Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 26 of 29

1772 Mini PLC-2/05 Processor (Cat. No. 1772-LS, LSP) Programming and Operations Manual, pages 251 to 260

Pages 251 to 260 of 289

The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1772-LSP

Page 251

Appendix B Glossary

Parallel Operation A type of information transfer where all bits, bytes, or words are handled simultaneously. Parallel Output Simultaneous availability of two or more bits, channels, or digits. Parallel Transmission The simultaneous transmission of bits which constitute a character. Peripheral Equipment Units which communicate with the programmable controller, but are not part of the programmable controller. Example: a programming device or computer. PR See Preset Value. Preset Value (PR) The number of time intervals or events to be counted. Primary Processor A PC that controls all the I/O, but has a backup processor to take over system operation in case it fails. Process 1) Continuous and regular production executed in a definite uninterrupted manner. 2) One or more entities threaded together to perform a requested service. Processor The decision making data and storage sections of a programmable controller. Program A set of instructions used to control a machine or process. Program Scan Time The time required for the processor to execute the instructions in the program. The program scan time may vary depending on the instructions and each instruction’s status during the scan. Program Storage The portion of memory reserved for saving programs, routines, and subroutines. Programmable Controller A solid-state control system which has a user-programmable memory for storage of instructions to implement specific functions such as I/O control, logic, timing, counting, report generation, Data Highway communication, arithmetic, data and file manipulation. A programmable controller consists of a central processor, input/output interface, and memory. A programmable controller is designed as an industrial control system. B-15

Page 252

Appendix B Glossary

PROM Programmable Read Only memory. A type of ROM that requires an electrical operation to store data. In use, bits, or words are read on demand but not changed. Rack An I/O addressing unit that corresponds to 8 input image table words and 8 output image table words. Rack Fault 1) A red diagnostic indicator that lights to signal a loss of communication between the processor and any remote I/O chassis. 2) The condition which is based on the loss of communication. RAM Random Access Memory. The type of memory in which data access is independent of the data most recently accessed. Red 1) To acquire data from a storage device. 2) The transfer of data between devices such as a peripheral device and a computer. Read/Write Memory A memory where data can be stored (write mode) or accessed (read mode). The write mode replaces previously stored data with current data; the read mode does not alter stored data. Record 1) A group of data that is stored together and/or used together in processing. 2) A collection of related data treated as a unit. See File. Register A memory word or area used for temporary storage of data used with mathematical, logical, or transferal functions. Relay Logic A representation of the program or other logic in a form normally used for relays. Remote I/O processor A processor system where some of all of the I/O racks are remotely mounted from the processor. The location of remote I/O racks from the processor may vary depending on the application and the processor used. Also see Local I/O Processor. Remote Mode Selection A feature which allows the user to select or change processor modes of operation with a peripheral device from a remote location. B-16

Page 253

Appendix B Glossary

Remote Programming A method of performing programming by connecting the programming device to the network rather than to the processor. Report Generation The printing or displaying of user-formatted application data by means of a data terminal. Report generation can be initiated by means of either a user program or a data terminal keyboard. Routine A sequence of instructions which monitors and controls a specific application function. Rung A group of instructions that controls an output or storage bit, or performs other controls functions such as file moves, arithmetic and/or sequencer instructions. This is represented as one section of a logic ladder diagram. SBR See Subroutine Area. Scan Time See Program Scan Time and I/O Scan Time Screen The viewing surface of a CRT where data is displayed. Scrolling The vertical movement of data on a CRT display caused by the dropping of one line of displayed data for each new line added. Search Function Allows the user to quickly display any instruction in the programmable controller program. Self-Diagnostic The hardware and firmware within a controller that monitors its own operation and indicates any fault which it can detect. Serial Operation A type of information transfer where the bits are handled sequentially. Contrasted with Parallel Operation. Signal The event or electrical quantity that conveys information from one point to another. Signaling Rate A measure of signaling speed equal to the number of discrete conditions or signal events per second. See Baud. B-17

Page 254

Appendix B Glossary

State The logic 0 or 1 condition in processor memory or at a circuit input or output. Station Any programmable controller, computer, or data terminal connected to, and communicating by means of, a data highway. Storage See Memory. Storage Bit A bit in a data table word which can be set or reset, but is not associated with a physical I/O terminal point. Subroutine A program segment in the ladder diagram that performs a specific task and is available for use. Subroutine Area (SBR) A portion of memory where subroutines are stored. Syntax Rules governing the structure of a language. System A set of one or more programmable controllers, I/O devices and modules, computers, the associated software, peripherals, terminals, and communication networks, that together, provide a means of performing information processing for controlling machines or processes. Tasks A set of instructions, data, and control information capable of being executed by a CPU to accomplish a specific purpose. Terminal Address A 5-, 6-, 7-, 8-, or 9-digit number which identifies a single I/O terminal. It is also related directly to a specific image table bit address. Trailing Edge One-Shot A programming technique that sets a bit for scan when its input condition has made a true-to-false transition. The true-to-false transition represents the trailing edge of the input pulse. True As related to processor instructions, an enabled logic state. Underflow Bit A bit that is set to indicate the result of an operation which is less than the minimum value that can be contained in a register. B-18

Page 255

Appendix B Glossary

Upload/Download Commonly refers to the reading/writing of programs and data tables from or into processor memory. The commands to do these processes come from some supervisory device. Upper Nibble The four most significant bits of a byte. Variable A factor which can be altered, measured, or controlled. Variable Data Numerical information which can be changed during application operation. It includes timer and counter accumulated values, thumbwheel settings, and arithmetic results. Volatile Memory A memory that loses its information if the power is removed. Watchdog Timer A timer that monitors logic circuits controlling the processor. If the watchdog timer is not reset in its programmed time period, it will cause the processor to fault. Word A grouping or a number of bits in a sequence that is treated as a unit. Word Length A number of bits in a word. In a processor, these are generally only data bits. One processor word equals 16 data bits. Word Storage An unused data table word which may be used to store data without directly controlling an output. Any storage word may be monitored as often as necessary by the user program. Work Area A portion of the data table reserved for specific processor functions. Write 1) The process of loading information into memory. 2) Block Transfer; a transfer of data from the processor data table to an intelligent I/O module. ZCL Instructions A user-programmed fence for ZCL zones. ZCL Zones Assigned program areas which may control the same outputs through separate rungs, at different times. Each ZCL zone is bound and controlled by ZCL B-19

Page 256

Appendix B Glossary instructions. If all ZCL zones are disabled, the outputs would remain in their most recent controlled state. Zone Control Last State (ZCL) See ZCL Zones.

B-20

Page 257

Appendix

C

Quick Reference

Data Table Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-22 Data Table Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-22 Data Table Organization, Factory Configured Data Table . . . . . . . C-33 Approximate Execution Time Per Scan . . . . . . . . . . . . . . . . . . . . . C-44 Relay Type Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-66 Program Control Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-77 Timer Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-88 Counter Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-99 Data Manipulation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-100 Arithmetic Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-111 File Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-122 Sequencer Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-133 Jump/Subroutine Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-144 Block Transfer Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-155 Editing Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-166 Search Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-177 Clear Memory Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-188 Help Directories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-199 Report Generation Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-200 Address Delimiters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-211 Alpha/Graphic Key Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-222 Industrial Terminal Control Codes . . . . . . . . . . . . . . . . . . . . . . . . . C-233 Contact Histogram Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-244 Troubleshooting Aids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-255

C-1

Page 258

Appendix C Quick Reference

Table C.A Data Table Configuration Function

Key Sequence

Mode

Description

Data table configuration

[SEARCH] [5][0] [Numbers]

Program

If the number of 128-word sections is 1 or 2, enter this number, and the number of timers/counters. If the number of 128-word sections is 3 or greater, enter only this number. The industrial terminal will calculate and display the data table size in decimal.

Processor memory layout

[SEARCH] [5][4]

Any

Displays the number of words in the data table area, user program area, message area and unused memory.

Either

[CANCEL COMMAND]

To terminate.

Table C.B Data Table Size

C-2

Enter

Data Table Size

01

128

02

256

03

384

04

512

05

640

06

768

07

896

08

1024

09

1152

10

1280

11

1408

12

1536

13

1664

14

1792

15

1920

16

2048

17

2176

18

2304

19

2432

20

2560

21

2688

22

2816

23

2944

Page 259

Appendix C Quick Reference

Table C.C Data Table Organization, Factory Configured Data Table Total Decimal Words

8

8

Bit Address

Word Address

Decimal Words Per Area

Processor Work Area No. 1

000

00

007 010

17 00

017 020

17 00

026 027 030

17

077 100

17 00

107 110

17 00

117 120

17 00

Output Image Table 16

8 Bit/Word Storage

24

64

72

8

40

8

Reserved

1

2

Timer/Counter Accumulated Values (AC) (or Bit/Word Storage)

Processor Work Area No. 2 Input Image Table

80

8 Bit/Word Storage

88

128

1 2 3 4 5 6

8

40

2944

2816

3072

128

Timer/Counter Preset Values (PR) (or Bit/Word Storage) Expanded Data Table and/or User Program

3

4

00

FactoryConfigured Data Table 6

Maximum Size of Data Table

5

127 130

17 00

177 200

17 00

5577 17

User Program End of Memory

May not be used for accumulated values. Not available for bit/word storage. Bits in this word are used by the processor. Unused timer/counter memory words can reduce data table size and increase user program area. May not be used for preset values. Do not use word 127 for block transfer data storage. Can be decreased to 48 words.

10663-I

C-3

Page 260

Appendix C Quick Reference

Table C.D Approximate Execution Time Per Scan (in average microseconds) Instruction Name

Symbol

Instruction True

Instruction False

Examine on, Examine off Output energize Output latch Output unlatch

-| |-.-| / |-( )-(L)-(U)-

14 16 17 17

11 16 13 13

Get Put

-[G]-(PUT)-

28 26

14

Equal Less than

-(=)-(<)-

23 25

11 13

Get byte Limit test

-|B|-|L|-

16 24

11

Counter reset Retentive timer reset

-(CTR)-(RTR)-

20 20

14 14

Timer on-delay Retentive timer on-delay Timer off-delay

-(TON)-(RTO)-(TOF)-

75 78 82

47 48 60

Up counter Down counter

-(CTU)-(CTD)-

70 75

55 60

3 Digit Math Add Subtract Multiply Divide

-(+)-(-)-(x)-(x)-(÷)-(÷)-

48 80 615 875

15 19 60 60

EAF 01 EAF 02 EAF 03 EAF 04 EAF 05 EAF 13 EAF 14

350-500 350-500 450-2250 400-3100 1850 150-350 250 27

27

Expanded Math Add Subtract Multiply Divide Square root BCD to binary Binary to BCD Add to any of the above when its address is 4008 or greater

C-4