Spec sheet · Allen-Bradley
Remote I/O Scanner/Distribution Panel (Cat. No. 1772-SD2) Product Data
Spec sheet16 pagesPDF 277 KB
Product data for the Allen-Bradley 1772-SD2 and 1772-SD remote I/O scanner/distribution panels used with PLC-2 family processors.
Covers · 1 model
The models it covers
Summary
What is in it
Allen-Bradley product data for the 1772-SD2 Remote I/O Scanner/Distribution Panel, a stand-alone board that lets PLC-2, PLC-2/20 and PLC-2/30 processors talk to remote 1771 I/O chassis over twinaxial cable; it also covers the older 1772-SD. It explains I/O capacity per processor, trunkline and daisy chain configurations, complementary I/O (1772-SD2 only), status indicators, power supply requirements, mounting, wiring, switch settings, scan times, application considerations and specifications.
Its parts
- Introduction
- Complementary I/O (1772 SD2 Only)
- Status Indicators
- Power Supply Requirements
- Mounting
- Wiring Connections
- Switch Settings
- Scan Times
- Applications Considerations
- Specifications
From the sheet · read page by page
Key facts from this sheet
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Product data for the Allen-Bradley 1772-SD2 Remote I/O Scanner/Distribution Panel, which links PLC-2, PLC-2/20 and PLC-2/30 processors to remote 1771 I/O chassis. It also covers the older 1772-SD panel. It gives capacities, cabling, power, mounting, scan times and application cautions.
- Device
- Compact single-board stand-alone remote I/O scanner for PLC-2, PLC-2/20 and PLC-2/30 processors p. 1
- I/O capacity
- 1772-SD2: 896 points any mix, or 1792 (896 inputs/896 outputs) with complementary I/O p. 1, 16
- Cable distance
- 10,000 feet per channel at 57.6k baud, or 5000 feet per channel at 115.2k baud p. 2
- Adapters
- Up to 16 remote I/O adapter modules (1771-AS) per channel p. 2
- Remote I/O cabling
- 1770-CD twinaxial cable; 1770-XG connector kit with 1770-XF terminators, or 1770-XT terminators when daisy-chained p. 11
- Power
- 1772-P1 supply in the processor or 1777-P2 auxiliary supply (series B or later); 2A max p. 9, 16
- Processor cable
- 1772-CS processor/scanner interconnect cable p. 4
- Indicators
- Eight bicolor red/green rack status LEDs p. 9
- Dimensions (W x H x D)
- 2.5 x 13.58 x 8.63 inches (6.35 x 34.49 x 21.9 cm) p. 16
- Environment
- Operating 0° to 60°C (32° to 140°F); humidity 5% to 95% without condensation p. 16
- Mounting
- Panel mount to the right of the processor, at least six inches away and within 10 cable feet p. 9
- Replaces 1772-SD
- Fully downward compatible; swaps in with the same switch settings p. 15
- Fault status bits
- Remote I/O fault status bits in word addresses 125 and 126 p. 13, 15
- Remote racks
- Up to 128 I/O per rack, made of one to four 1771 I/O chassis p. 2
What this sheet walks you through
- Laying out trunkline/dropline and daisy chain remote I/O systems p. 3, 4
- Planning complementary I/O racks on the 1772-SD2 p. 5, 6, 8
- Mounting the panel p. 9, 10
- Wiring and terminating the twinaxial remote I/O channel p. 11
- Setting the configuration switches p. 11, 12
- Estimating remote I/O scan and response times p. 11, 12, 13
- Replacing a 1772-SD with a 1772-SD2 p. 15
- Programming critical outputs for a remote rack fault p. 15, 16
Good to know
- Do not mount the panel more than 10 cable feet from the processor. p. 9
- With block transfer, the user program scan must stay under 250 milliseconds or transfers may be missed. p. 14
- After a fault in a remote chassis with inputs, those inputs hold their last state, which can cause unexpected machine motion. p. 15
- The auxiliary power supply must be used if the controller has a core memory module. p. 9
- I/O is limited to 256 points with any processor if the system includes any 1777 I/O. p. 1
Questions this sheet answers
What is the difference between the 1772-SD and 1772-SD2?
The 1772-SD has the same capabilities except complementary I/O and handles up to 896 I/O points. The 1772-SD2 replaces it and is fully downward compatible. p. 2, 15
How far can remote I/O chassis be from the 1772-SD2?
Up to 10,000 feet per channel at 57.6k baud, or 5000 feet per channel at 115.2k baud. p. 2
What cable connects the 1772-SD2 to remote I/O adapters?
1770-CD twinaxial cable runs to 1771-AS remote I/O adapter modules. p. 2, 11
What do the LEDs on the 1772-SD2 mean?
A rack LED is green when the rack is used and communication is valid, off when unused, and red on a rack fault. All LEDs red means the power-up memory check failed. p. 9
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 2 parts
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file