Page 1
ALLEN-BRADLEY
Ty
Allen-Bradley
Data Highway Plus
Local Area Network
Product Data Introducing Data Highway The Allen-Bradley Data Highway Plus (figure 1) is an economical Plus baseband local area network (LAN) that provides:
® remote programming capabilities ® industrial-hardened interfaces ® easy reconfiguration to meet changing manufacturing needs
Page 2
Allen-Bradley Data Highway Plus Product Data
Figure 1 A Typical Data Highway Plus Configuration
Data Highway Plus features: remote programming of any PLC-2, PLC-3, or PLC-5 on your network with Allen-Bradley 6200 Series Software direct connection to PLC-5s and Industrial Programming Terminals transparent connectivity with Data Highway, Data Highway II, and broadband networks token-passing protocol that provides efficient and reliable data transport You can use Data Highway Plus alone in smaller applications (generally less than 20 nodes) or with other industrial networks as part of a plant-wide Computer Integrated Manufacturing (CIM) facility. You can also use Data Highway Plus with a variety of networks, devices, and software packages. Use the table below to find the information you are interested in.
2
Page 3
Allen-Bradley Data Highway Plus Product Data
To Find Out About:
See Page:
The Cabling System: Trunkline and Droplines
3
Station Connectors and Terminators
4
Using Hardware interfaces to Connect: Asynchronous Devices
6
Personal Computers
7
PLC-2 Family Programmable Controllers
9
PLC-3 Family Programmable Controllers
10
PLC-5 Family Programmable Controllers
11
Industrial Programming Terminals
11
Connecting Data Highway Plus to: Data Highway
12
Data Highway II
14
Broadband Networks
17
Network Software You Can Use:
Data Highway Plus Cabling
6001-NET Series Communication Software
19
6001-F1E Standard Driver Software
19
6001-F3E Diagnostic Software
20
Remote Programming With 6200 Series Software
20
Ordering Information
21
Where to Read More
23
Specifications
24
Cabling provides the medium for transporting data between nodes. Your Data Highway Plus cabling system consists of the following parts (figure 2): a trunkline droplines station connectors and terminators
3
Page 4
Allen-Bradley Data Highway Plus Product Data
Figure 2 Components of a Data Highway Plus Cable System
Important: Do not put Data Highway or Data Highway II nodes directly on a Data Highway Plus trunkline.
Trunkline and Droplines The Data Highway Plus trunkline is the main channel of communication on the network. The trunkline is twinaxial cable with a maximum length of 10,000 feet. Droplines connect each node to the trunkline and are made of the same cable as the trunkline. A dropline can be up to 100 feet long. Allen-Bradley offers a 15-pin female connector kit (catalog no. 1771-XE) that you can use to connect the dropline to the node. When planning and installing your cable system: use only the cable specified in the Ordering Information section of this document isolate the cable from high amounts of electrical noise or high voltage avoid tension by providing some slack in the cable For more information on Data Highway Plus cabling, refer to the Data Highway Cable Assembly and Installation Manual (publication 1770-6.2.1).