The text of a manual · part 9 of 10
Mini-PLC-2/05 Assembly and Installation Manual, pages 81 to 90
Pages 81 to 90 of 92
The original document is the PDF (4.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1772-LS A
Page 81
“
Chapter
Troubleshooting Your Processor System
Chapter Objectives
How to Troubleshoot Your System
Troubleshooting Aids
In this chapter you will read: e how to troubleshoot your system
® troubleshooting aids for each Mini-PLC 2/05 processor
To make your job troubleshooting the Mini-PLC-2/05 easier, be sure you:
® have followed instructions on mounting (chapter 3), wiring (chapter 3), and addressing (chapter 5)
® can interpret the meanings of status indicators (chapter 2 or individual I/O module’s product data publications)
Table 6.A lists symptoms, possible causes, and recommended action to correct.
Page 82
Page 6-2
Troubleshooting Your Processor System
Table 6.A Troubleshooting Guide
Symptom
Possible Cause
Recommended Action
Processor’s memory contents will transfer to the EEPROM memory module.
Backplane switch assembly is not set correctly.
Set backplane switch assembly. Refer to chapter 3.
Loss of processor's memory contents after a power failure.
Processor’s battery is dead.
Replace processor's battery. Refer to chapter 4.
PROG RUN/FAULT indicator turns red,
There is a processor fault or the watchdog timer timed out.
® Cycle power to reset the processor. * Cycle power to reset the processor.
® Ifthe industrial terminal shows a run time error, correct the run time error. Refer to the Mini-PLC-2/05 Processor Programming and Operations Manual.
P/S ACTIVE indicator is off.
You did not connect an external power source.
POWER switch is defective.
The 1772-LSP processor's terminal strip is not wired properly.
Power supply defective.
Fuse blown
AC or DC power is not available.
One or both power supplies are off.
1/O modules current requirements is too large for power supply.
Incoming AC power is not within specification.
Power supply defective.
Connect an external power source.
Cail your Allen-Bradley sales engineer or distributor.
Wire the terminal strip properly. Refer to chapter 3.
Call your Allen-Bradley sales-engineer or distributor.
Replace the fuse.
Provide AC or DC power.
Turn both POWER switches off at the same time, wait 15 seconds, then, turn both switches on at the same time.
Measure the backplane current (1771-A1, -A2,, -A4); maximum current rating is 6.5 amps. Remove I/O modules until rating is within specification.
Measure line voltage; its specification is: 97 to 132V AC.
Call your Allen-Bradley sales engineer or distributor.
Output device did not turn on or off.
Improper wiring of field wiring arms and/or output devices.
Program error
Wire field wiring arms or output device properly. Refer to chapter 3.
Verify all program rungs.
Verify all instructions for their proper use.
Chapter Summary
If you have followed the installation and assembly procedures in earlier chapters, you'll have minimized the need to troubleshoot your Mini-PLC-2/05 system. However, should troubleshooting become necessary, the material in this chapter can help you diagnose and correct the fault.
Page 83
Appendix
Glossary
This glossary defines terms pertaining to Allen-Bradley Mini- PLC-2/05 processors. For a broader glossary of programmable controller (PC) words, contact Allen-Bradley sales engineer or distributor for publication SD60.
AC Input Module: An I/O module that converts various AC signals originating at user devices to the appropriate logic level signal for use within the processor.
AC Output Module: An I/O module that converts the logic level signal of the processor to a usable output signal to control a user AC device.
Accumulated Value: The number of elapsed timed intervals or counted events.
Active: A diagnostic indicator on Allen-Bradiey PC hardware that, when lit, signifies an operational condition.
Analog Input Module: A module that converts an analog input signal to a number that can be manipulated by the processor.
Analog Output Module: A module that outputs a signal proportional to a number transferred to the module from the processor.
Application: 1) A machine or process monitored and controlled by a PC. 2) The use of computer- or processor-based routines for specific purposes.
Arithmetic Capability: The ability to do addition, subtraction, multiplication, division, and other advanced math functions with the PC processor.
AWG: See American Wire Gauge.
Backplane: A printed circuit board, located in the back of a chassis, that contains a data bus, power bus, or mating connectors for modules to be inserted in the chassis.
Battery Backup: A battery or set of batteries that will provide power to processor memory only in case of a system power outage.
BCD: See Binary Coded Decimal.
Page 84
Page A-2 Glossary
Binary Coded Decimal (BCD): A numbering system used to express individual decimal digits (0 through 9) in four-bit binary notation.
Binary Word: A related group of ones and zeros that has meaning assigned by position, or by numerical value in the binary system of numbers.
Bit: Binary digit. The smallest unit of information in the binary numbering system. Represented by the digits 0 and 1. The smallest division of a PC word.
Byte: Equals eight consecutive bits.
Chassis: A hardware assembly used to house PC devices such as I/O modules, adapter modules, processor modules, power supplies, and processors.
CMOS: Complementary Metal Oxide Semiconductor circuitry. See MOS.
Data Highway: A baseband, half-duplex communications link that provides data communications between multiple stations such as PCs, computers, and data terminals. Data Highway is a registered trademark of the Allen-Bradley Company.
Decimal: Pertains to the base-10 numbering system.
EEPROM: Electrically Erasable PROM. A type of PROM that is programmed and erased by electrical pulses.
Environment: In a systems context, the environment is anything that is not a part of the system itself. Knowledge about the environment is important because of the affect it can have on the system or because of possible interactions between the system and the environment.
Force Off Function: A feature which allows the user to reset an input image table bit or de-energize an output, independent of the PC program.
Force On Function: A feature which allows the user to set an image table bit or energize an output, independent of the PC program,
Hard Contacts: Any type of physical switch contacts.
Hard Copy: Any form of a printed document such as a ladder diagram program listing, paper tape, or punched cards.
Hardware: The mechanical, electrical, and electronic devices that make up a programmable controller and its application.
Page 85
Page A-3 Glossary
Input Devices: Devices such as limit switches, pressure switches, push buttons, analog and/or digital devices, that supply data to a programmable controller.
Intelligent I/O Module: Microprocessor-based modules that perform processing or sophisticated closed-loop, application functions.
I/O: Input/Output. I/O Chassis: See chassis.
I/O Module: A device that interfaces between the user devices and the PC.
I/O Rack: See rack.
Keying: Keying bands installed on backplane connectors to ensure that only one type of module can be inserted into a keyed connector.
Master Control Relay (MCR): A mandatory hardwired relay that can be de-energized by any series-connected emergency stop switch. Whenever the master control relay is de-energized, its contacts open to de-energize all application I/O devices.
MOS: Metal Oxide Semiconductor. A semiconductor device in which an electric field controls the conductance of a channel under a metal electrode called a gate.
Mode: A selected method of operation. Example: run, test, or program.
Module: An interchangable, plug-in item containing electronic components.
Module Addressing: A method of identifying the I/O modules installed in a chassis.
Module Group: Adjacent I/O modules which relate 16-I/O terminals to a single 16-bit image table word.
Module Slot: A location for installing an I/O module.
NEMA Standards: Consensus standards for electrical equipment approved by the members of the National Electrical Manufacturers Association (NEMA).
NEMA Type 12: A category of industrial enclosures intended for indoor use to provide a degree of protection against dust, falling dirt, and dripping non-corrosive liquids. They do not provide protection against conditions such as internal condensation.
Noise: Unwanted disturbances imposed upon a signal that tend to obscure its data content.
Page 86
Page A-4 Glossary
Output Devices: Devices such as solenoids and motor starters that receive data from the programmable controller.
PC: See Programmable Controller.
Peripheral Equipment: Units which communicate with the programmable controller, but are not part of the programmable controller. Example: a programming device or computer.
Port: A connection point on a processor or peripheral device. PR: See Preset Value.
Preset Value (PR): The number of time intervals or events to be counted.
Processor: The decision making data and storage sections of a PC.
Programmable Controller: A solid-state control system which has a user-programmable memory for storage of instructions to implement specific functions such as I/O control, logic, timing, counting, report generation, Data Highway communication, arithmetic, data and file manipulation. A PC consists of a central processor, input/output interface, and memory. A PC is designed as an industrial control system.
Rack: An addressing concept equivalent to 128 discrete I/O.
RAM: Random Access Memory. The type of memory in which data access is independent of the data most recently accessed.
Remote I/O PC: A PC system where some or all of the 1/O racks are remotely mounted from the PC. The location of remote I/O racks from the PC may vary depending on the application and the PC used. Also see Local I/O PC.
Remote Mode Selection: A feature which allows the user to select or change processor modes of operation with a peripheral device from a remote location.
Remote Programming: A method of performing PC programming by connecting the programming device to the network rather than to the PC.
Report Generation: The printing or displaying of user-formatted application data by means of a data terminal. Report generation can be initiated by means of either a user program or a data terminal keyboard.
ROM: Read Only Memory. A type of memory with data content that cannot be changed or is changed infrequently. In use, bits and words are read on demand, but not changed.
Page 87
Page A-5 Glossary
Suppression Device: A unit that attenuates the magnitude of electrical noise.
System: A set of one or more PCs, I/O devices and modules, computers, the associated software, peripherals, terminals, and communication networks, that together, provide a means of performing information processing for controlling machines or processes.
Watchdog Timer: A timer that monitors logic circuits controlling the processor. If the watchdog timer is not in its programmed time period, it will cause the processor to fault.
Word: A grouping or a number of bits in a sequence that is treated as a unit.
Word Length: The number of bits in a word. In PC, these are generally only data bits. One PC word = 16 data bits.
Page 88
Page 89
Page I-1 Index
Accumulated Value 2-12 Addressing 5-5
Audience 1-1
Backpanel 3-20 3-21
Battery 4-6
Lithium 2-6
Pack 2-13
Housing 2-6
Mounting hardware set 2-13 Holder 4-5
Cable
Muiti-conductor 3-24 Multi-conductor shielded 3-23 Caution 1-2
Convection cooling 3-4 CMOS RAM 2-4 Complementary Metal Oxide Semiconductor Random Access Memory 1-1 Connecting
Power Cable 3-32 Industrial Terminal 3-37 Battery Pack 4-3
Copper Wire 3-21
Current 2-9
Data Cartridge 2-11
Data Cartridge Recorder 2-11 Data Highway cables 2-5 Data Highway
Modules 2-5
Cables 2-5
Data Highway Modules 2-5 Digital Cassette Recorder 2-11 Disconnects 3-9
Disposal
Battery 4-6
Earth Ground 3-21 Emergency Stop Switches 5-7 EEPROM 1-1 4-1 6-2 Electrically Erasable Programmable Read Only Memory 1-1
Emergency Stop 3-8 Enclosure 3-2
NEMA 3-4
Environment
Specifications 3-2
Field Wiring Arm 3-22
INDEX
Force
1/O bits 2-12 Function 5-9 On 5-9
Off 5-9
Force Functions 5-9 Force On 5-9 Force Off 5-9 Using 5-10 Removing 5-10 Clearing 5-10 Testing 5-11 Force Off 5-9 Force On 5-9 Fuse 2-5
General Features 2-2 Ground Bus 3-21 Grounding 3-6
Earth 3-21
Hand Held Terminal 2-12 Hardware 3-1
Features 2-3 Processor System 3-1 Input Devices 5-12 Input Source Voltage 2-9 Industrial Terminal 2-7 3-37 Install
Keying Bands 3-11
1/O Modules 3-13 Processor 3-2 3-4 3-15 Power Supplies 3-16 Industrial Terminal 3-37 INTFC
Connector 2-5
Port 2-4
1/O Chassis 2-5 3-13 I/O Modules 3-13 5-3 Keying Bands 3-11 Lithium 2-6
Master Control Relay 3-8 5-7 Math 2-2
Memory
Protect 3-10
Store Switch 2-4 Module 2-8 4-2 Memory Module 2-8
Page 90
Page |-2 Index
Memory Protect 3-10 Memory Store Switch 2-4 Mounting
Backpanel 3-20 Multi-conductor Cable 3-24 Multi-conductor Shielded Cable 3-23 3-27 NEMA 3-4
Noise
Electric 3-3
Generator 3-3
Output Devices 5-7 Paralleling Cable 3-36 Port
P/S Parallel 2-5
Power Cable 3-33 5-7 Connecting 3-32 Power Supply 2-7 3-39 POWER Switch 2-5 Preset Value 2-12 Processor System 2-1 Hardware 3-1
PROC RUN/FAULT 2-4 P/S ACTIVE 2-4
P/S Parallel 2-5 Publication 1-2 Pushbutton 5-8
Remote program 2-7 Remote Test 2-7
Report Generation Module 2-10 Replacing
Battery 4-4 RUN/PROGRAM 2-7 Specifications
Power Supply 2-7 Status Indicators 2-4 5-3 Suppression Devices 3-3 Switch
Memory Store 2-4 POWER 2-5
Group Assembly 3-9 6-2 Terminal Numbers 3-27 Terminal Strip 2-5 3-29 Test
Output Devices 5-7 Input Devices 5-12 Program 5-13
Force Functions 5-11 Training Center 1-1 Troubleshooting 6-1
Warning 1-2
Wire
Single-conductor 3-22 Terminal Strip 3-29 6-2 Wiring
Field Wiring Arms 3-22 Grounding 3-21
Error 5-3