The text of a manual · part 5 of 10
Mini-PLC-2/05 Assembly and Installation Manual, pages 41 to 50
Pages 41 to 50 of 92
The original document is the PDF (4.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1772-LS A
Page 41
Page 3-19
Installing Your Processor System
Table 3.D
Location of the Power Supply in Each I/O Chassis
Then Slide the Power
If You Have: And: And: Supply in 1/0 Chassis in: 1772-L8 One power 1771-A1 Any slot processor supply /O chassis 1772-LS One power 1771-A2 Module Group 0 processor supply 1/0 chassis 1772-LS One power 1771-A4 Module Group 0 processor supply 1/0 chassis 1772-LS Two power 1771-A1 Any slot processor supplies 1/0 chassis 1772-LS Two power 1771-A2 Module groups 0 and 2 processor supplies 1/0 chassis 1772-LS Two power 1771-A4 Module groups 0 and 5 processor supplies 1/0 chassis 1772-LSP One power 1771-A1 Any slot processor supply 1/0 chassis 1772-LSP One power 1771-A2 Module group 2 processor supply 1/0 chassis 1772-LSP One power 1771-A4 Module group 4 processor supply 1/0 chassis
Page 42
Page 3-20 Installing Your Processor System
Task 7 Mounting the Backpanel
Figure 3.13 shows:
¢ stud mounting of a backpanel to the back wall of an enclosure
© bolt mounting of an I/O chassis or ground bus to the backpanel
© stud mounting of an I/O chassis or ground bus to the backpanel ra
Stud mounting of the back panel to < the back wall of the enclosure
Bolt mounting of a
Stud mounting of ground bus to the chassis or back panel ground bus ora q chassis to the back panel ‘ ‘ ; g / Ground H Bus or 4 Star Ground Mounting H Washer Lug Bracket j Welded i cae
Backpanel
Use a wire brush to remove paint from threads to allow a ground connection
WRRRAANY vi Se WANN et
Scrape paint and use a star washer
Flat Washer
AWE _-- AVANAWARAANUER REL EARERR REA
Stud
ARRAY >
FAVARREREES
Flat Washer
Scrape Paint
PR URURUREBEL LLRRERLLELEEn ee mEateseneuueuauen:
Back Wall
Sct
Welded Stud mut ig a Q Cc n o. + a star washer
< - Wen eu
WEB Lwaaae of Enclosure
12068
Figure 3.13, Hardware Needed for Mounting the Backpanel Inside Your Enclosure
Page 43
Page 3-21 Installing Your Processor System
Remember these guidelines when mounting the I/O chassis on the backpanel:
e If the mounting brackets of an I/O chassis do not lie flat before the nuts are tightened, use additional washers as shims so that the chassis will not be warped by tightening the nuts.
e Warping an I/O chassis could damage the backplane and cause poor connections.
@ Make good electrical connections between each I/O chassis, the back panel, and the enclosure.
@ Remove paint or other nonconductive finish from studs and the back panel so that good electrical contact is made at each bolt or stud.
Use either copper braid or copper wire to connect between: ® each chassis e backpanel
® enclosure
® ground bus that connects to earth ground (the grounding electrode system) through a grounding electrode conductor.
We define earth ground as the central ground for all electrical equipment and AC power within any facility.
All ground connections must be permanent and continuous to provide a low-impedence path to earth ground for induced noise currents and fault currents. Remember, observe all applicable codes and ordinances when making these grounding connections. Figure 3.14 shows a ground bus connection through one mounting bracket of an I/O chassis.Here are some general guidelines when connecting a ground bus:
® connect the chassis in vertical groups
® connect each vertical group to a ground bus mounted on the back panel of the enclosure
¢ connect the ground bus to the grounding electrode system through a grounding electrode conductor
Page 44
Page 3-22 Installing Your Processor System
Task 8 Wiring Field Wiring Arms
How to Wire Your I/O Devices to a Field Wiring Arm
Ground Bus
Ground Bus Mounting one
O9°°9 Ts.
Ground Lug
Grounding electrode conductor to earth ground
Equipment Grounding Conductors
12070
Figure 3.14, Connecting a Ground Bus Through One Mounting Bracket of an I/O Chassis
CAUTION: Avoid connecting more than two lugs to any single bolt. The connection can become loose due to the compression of the metal lugs.
Your I/O devices connect to the I/O module’s field wiring arm. Every I/O module must be properly wired and every I/O connection must be made at the proper field wirlng arm terminal. Refer to the specific I/O module publication for connection diagrams.
There are three ways to wire your I/O devices, using: ® single-conductor wire
® multi-conductor cable
¢ multi-conductor shielded cable
Single-conductor wire and multi-conductor cable are similar to each other. The difference is that single-conductor wire has one wire strand and multi-conductor cable has many single-conductor wires enclosed in a casing or outer jacket. We recommend using copper wire for these connections.
Page 45
Page 3-23 Installing Your Processor System
Multi-conductor shielded cable can be Belden type 8761 or its equivalent. It consists of twisted pairs of conductor wires wrapped in two layers of shielding. Our wiring procedure shows one pair of conductor wires. The number of needed I/O terminals determines the number of conductor wires needed within the cable for your application. Figure 3.15 shows each component making up this cable. The components are:
outer jacket e braided shield e drain e foil shield
® insulation e filler cord(s)
e blue conductor wire
® white conductor wire
Braided Shield | Cord
Foil Shield Insulation wee Conductor Wire
=
Insulation
Blue Conductor Wire
Outer Jacket Drain Wire Filler Cord
Figure 3.15, Components Making up a Multi-Conductor Shielded Cable
Intelligent and low voltage DC (discrete) I/O modules require multi-conductor shielded cable.Analog and the remaining discrete I/O modules require either the single or multi-conductor wire.
Page 46
Page 3-24 Installing Your Processor System
Single-conductor Wire or Multi-conductor Cable
To wire your I/O devices:
Step 1, Pry the field wiring arm’s terminal cover off using a flat-head screwdriver.
Step 2, Measure the wire distance from your I/O devices to the field wiring arm terminals. This distance determines the amount of wire you need for your application.
Step 3, For multi-conductor cable, strip some casing (to expose the individual wires) from the end of the cable that connects to the field wiring arm.
Strip some casing to expose the wires
Step 4, Strip about 3/8 inch insulation to expose the end of the wire.
Strip about 3/8 inch insulation to expose the wire
Page 47
Page 3-25 Installing Your Processor System
Step 5, Loosen a terminal screw and place the wire under the pressure plate of the terminal.
Terminal screw
Step 6, Secure the terminal screw.
Step 7, Repeat steps five and six until you wire the appropriate I/O devices to the field wiring arm.
Page 48
Page 3-26 Installing Your Processor System
Step 8, Connect the drain wire to ground.
Drain wire
Step 9, Gather all wires and neatly bundle them using tie wraps.
Tie wrap__» &
Step 10, Label all wires with a 5-digit I/O address code at each wire connection. Chapter 5 describes I/O addressing.
Step 11, Make sure that the field wiring arm pivots freely from vertical to horizontal.
Leave enough slack for pivoting
Page 49
Page 3-27 Installing Your Processor System
Step 12, Replace the field wiring arm’s terminal cover.
Step 13, Write terminal numbers on the labels next to the terminal’s status indicator and on the terminal cover. These notes aid you during system start-up (chapter 5) and troubleshooting (chapter 6).
Use blank labels to identify your I/O device lal BERRBRAEH
Use blank labels to identify your wire numbers eee ee
-#.
ww ghe E
‘aia
Page 50
Page 3-28 Installing Your Processor System
Multi-conductor Shielded Cable
To wire your I/O devices:
Step 1, Pry the field wiring arm’s terminal cover off using a flat-head screwdriver.
Step 2, Measure the wire distance from your I/O devices to the field wiring arm terminals. This distance determines the amount of wire you need for your application.
Step 3, Strip some insulation from the end of the cable that connects to the field wiring arm.
Insulation
Step 4, Cut the braided shield.
Braided shield
Step 5, Remove the foil shield.
Foil shield