The text of a manual · part 2 of 2
Mini-PLC-2 Family Programmable Controllers Quick Start for Experienced Users, pages 10 to 17
Pages 10 to 17 of 17
The original document is the PDF (326 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1772-LX / LXP and Allen-Bradley 1772-LZP
Page 10
Step
3
Install Backup Battery and Memory Module Install Backup Battery
+ battery cover
- lithium battery cover screw
Install Memory Module the chassis POWER switch to the OFF position and a Move turn off the incoming power source to the processor and chassis. the power cable and lift the latch of the I/O chassis that b Unplug holds your processor, then slide the processor out of the chassis. the processor on a clean, flat surface with the bottom of the c Place module facing you. and insert the memory module in the memory module slot d Position with its label facing upward.
d Slide the processor into the I/O chassis and secure the latch. e Connect the power cable and reapply power to the processor.
Publication 1772-10.2 - March 1996
Page 11
Step
4
Install Processor and Power Supply Install Processor locking bar
Mini-PLC-2/17 processor left-most slot
Install Power Supply If you have a processor with a power supply, and do not need additional current for your I/O modules, skip this step. If you need additional current, use an ac powered supply because we recommend that you use the same input voltage source for two paralleled power supplies. ATTENTION: Do not parallel a 1771-P5 power supply and a processor with a power supply because of power-up and power-down timing difference.
Publication 1772-10.2 - March 1996
Page 12
Step
5
Connect Power to the Processor or Power Supply Connect Power to Processor place tool here a Strip 3/32 inch insulation from the end of the wire. b Insert screwdriver into the square opening and press down with it. the wire into the round opening on the front of the plug and c Insert remove the screwdriver.
insert wire here
Connect Power Supply a Strip 3/8 inch insulation from the end of the wire. b Loosen each terminal screw and place the appropriate wire under it. c Connect power cable to the ac or dc power supply's terminal strip. ac dc 1.5A 125V
SLOW BLOW
5A 32V NORM BLO
120V AC L1 N GN
24V DC +DC COM GND power wire connects to L1 neutral wire connects to N positive negative equipment grounding conductor ground bus connects to GND e Set the input voltage selector switch.
24V dc input voltage selector switch
Publication 1772-10.2 - March 1996
Page 13
Step
6
Connect Programming Terminal the power switch on the front of the terminal to the OFF position a Turn and plug the ac power cord into the terminal.
Mini-PLC-2/02, -2/16, -2/17
Industrial Terminal (rear view)
Channel A PLC-2 Family
Program Panel Interconnect Cable cat. no. 1772-TC 10 ft (3.05 cm)
Interface processor has a power supply, plug the ac power cord into b Iftheyourac power source. one end of the 1772-TC Interconnect Cable to Channel A c Connect at the back of the terminal and connect the other end to the socket labelled INTFC at the front of the processor.
the PLC-2 family keytop overlay onto the keyboard and turn d Place the power switch on the front of the terminal to the ON position. Turn the power switch of the processor to the ON position and e press the keys [1] [1] on the terminal keyboard.
Publication 1772-10.2 - March 1996
Page 14
6–2
Connect to a Personal Computer 62-pin D-shell Connector Pin Male 10.2 cm (4 in.)
22 43
1
62
21
15-pin D-shell Connector Pin Female
3.2 m (10.50 ft.) 10.2 cm (4 in.)
1784-CP2 cable
8
15
1
9
PLC-2 Processor
Industrial Terminal 4
1
5
2
7
3
6
4
26
5
27
6
47
7
48
8
62-pin D-shell
Using 6200 Programming Software
For more information...
For specific information about using 6200 programming software, see the Mini-PLC-2/02, -2/16, -2/17 Processor User Manual, publication 1772-6.5.8.
Cable shield tied to chassis
PLC-2
Any Allen-Bradley or IBM and IBM-compatible machine can be used as a programming device using 6200 or Application Interface (AI) programming software. Before you install the PLC-2 programming software, you need the following: - 640 KBytes of RAM as base memory (extended or expanded memory not required - 10 MBytes of disk space for storing files. - Allen-Bradley DOS version 3.2x if you use a 1784-T50 or 1784-T45 programming terminal. If you use a 1784-T47 programming terminal use DOS 4.01. If you use an IBM PC/XT, IBM PC-AT, or IBM-compatible programming terminal, use DOS 3.2, 3.3, 4.x, or 5.0. - monochrome or color graphics monitor - installed 1785-KL, -KTP, -KT, -KT2, -KTK1 card If your 1784-T50 has DOS version 2.11 or earlier, you must upgrade to the current version of Allen-Bradley DOS. The current version of Allen-Bradley DOS is version 3.21.
Using AI Programming Software
Before you install the AI PLC-3 programming software, you need the following: - IPM PC XT, AT or compatible computer with DOS 2.1 or later
For more information...
For specific information about using AI programming software, see the PLC-2 Ladder Logistics Manual, publication 9399-L2man-07.05.89.
- monitor and graphics board. These display types are supported: monochrome display system CGA display system EGA display system VGA display system - 640K RAM of system memory - a floppy drive and a hard drive
Publication 1772-10.2 - March 1996
Page 15
Appendix
Specifications Specifications
Specifications for Mini-PLC-2 processors follow.
Mini-PLC-2/02 Processor without a power supply (1772-LZ) Location
Mini-PLC-2/16 Processor without a power supply (1772-LX)
Mini-PLC-2/17 Processor without a power supply (1772-LW)
1771 I/O chassis left most slot
Backplane Current
1.25 A Requirement
Battery Back-up
Self-contained lithium battery maintains memory for 1 year with no AC applied to the processor
Data Table Size
48-1920 Floating words
48-3968 Floating words
48-7808 Floating words
Memory Size 16-bit words RAM
2K
4K
7.75K
I/O Scan
0.82 ms (2-slot addressing) 2.00 ms (1-slot addressing) 2.15 ms (1/2-slot addressing)
Program Scan I/O Capacity (Typical) Bulletin 1771 I/O Mode Selection
7.5 ms/K (minimum) 12 ms (typical application program) 128
256
256-512 (maximum)
Key switch on the front panel and from the keyboard of the 1770-T3 terminal
Environmental Conditions Operating Temperature
0 to 60o C (32 to 140o F)
Storage Temperature
-40 to 85o C (-40 to 185o F)
Relative Humidity
5% to 95% (without condensation)
Publication 1772-10.2 - March 1996
Page 16
A-2
Specifications
Mini-PLC-2/02 Processor with a power supply (1772-LZP)
Mini-PLC-2/16 Processor with a power supply (1772-LXP)
Mini-PLC-2/17 Processor with a power supply (1772-LWP)
These processors have the same features as above and they also have a self-contained power supply. Input Voltage
120/220 V ac (switch selectable)
Input Voltage Range
97 to 132 V ac 194 to 264 V ac
Nominal Input Power
96 VA
Frequency
47 to 63 Hz
Output Current to Backplane
4A
Keying (top connector)
Between 46 and 48 Between 54 and 56
Publication 1772-10.2 - March 1996
Page 17
I–2
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.
Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1772-10.2 - March 1996 Supercedes 1772-2.23 October 1985 , 1772-2.27 Publication 1772-10.2 - March 1996April 1988, 1772-2.15 August 1984, 1772-2.16 February 1986
PN 955124-62
Copyright 1996 Allen-Bradley Company, Inc. Printed in USA