Page 1 of Mini-PLC-2 Family Programmable Controllers Quick Start for Experienced Users

Manual · Allen-Bradley

Mini-PLC-2 Family Programmable Controllers Quick Start for Experienced Users

Manual17 pagesPDF 326 KB

Quick start for Allen-Bradley Mini-PLC-2 family controllers (1772-LZ, LZP, LX, LXP, LW, LWP, LS, LSP): chassis, modules, power and specs.

Download the PDF326 KB

Names · 2 models

The models it names

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

A short quick start guide for installing and connecting a basic Allen-Bradley Mini-PLC-2 family programmable controller system, aimed at users who already know the products. It walks through configuring and grounding the 1771 I/O chassis, installing field wiring arms and I/O modules, the backup battery and memory module, the processor and power supply, making power connections and connecting a programming terminal, with specifications for the Mini-PLC-2/02, 2/16 and 2/17 processors.

Its parts

  1. Preface
  2. Configure and Ground I/O Chassis
  3. Install I/O Modules
  4. Install Memory Module
  5. Install Processor and Power Supply
  6. Make Power Connections
  7. Connect Programming Terminal
  8. Specifications

From the manual · read page by page

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

Quick start guide (publication 1772-10.2, March 1996) for experienced users who need to install and connect a basic Mini-PLC-2 family controller system. It lists the processors 1772-LZ, -LZP, -LX, -LXP, -LW, -LWP, -LS and -LSP, walks through chassis setup, I/O, memory module, power and programming terminal connection in six steps, and gives specifications for the Mini-PLC-2/02, -2/16 and -2/17 processors only.

Device
Mini-PLC-2 family processor for the leftmost slot of a 1771 I/O chassis p. 15
Memory
2K words (2/02), 4K (2/16), 7.75K (2/17) p. 15
I/O capacity
128 (2/02), 256 (2/16), 256-512 (2/17) p. 15
Battery backup
Built-in lithium battery holds memory 1 year without AC power p. 15
Operating temperature
0 to 60 C (32 to 140 F) p. 15
Programming terminal
1770-T3 series C, or an IBM PC-compatible computer with 6200 series or AI PLC-2 software p. 5
Built-in supply (P models)
120/220 V ac switch selectable; 97 to 132 or 194 to 264 V ac, 47 to 63 Hz, 96 VA p. 16
Backplane current
Models without a supply draw 1.25 A; P models supply 4 A p. 15, 16
Memory modules
1775-MJ, 1772-MJ p. 5
Terminal cable
1772-TC program panel interconnect cable, 10 ft p. 13
PC cable
1784-CP2, 62-pin D-shell to 15-pin D-shell p. 14
I/O chassis
1771-A1B, -A2B, -A3B, -A3B1, -A4B, -A1, -A2, -A4 p. 5
Power supplies
1771-P3, -P4, -P5, -P7 p. 5
PC interface cards
1785-KL, -KTP, -KT, -KT2 or -KTK1 card for 6200 software p. 14

What this manual walks you through

  • Setting backplane switches and keying the processor slot p. 6
  • Grounding the I/O chassis p. 7
  • Installing field wiring arms and I/O modules p. 8, 9
  • Installing the processor and an added power supply p. 11
  • Wiring power to the processor plug or power supply p. 12
  • Connecting the 1770-T3 programming terminal p. 13
  • Programming from a personal computer with 6200 or AI software p. 14

Good to know

  • A 1771-P5 supply must not be paralleled with a processor that has its own power supply. p. 11
  • Two paralleled supplies should run from the same input voltage source. p. 11
  • With the grounding layout shown, EQUIP GND on the power supply terminal strips is left unconnected to avoid ground loops. p. 7
  • Power is switched off before the processor is removed to fit a memory module. p. 10
  • A 1784-T50 with DOS 2.11 or earlier needs a DOS upgrade before the PLC-2 software is installed. p. 14

Questions this manual answers

What memory module fits a Mini-PLC-2 family processor?

The guide lists the 1775-MJ and 1772-MJ memory modules. p. 5

Where does the keying band go for a Mini-PLC-2 processor?

In the leftmost slot, between pins 46 and 48 and between pins 54 and 56 of the top connector. p. 6

What cable connects a PC to a Mini-PLC-2 processor?

The 1784-CP2 cable, from a 62-pin D-shell connector to the processor's 15-pin D-shell socket. p. 14

What input voltage does the 1772-LZP take?

120 or 220 V ac, switch selectable (97 to 132 or 194 to 264 V ac), 47 to 63 Hz. p. 16

How long does the Mini-PLC-2 battery keep memory?

The self-contained lithium battery keeps memory for 1 year with no AC power applied. p. 15

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1772-10.2, Mini-PLC-2 Family Programmable Controllers, Quick Start for Experienced Users1
    1. 1772-10.2, Front Cover1
    2. 1772-10.2, Inside Cover2
    3. 1772-10.2, Table of Contents3
    4. 1772-10.2, Preface4
    5. 1772-10.2, 1 - Configure and Ground I/O Chassis6
    6. 1772-10.2, 2 - Install I/O Modules8
    7. 1772-10.2, 3 - Install Memory Module10
    8. 1772-10.2, 4 - Install Processor and Power Supply11
    9. 1772-10.2, 5 - Make Power Connections12
    10. 1772-10.2, 6 - Connect Programming Terminal13
    11. 1772-10.2, 7 - Specifications15
    12. 1772-10.2, Back Cover17

From the PDF’s own bookmarks.

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 91-9
  2. Pages 10 to 1710-17

The file

Revision and size

RevisionPublication 1772-10.2, March 1996
PublisherAllen-Bradley
Pages17
PDF326 KB
TextText from the PDF itself; page 1 is a scan, read by OCR, which may hold reading errors.

The first pages · 3 of 17

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 17
Page 2
Page 2of 17
Page 3
Page 3of 17