°9 Ts.

Ground Lug

Grounding electrode conductor to earth ground

Equipment Grounding Conductors

12070

Figure 3.14, Connecting a Ground Bus Through One Mounting Bracket of an I/O Chassis

CAUTION: Avoid connecting more than two lugs to any single bolt. The connection can become loose due to the compression of the metal lugs.

Your I/O devices connect to the I/O module’s field wiring arm. Every I/O module must be properly wired and every I/O connection must be made at the proper field wirlng arm terminal. Refer to the specific I/O module publication for connection diagrams.

There are three ways to wire your I/O devices, using: ® single-conductor wire

® multi-conductor cable

¢ multi-conductor shielded cable

Single-conductor wire and multi-conductor cable are similar to each other. The difference is that single-conductor wire has one wire strand and multi-conductor cable has many single-conductor wires enclosed in a casing or outer jacket. We recommend using copper wire for these connections.

Page 45 read from a scan by OCR; it may hold reading errors

Page 3-23 Installing Your Processor System

Multi-conductor shielded cable can be Belden type 8761 or its equivalent. It consists of twisted pairs of conductor wires wrapped in two layers of shielding. Our wiring procedure shows one pair of conductor wires. The number of needed I/O terminals determines the number of conductor wires needed within the cable for your application. Figure 3.15 shows each component making up this cable. The components are:

outer jacket e braided shield e drain e foil shield

® insulation e filler cord(s)

e blue conductor wire

® white conductor wire

Braided Shield | Cord

Foil Shield Insulation wee Conductor Wire

=

Insulation

Blue Conductor Wire

Outer Jacket Drain Wire Filler Cord

Figure 3.15, Components Making up a Multi-Conductor Shielded Cable

Intelligent and low voltage DC (discrete) I/O modules require multi-conductor shielded cable.Analog and the remaining discrete I/O modules require either the single or multi-conductor wire.

Page 46 read from a scan by OCR; it may hold reading errors

Page 3-24 Installing Your Processor System

Single-conductor Wire or Multi-conductor Cable

To wire your I/O devices:

Step 1, Pry the field wiring arm’s terminal cover off using a flat-head screwdriver.

Step 2, Measure the wire distance from your I/O devices to the field wiring arm terminals. This distance determines the amount of wire you need for your application.

Step 3, For multi-conductor cable, strip some casing (to expose the individual wires) from the end of the cable that connects to the field wiring arm.

Strip some casing to expose the wires

Step 4, Strip about 3/8 inch insulation to expose the end of the wire.

Strip about 3/8 inch insulation to expose the wire

Page 47 read from a scan by OCR; it may hold reading errors

Page 3-25 Installing Your Processor System

Step 5, Loosen a terminal screw and place the wire under the pressure plate of the terminal.

Terminal screw

Step 6, Secure the terminal screw.

Step 7, Repeat steps five and six until you wire the appropriate I/O devices to the field wiring arm.

Page 48 read from a scan by OCR; it may hold reading errors

Page 3-26 Installing Your Processor System

Step 8, Connect the drain wire to ground.

Drain wire

Step 9, Gather all wires and neatly bundle them using tie wraps.

Tie wrap__» &

Step 10, Label all wires with a 5-digit I/O address code at each wire connection. Chapter 5 describes I/O addressing.

Step 11, Make sure that the field wiring arm pivots freely from vertical to horizontal.

Leave enough slack for pivoting

Page 49 read from a scan by OCR; it may hold reading errors

Page 3-27 Installing Your Processor System

Step 12, Replace the field wiring arm’s terminal cover.

Step 13, Write terminal numbers on the labels next to the terminal’s status indicator and on the terminal cover. These notes aid you during system start-up (chapter 5) and troubleshooting (chapter 6).

Use blank labels to identify your I/O device lal BERRBRAEH

Use blank labels to identify your wire numbers eee ee

-#.

ww ghe E

‘aia

Page 50 read from a scan by OCR; it may hold reading errors

Page 3-28 Installing Your Processor System

Multi-conductor Shielded Cable

To wire your I/O devices:

Step 1, Pry the field wiring arm’s terminal cover off using a flat-head screwdriver.

Step 2, Measure the wire distance from your I/O devices to the field wiring arm terminals. This distance determines the amount of wire you need for your application.

Step 3, Strip some insulation from the end of the cable that connects to the field wiring arm.

Insulation

Step 4, Cut the braided shield.

Braided shield

Step 5, Remove the foil shield.

Foil shield