Page 71
Page 5-5 System Start-Up
128 1/0, v \ 64 1/0 ran / \ 32 1/0
Module Groups 0 thru 7 WAN
1/O module terminal points in a module group.
TTT oN, {=}, 7 > _ _ ~“ --+-- - -
2 ‘ - | | re 00}|: ; S a 02): t 3] gil gi] 3 3) 2) 3) gi Sg We ei] EE 04 ||: ‘ ‘ce C Ca eur Ey, ale : a | ell] Za] FE reat] gt] || Gea] | eg) C2ai| | Fal] Fe 06 6 6 Mi [e es M les i f 0 : eH | rd) | ed) tet | RAT) ES) FS) Bt) RS JI Pik > TF eH It . 7 7 T a he) 128 1/0 RACK Left Right Slot Slot Data Table Bits = Program Address 16!15/14]13]121]11] 10] 07] 06] 05] 04/03] 02] 01] 00 010/12
12083
Figure 5.4, Module Group and Terminal Numbers’ Relationship to Your Program Address
The arrangement of I/O modules within a module group does not imply that both modules be the same the type, have the same voltage range, or AC or DC voltage. Module group designation is for the purpose of addressing inputs and/or outputs in your application program. However, for ease of addressing, we recommend that similar I/O modules be grouped together.
Page 72
Page 5-6
System Start-Up
Addressing Your
You must properly address your hardware so that it relates to
Hardware = your ladder diagram program. In the ladder diagram program, the input or output instruction address is associated with a particular I/O terminal and identified by a 5-digit address (figure 5.5). Concept Example
Hardware Terminology
Rack No. (1-7}
Module Group No.
Input (1) or Output (0)
Hardware Terminology
Output 0
Rack No.: 1
Module Group No.: 0
(0-7) Terminal No. F ; Limon 10-17) Terminal No.: 12 y u Y Instruction XXX/XX 010/12] Address Word Bit Data Table Word Bit Address Address | Terminology Address Address Program Rung Concept XXX XXX wet lw er rn ce eee en ee nr ee ee ee ee ( )---- XX xx Example 112 010 woe | bee meen ee ee C Jow- it 12
12084
Figure 5.5, Hardware Terminology Translated Into a Program Rung
Page 73
Page 5-7 System Start-Up
Before You Supply AC Power
Testing Output Devices
Reading from left to right the:
e first number denotes the type of module: ® 0 output ® 1 input
® second number denotes the I/O chassis number and is always a one.
e third number denotes a module group (0 thru 7)
e fourth and fifth numbers denote a terminal point designation: e 00 thru 07 left slot of the module group e 10 thru 17 right slot of the module group
WARNING: Machine motion during system start-up can be hazardous to personnel. Disconnect any device that might cause machine motion to occur when it is energized.
Before you supply AC power to your processor do the following:
Step 1, Measure the AC line voltage and make sure it corresponds to the system power supply.
Step 2, Check wiring of:
® main disconnect switch or circuit breaker ¢ master control relay
® emergency stop switches
Step 3, Check the power cable connections. Make sure plugs are securely held on their sockets.
Step 4, Check the location and chassis positioning of each I/O module. All I/O chassis latches must be snapped down. All field wiring arms must be connected with their corresponding I/O modules.
Step 5, Disconnect all motors to ensure that no power-driven machine can start when you first apply power to the processor; or disconnect the output device at its terminal strip.
There are two ways to test output devices, using: ® a pushbutton (you supply the pushbutton) e force functions (through the industrial terminal)
If you are unfamiliar with the industrial terminal, refer to the Mini-PLC-2/05 Processor Programming and Operations Manual (publication 1772-6.8.6).
Page 74
Page 5-8 System Start-Up
Using Pushbuttons
CAUTION: Use only trained personnel to conduct this test. Have a trained person at appropriate emergency stop switches to de-energize output devices that could cause hazardous operation.
To test your output devices while using a pushbutton do the following:
Step 1, Connect a normally-open/momentary-close pushbutton as an input device to an input module.
Step 2, Connect the industrial terminal to your processor. Refer to chapter 3 for the procedure.
Step 3, Press [SEARCH] 591 to select the test mode of operation.
Step 4, Use an examine-on address corresponding to the address of the pushbutton. Use an energize address corresponding to the output device being tested. For example, enter a rung similar to this one:
a oa i ted Dawn nn en ne ne ee ee ee ( )--4 | 14 og |
CAUTION: Test only one rung at a time. Do not program multiple rungs, unpredictable machine operation can occur.
Step 5, Close the pushbutton and observe the following: * output address instruction is intensified
* output module’s status indicator lights
Address of Address of the pushbutton your output device f lit 014 !
te Damm rr er ee ee ee { y--+
Page 75
Page 5-9 System Start-Up
Using Force Functions
What Does the Force Functions Determine?
Step 6, If the indicator does not light or the instruction does not intensify, then check the:
® processor
® output module
If there are no failures, then: ® repeat the test procedure e call your Allen-Bradley sales engineer or distributor
Force functions are troubleshooting aids available when you use the industrial terminal.
There are two types of force functions: e force on e force off
You can use the force functions to selectively force an input bit or output terminal on or off. The processor must be operating in the remote test or run/program mode.
The on or off status of a forced bit appears beneath the bit instruction in the rung.
In all processor modes, a “FORCED I/O” message is displayed near the bottom of the screen when bits are forced on or off. In every mode except the program mode, the forced status “ON” or “OFF” is displayed below each forced instruction.
The force functions determine the on/off status of input bits and output terminals by overriding the I/O scan. You can force an input bit on or off regardless of the actual state of the corresponding input device. However, forcing an output terminal causes the corresponding output device to be on or off regardless of the rung logic or the status of the output image table bit.
When in remote test mode, the processor holds outputs in their last state regardless of attempts to force them on, even though the instruction address of the output bit is intensified on the CRT screen.
Page 76
Page 5-10 System Start-Up
How to Use Force Functions
How to Remove Force Functions
How to Clear Force Functions
You can use force functions in either of two ways using: e bit manipulation/monitor display of an I/O word ¢ ladder diagram display of user program
By pressing [SEARCH] 53 <key sequence of address>, on the industrial terminal, you can display the bit status and force status of the 16 corresponding input bits or output terminals of the desired word. Use the -e] and [-«] key to cursor to the desired bit. Or, in the ladder diagram display, forcing can be applied by placing the cursor on an examine or energize instruction. In either case, after positioning the cursor, you can use any one of the following key sequences for inserting or removing a forced condition:
[FORCE ON][INSERT] [FORCE OFF][INSERT] [FORCE ON][REMOVE] [FORCE OFF]JIREMOVE]
You can remove all force on or force off functions at once ladder by pressing either of the following key sequences:
[FORCE ON][CLEAR MEMORY] [FORCE OFF][CLEAR MEMORY]
All force functions are cleared from the industrial terminal when:
® you disconnect the power cable or communications cable of the industrial terminal or processor
® you turn off the industrial terminal
© there is a power failure that shuts down the power supply that powers the processor.
® you press [MODE SELECT]
WARNING: Keep personnel away from the machine area when an energized output is being forced off. Accidental removal of force functions will instantly turn on the output device. Injury to personnel near the machine could result.
Page 77
Page 5-11 System Start-Up
How to Display all Bit Addresses
How to Test with Force Functions
The industrial terminal displays a complete list of bit addresses that are forced on or off when you press:
[SEARCH][FORCE ON] [SEARCH][FORCE OFF]
If all the bits forced on or off cannot be displayed at one time, use the [SHIFT ][4] and [SHIFT] ¥] keys to display additional forced bits.
Press [CANCEL COMMAND] to terminate the display.
CAUTION: Use only trained personnel to conduct this test. Have a trained person at appropriate emergency stop switches to de-energize output devices that could cause hazardous operation.
To test your output devices using force functions do the following:
Step 1 ~ - Connect the industrial terminal to your processor. Refer to chapter 3 for the procedure.
Step 2, Load your program into the industrial terminal.
Step 3, Press [SEARCH] 591 to select the test mode of operation.
Step 4, Position the cursor on the first output instruction. Step 5, Press [SELECT] [FORCE ON] [INSERT].
Step 6, Make sure that the output module’s status indicator lights. If the indicator does not light then check the:
® power source for the output device
@ fuse on the output module
If there are no failures, then:
® repeat the test procedure
® call your Allen-Bradley sales engineer or distributor
Step 7, Repeat steps five and six until you test all output devices.
During the next procedure, you will test input devices.
Page 78
Page 5-12 System Start-Up
Testing Input Devices gine CAUTION: Use only trained personnel to conduct this test.
Have a trained person at appropriate emergency stop switches to de-energize output devices that could cause hazardous operation.
To test your input devices ,using force functions, do the following:
WARNING: Do not reach into a machine to actuate a switch since unexpected machine motion can occur. Use a wooden stock or other non-conductive device to guard against electrical shock.
Step 1, Manually turn on one input device.
Step 2, Make sure that the input module’s status indicator lights. If the indicator does not light, check:
® power source for the input device
® wiring from the input device
® connection to the field wiring arm’s terminal ® input device e verify the address of the input device
® input terminal e address of input device
Step 3, Connect the industrial terminal to your processor (refer to chapter 3).
Step 4, Press [SEARCH] 591 to select the test mode of operation.
Step 5, Use an examine-on address corresponding to your input device address. Use an address that is an internal storage bit. For example, enter a rung similar to this one:
! 144 Gi4 3
Fe Powe ee en ne ee ef ed i
! i4 oa 1
Page 79
Page 5-13 System Start-Up
Testing Your Program
Step 6, Manually turn on one input device and observe: ® input instruction is intensified
® input module’s status indicator lights
Address of your Address of your input devices output device ! 411 o14 i te Dam rr et re eee ( }--4 i 14 00!
Input address intensifies
Step 7, If the instruction does not intensify, then: ® repeat the test procedure ¢ check your input module
¢ call your Allen-Bradley sales engineer or distributor
This is the last phase of testing needed to help ensure proper start-up.
CAUTION: Use only trained personnel to conduct this test. Have a trained person at appropriate emergency stop switches to de-energize output devices that could cause hazardous operation.
To test your program do the following:
Step 1, Connect the industrial terminal to your processor (refer to chapter 3).
Step 2, Press [SEARCH] 590 to select the run/program mode of operation.
Step 3, Enter your program.
Step 4, Press [SEARCH] 591 to select the remote test mode of operation.
Step 5, Examine your entered program - making sure that no output device energizes unconditionally.
Step 6, Restore the connection from an output module to a single device which causes machine motion.
Page 80
Page 5-14 System Start-Up
Chapter Summary
Step 7, Check the behavior of the connected output device. To do this, simulate the input conditions necessary to energize the output in the program while the processor is in the run/program mode of operation.
Step 8, Disconnect the output device.
Step 9, Restore the connection from an output module to the next single output device to be tested.
Step 10, Repeat steps seven through nine until you test all outputs.
Step 11, Restore the connection from output modules to all devices causing machine motion. Restore power to any machine that you disconnected for start-up.
Step 12, Perform a first run of your processor program with all output devices enabled.
In this chapter we described how to test input devices, output devices, and your program. If you follow our procedures, you will be able to have a successful processor system start-up. Should problems develop, you'll have to troubleshoot your Mini-PLC-2/05 system. This is covered in the next chapter.