Product Data Remote I/O Scanner Distribution Panel
Allen-Bradley Remote I/O Scanner/Distribution Panel (Cat. No. 1772-SD2)
Product Data
Introduction
The Remote I/O Scanner/Distribution Panel is a compact, single board, stand-alone unit. It enables the Allen-Bradley PLC-2, PLC-2/20 and PLC-2/30 processors to communicate with up to 1792 I/O points (896 inputs and 896 outputs) as indicated in table A. Table A Processor
Max I/O 1
Max I/O with Complementary 2
PLC-2 (1772-LR) PLC-2/20 (1772-LP1) PLC-2/20 (1772-LP2) PLC-2/30 (1772-LP3)
256 512 896 896
512 1024 1792 1792
1 I/O maximum is 256 regardless of processor type if system includes any 1777 I/O. 2 1772-SD2 only - half inputs/half outputs.
1
Page 2
Product Data Remote I/O Scanner Distribution Panel
NOTE: The 1772-SD remote I/O scanner/distribution panel has all the capabilities of the 1772-SD2 remote I/O scanner/distribution panel except complementary I/O. The 1772-SD will communicate with up to 896 I/O points maximum (any mix). The 1772-SD2 obsoletes the 1772-SD. However, since many 1772-SD panels are in use, this document covers both panels. Bulletin 1771 I/O chassis may be placed up to 10,000 feet away from the scanner/distribution panel. Interconnection between the scanner/distribution panel and the Remote I/O Adapter Module (cat. no. 1771-AS) is via Twinaxial Cable (cat. no. 1770-CD). Refer to figures 1 and 2. NOTE: The cable limitation is 10,000 feet for each channel (20,000 feet total) at 57.6k baud rate, or 5000 feet for each channel (10,000 feet total) at 115.2k baud rate. A maximum of 16 remote I/O adapter modules may be connected to each channel. The functions of the remote I/O scanner/distribution panel are: Gather input data from remote I/O adapter modules and send this data to the PLC-2, PLC-2/20 and PLC-2/30 processor which uses it to update the input image table. Receive output data from the output image table of the PLC2, PLC-2/20 and PLC-2/30 processor and distribute this data to remote I/O adapter modules, thereby updating the status of the output signals. The scanner/distribution panel may be connected directly for all remote I/O, or up to two local I/O chassis may be connected between it and the processor chassis. Remote I/O consists of racks of up to 128 I/O, made up of one to four 1771I/O chassis.(Refer to Remote I/O Adapter Module Assembly product data, publication 1771-938.) Figures 1 and 2 outline I/O configuration examples and figure 3 illustrates I/O addressing.
2
Page 3
Product Data
Remote I/O Scanner Distribution Panel
Figure 1 1/0 Trunkline/Dropline Configuration Example
Blue
Shield ~ Clear 7 Channel A, - p> Blue ® - ° Shield i" |= Clear Channel! B as ee 104 oo l, IS
1/O Rack No. 4
©) a (/O Rack
? No.3
1. Terminator Set (1770-XF)
2. Connector Kit (1770-XG)
3. Twinaxial Cable (1770-CD) 10,000 Ft. Max Total Trunkline Each I/O Channel, 100 Ft. Max. Each Dropline
4.1/0 Interconnect (1777-CA, 3 Ft. or 1777-CB, 6 Ft.)
5.1/O Power Cable (1771-CJ, 8 Ft. or 1771-CK, 3 Ft.) Note: If a core memory module is used, the I/O Scanner must have a separate power supply.
6. Processor/Scanner
2 Interconnect Cable
(1772-CS)
11221
Page 4
Product Data
Remote I/O Scanner Distribution Panel
Figure 2
Daisy Chain Configuration Example
TS if ie
2 " ° °
Q
1/O Rack No. 1 (Local)
ja teterer rite He
1/O Rack No. 4 prereth L ERPEEE
Lely ee of
1.1/0 Channel Terminator (1770-XT) 2. Twinaxial Cable (1770-CD) 10,000 Ft. Max. Total Each I/O Channel 3.1/0 Interconnect Cable (1777-CA, 3 Ft. or 1777-CB, 6 Ft.) 4.1/0 Power Cable (1771-CJ, 8 Ft. or 1771-CK, 3 Ft.) Note: If a core memory module is used, the t/O Scanner must have a separate power supply. 5. Processor/Scanner Interconnect Cable (1772-CS)
1/O Rack No. 2
CCT
J a J yw Woy ii
1? ff al gl al el gt li DI el
Channel A
Channel B
Blue Lys Blue Shield Shield Clear Clear
1/O Rack > No.3
Blue
Shield
Clear
41222
Page 5
Product Data Remote I/O Scanner Distribution Panel
Figure 3 I/O Addressing
Complementary I/O (1772-SD2 Only)
To obtain 1792 I/O points, complementary I/O techniques must be used. The essence of complementary I/O is that any physical I/O chassis in the remote I/O system may be duplicated by rack number and module group number within the I/O rack. Complementary I/O racks are restricted as follows: 1.
For optimum system utilization, the complementary I/O rack must be the same size as the primary rack that it duplicates. The complementary rack must be on the same channel of the scanner. If the complementary rack is a different size than the primary rack, the first module group number for both must be the same, the maximum physical module group number in the complementary rack must not exceed 7, and the complementary rack must be set for the last rack. In addition, for any given rack number, primary and/or complementary racks beyond the complementary rack set for the last rack will not be scanned.
2.
Complementary I/O racks must contain module group-for module group the opposite I/O function of that in the primary rack. That is, if the primary rack has an input module or modules in module group 0, then the complementary rack may only have output modules in module group 0 and vice versa. This is required for all module groups in the racks (figure 4).
5
Page 6
Product Data Remote I/O Scanner Distribution Panel
3.
6
Block transfer modules may be used in complementary I/O remote systems. Double slot block transfer modules may be used in either primary or complementary I/O racks provided that: 1) no module is placed in the lower slot of the opposite rack; and 2) only an output module (if any) is placed in the upper slot of the opposite rack. Lower slot is defined as the left slot of a module group; upper slot, right slot of a module group. Single slot block transfer modules may be used in either primary or complementary I/O racks provided that: 1) no module is placed in the corresponding slot of the opposite rack; and 2) only an output module (if any) is placed in the opposite slot of the opposite rack.
Page 7
Product Data
Remote I/O Scanner Distribution Panel
Figure 4 Complementary I/O Example
Module Group 0 1 2 3 Slot 0 1 0 1 0 1 0 1
6 etree ee
0 0 Block | {| Block T T Xfer] oN Xfer q @p @ ® Pye U U Single U | Double T T Slot} T Slot
C
Primary Rack #2
Module Group 0 1 2 3 Slot 0 1 Oo 1 0 1 Oo 1
6 Oe A i ath br
REMOTE 1/0 ADAPTER o|o O O LOT OtN tda| la |e TIT T T misis P@PIP4 Pq @ ®@ P Yep P P ulult T
Ulu; >] rly] uty fu TIT T T
Olle
Complementary Rack #2
14224
Page 8
Product Data Remote I/O Scanner Distribution Panel
4.
Complementary I/O racks must be connected to the remote I/O trunkline as though they were additional primary racks. The maximum number of adapters per channel remains 16.
5.
I/O addressing by the processor for complementary racks follows the same format as that used for primary racks.
6.
The ASCII Interface Module (cat. no. 1771-DA) must be at least a revision F to be used in either the primary or complementary rack of a complementary I/O system.
7.
The following modules may be used in primary or complementary I/O racks opposite any module. Analog Input Expander Assembly (cat. no. 1771-E1), 8 single ended inputs Analog Input Expander Assembly (cat. no. 1771-E2), 6 differential inputs Analog Input Expander Assembly (cat. no. 1771-E3), 6 current sourcing inputs Analog Output Expander Assembly (cat. no. 1771-E4), 4 single ended inputs Thermocouple Input Expander Module Assembly (cat. no.1771-IY), 6 inputs Servo (Encoder Feedback) Expander Assembly (cat. no.1771-ES) Communication Adapter Module (cat. no. 1771-KA) Communication Controller Module (cat. no. 1771-KC) Stand Alone Communication Controller Module (cat. no.1771-KD) Data Highway/RS-232-C Interface Module (cat. no. 1771-KF) PLC-2 Family/RS-232-C Interface Module (cat. no. 1771-KG) Pulse Output Expander Assembly (cat. no. 1771-OJ)
8