The text of a spec sheet · part 2 of 2
Remote I/O Scanner/Distribution Panel (Cat. No. 1772-SD2) Product Data, pages 9 to 16
Pages 9 to 16 of 16
The original document is the PDF (277 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1772-SD2
Page 9
Product Data Remote I/O Scanner Distribution Panel
Status Indicators
The front of the scanner/distribution panel has eight bicolor red/green LED indicators. If an I/O rack is declared used (regardless of physical configuration) and serial communication is valid, that rack status LED will be green. If not used, the LED will be off. For an I/O rack fault condition, the corresponding rack status LED will be red. At power up, the scanner/distribution panel PROM memory is checked to verify its integrity. Any diagnostic error results in the scanner/distribution panel halting communication with the processor. In this case, all the LED’s turn red.
Power Supply Requirements
The Power Supply (cat. no. 1772-P1) in the processor or an Auxiliary Power Supply (cat. no. 1777-P2) may be used to power the scanner/distribution panel. The auxiliary supply must be used if the controller is equipped with a core memory module. The auxiliary power supply must be series B or later.
Mounting
The scanner/distribution panel is designed for panel mounting. Mounting dimensions are shown in figure 5. Recommended mounting is to the right of the PLC-2, PLC-2/20 or PLC-2/30 processor. Maintain at least six inches clearance between the scanner/distribution panel and the processor. NOTE: Do not mount the scanner/distribution panel more than 10 cable feet from the processor.
9
Page 10
Product Data
Remote I/O Scanner Distribution Panel
Figure 5 Mounting Dimensions
8.63" (21.92cm), A st PAA wat ayee 0.625” (1.588cm) ( ; ; 11.0" 13.58 (27.94cm) (34.49cm) | | I 0.312 (0.79cm) L na
1.53” (8880m) Wiis (4.039cm) a
2.50" 0.625” (6.35cm) (1.588cm)
11225
10
Page 11
Product Data Remote I/O Scanner Distribution Panel
Wiring Connections
Use Twinaxial Cable (cat. no. 1770-CD) to connect the scanner/distribution panel to the remote adapters. Connect the cable to the scanner/distribution panel at the terminal strip on the front of the module. The remote adapters may be connected to the remote I/O channel using Connector Kit (cat. no. 1770-XG). The remote I/O channel must be terminated using Terminators (cat. no. 1770-XF) at both ends (figure 1). Optionally, remote adapters may be connected to the remote I/O channel directly. The remote I/O channel is terminated using Terminators (cat. no. 1770-XT) at the scanner/distribution panel and the last remote adapter (figure 2).
Switch Settings
There are three switch assemblies beneath the cover plate of the scanner/distribution panel (figure 6). To select a particular configuration, remove the two slotted screws which secure the cover plate. Set the switches to your requirements using a blunt-pointed instrument, such as the tip of a ball-point pen. Do not use anything that might break off and jam the switch. Replace the cover plate and secure screws.
Scan Times
The processor goes through a scan consisting of program execution and I/O update. During the I/O update portion of the processor’s scan, the processor communicates with local I/O racks and the scanner/distribution panel. The scanner/distribution panel goes through its own remote I/O scan which is not synchronous to the processor’s scan. In this remote I/O scan, I/O chassis are scanned sequentially by I/O rack number regardless of I/O channel. The remote I/O scan time varies according to the amount of I/O data change taking place; however, with no block transfer, the I/O scan time per I/O chassis (primary or complementary) is:
Nominal Worst case
5,000 ft max (115.2k baud)
10,000 ft max (57.6k baud)
7ms 8ms
8.5ms 10ms
The remote I/O scan time with no block transfer is the product of the following: (I/O scan per chassis) (total number of I/O chassis)
11
Page 12
Product Data Remote I/O Scanner Distribution Panel
Figure 6 Switch Settings
With no block transfer, the response time for recognizing an input impulse is the sum of the following: Input module delay time Remote I/O scan time Processor scan time including the local I/O update time
12
Page 13
Product Data Remote I/O Scanner Distribution Panel
Table B Fault Table Rack
Module Groups
Fault Status Bit
1 0-1 2-3 4-5 6-7
12507 12506 12505 12504
2
0-1 2-3 4-5 6-7
12503 12502 12501 12500
3
0-1 2-3 4-5 6-7
12517 12516 12515 12514
4
0-1 2-3 4-5 6-7
12513 12512 12511 12510
5
0-1 2-3 4-5 6-7
12607 12606 12605 12604
6
0-1 2-3 4-5 6-7
12603 12602 12601 12600
7
0-1 2-3 4-5 6-7
12617 12616 12615 12614
The response time for changing the state of an output device in response to an input change is the sum of the following: Input module delay time Two remote I/O scan times Processor scan time Delay time of the output device
13
Page 14
Product Data Remote I/O Scanner Distribution Panel
Block transfer modules are handled fastest by placing one in each rack used or distributing them evenly throughout the remote I/O chassis. The scanner/distribution panel performs one block transfer per processor I/O scan. It should be noted that block transfer modules increase I/O scan times significantly, due to the large amounts of data that must be transferred. Therefore, they should be placed in local I/O racks, if possible. Contact your Allen-Bradley systems specialist for detailed information.
Applications Considerations
14
Some important application considerations are listed below. 1.
If the 1772-SD2 scanner/distribution panel is being operated in the dependent mode or in the independent, nonsearch mode, quarter racks (pair of module groups) within a rack group, i.e., all the same rack number, must have module groups numbered sequentially. For example, the first quarter rack must be numbered module group 0, 1. The second quarter rack must be 2, 3, not 4, 5 or 6, 7. Module group numbers may not be skipped or a rack fault will occur and be indicated at the scanner/distribution panel.
2.
If the 1772-SD2 scanner/distribution panel is being operated in the independent and search mode and gaps are left in the module group numbers as described above, a rack fault will be indicated on the 1772-SD2 and in the appropriate bit for the missing rack in the rack fault status word in the processor. However, the existing unfaulted racks will operate properly.
3.
If block transfer is used, user program scan time must be less than 250 milliseconds. Scan times longer than this may cause block transfers to be missed.
4.
If your 1772-SD2 scanner/distributor panel is prior to series A, revision B (series A, revision G for 1772-SD), the following procedure must be used. When you use a 1770-T1, -T2, or -T3 industrial terminal to enter the remote mode select function for a remote I/O PLC-2/30 system, you must select the remote test mode before changing from remote program to remote run/program mode. To go from remote program to remote run/program mode, press keys [SEARCH] 591 then keys [SEARCH] 590. Following this procedure will help to ensure proper remote system operation.
Page 15
Product Data Remote I/O Scanner Distribution Panel
5.
The 1772-SD2 scanner/distribution panel is fully downward compatible with the 1772-SD. That is, a 1772-SD scanner/distribution panel may be replaced with a 1772-SD2 having the same switch settings without changing anything else in the system (1771-AS I/O adapter module switch settings remain valid). When complementary I/O chassis (racks) are being added to an existing remote system, the switches on the 1771-AS I/O adapter module must be set appropriately. Consult the Remote I/O Adapter Module product data (publication 1771-938) for the appropriate switch setting information.
6.
If you are operating a PLC-2/20 or PLC-2/30 remote system with independent fault control, you may have a condition which you should correct thru a change in programming. WARNING: If a fault should occur in a remote I/O chassis containing input data, the input data will remain in their last prefault state at the Remote Scanner/Distribution Panel (cat. no. 1772-SD, -SD2).If the following recommendations are not followed, unexpected machine motion could occur with possible injury to personnel.
The I/O image table of the remote scanner/distribution panel retains the status of inputs when the fault occurred, and updates the PC processor with this status each I/O scan. If you have selected independent fault control, the inputs of either the faulted chassis or the entire rack will be frozen depending on how you have selected the faulted I/O search. This condition applies when these inputs, located in a remote chassis, control outputs located in any chassis. As a result, if an I/O fault should occur in a chassis containing inputs, outputs in an unfaulted local or remote rack can remain on according to the last state input conditions governing those outputs. To guard against this condition, you should use programming techniques to ensure that critical outputs are properly controlled when a fault of this type occurs. By monitoring the remote I/O fault status bits (in word addresses 125 and 126) you can detect a fault in the rack and module groups of the input modules which condition your critical outputs. Then you can use one or more of the following programming techniques to establish the required states for your critical outputs. MCR, outputs within the MCR zone are disabled. (The outputs in this case must be controlled by non-retentive program instructions.) ZCL, outputs within the ZCL zone remain in their last state.
15
Page 16
Product Data Remote I/O Scanner Distribution Panel
FFM, update selected input image table word values with a file-to-file move (FFM) instruction to condition input instructions of critical output rungs. (Place this rung at the beginning of your program. For PLC-2/30 controllers, only.) NOTE: When using remote I/O fault bits, you must not have input modules in rack 2, module groups 5 and 6. Independent fault control, remote I/O fault bits, and associated module switch settings are described earlier in this publication. For information on MCR and ZCL instructions, refer to the appropriate Programming and Operations Manual (publication 1772-802 for the PLC-2/20 controller; publication 1772-806 for the PLC-2/30 controller). The FFM instruction is described in the PLC-2/30 Controller
Specifications
Function G Distribute output status data to outputs G Gather input status data from inputs I/O Points (Max.)
G 896 Standard (any mix) G 1792 with complementary I/O (896 inputs/896 outputs)
Current Requirement (from System power Supply) G 2A (max.)
With offices in major cities worldwide WORLD HEADQUARTERS Allen-Bradley 1201 South Second Street Milwaukee, WI 53204 USA Tel: (1) 414 382-2000 Telex: 43 11 016 FAX: (1) 414 382-4444
EUROPE/MIDDLE EAST/AFRICA HEADQUARTERS Allen-Bradley Europe B.V. Amsterdamseweg 15 1422 AC Uithoorn The Netherlands Tel: (31) 2975/43500 Telex: (844) 18042 FAX: (31) 2975/60222
PLC is a registered trademark of Allen-Bradley Company Publication 1772-2.18 - April 1984
16 Supersedes Publication 1772-929 - April 1984
Environmental conditions G Operational Temperature 0° to 60°C (32° to 140°F) G Storage Temperature -40° to 85°C (-40° to 185°F) G Relative Humidity 5% to 95% (without condensation) Dimensions (W x H x D)
G 2.5 x 13.58 x 8.63 inches G 6.35 x 34.49 x 21.9 cm
As a subsidiary of Rockwell International, one of the world’s largest technology companies, Allen-Bradley meets today’s challenges of industrial automation with over 85 years of practical plant-floor experience. More than 11,000 employees throughout the world design, manufacture and apply a wide range of control and automation products and supporting services to help our customers continuously improve quality, productivity and time to market. These products and services not only control individual machines but integrate the manufacturing process, while providing access to vital plant floor data that can be used to support decision-making throughout the enterprise. ASIA/PACIFIC HEADQUARTERS Allen-Bradley (Hong Kong) Limited Room 1006, Block B, Sea View Estate 28 Watson Road Hong Kong Tel: (852) 887-4788 Telex: (780) 64347 FAX: (852) 510-9436