Allen-Bradley Data Highway Plus Product Data
Station Connectors and Terminators A station connector (catalog no. 1770-SC) connects the dropline from a hardware interface to the trunkline. Station connectors include a 150-ohm terminating resistor to maintain the proper impedance on the network.
Using Interfaces to Connect to Data Highway Plus
Devices send and receive data over your Data Highway Plus network through hardware interfaces. The devices you can connect to your Data Highway Plus network and their required hardware interfaces are listed here: To Connect This Device:
Use This Interface
Desktop RS-232-C or RS-422-A Compatible
1770-KF2 Data Highway/Data Highway Plus Asynchronous Interface Module
Industrial RS-232-C or Compatible
1785-KE Communication Interface Module
T-50, T-35, and IBM PC/XT/AT Compatible
1784-KT Processor Communication Interface Module
T-45 Industrial Terminal
1784-KL Industrial Hardware Interface
PLC-2 Family Programmable Controller
1785-KA3 Data Highway Plus PLC-2 Family Communication Adapter Module
PLC-3 Family Programmable Controller
1775 -S5, -SR5 PLC3 Family I/O Scanner Communication Adapter Module
PLC-5 Family Programmable Controller
(built-in)
You connect these interfaces to droplines on your cable system (figure 3). The following sections discuss the hardware interfaces you use to connectvarious devices to your Data Highway Plus network.
5
Page 6
Allen-Bradley Data Highway Plus Product Data
Figure 3 A Typical Configuration of Data Highway Plus Interfaces
6
Page 7
Allen-Bradley Data Highway Plus Product Data
The 1770-KF2 Asynchronous Interface Module The 1771-KF2 Series B RS-232-C/RS-422-A device interface allows an intelligent asynchronous device to communicate over either of these networks: Data Highway Plus Data Highway To find out about the Data Highway network, refer to the Data Highway Local Area Network Overview (publication 1770-2.39). The 1770-KF2 Series B is a desktop module intended for use in an office environment. It supports baud rates from 110 to 9600. Typical applications include connecting host computers and personal computers to your Data Highway Plus network (figure 4). Figure 4 A Host Computer on a Data Highway Plus Configuration
Specifications for the 1770-KF2 are listed on page 24.
The 1785-KE Communication interface Module Use the 1785-KE to connect an asynchronous device to your Data Highway Plus network in plant floor applications (figure 5). You install the 1785-KE in a 1771 I/O chassis. The 1785-KE can connect RS-232-C devices (such as computers and graphics software) to your Data Highway Plus network using a baud rate of up to 19.2 Kb. You can also use the 1785-KE as a slave interface between a Data Highway Plus network and a SCADA master. For more information on SCADA applications, refer to the Allen-Bradley SCADA Applications Guide (publication CMGI-11.2).
7
Page 8
Allen-Bradley Data Highway Plus Product Data
Figure 5 Computer with Graphics Software on a Data Highway Plus Configuration
Specifications for the 1785-KE are listed on page 27.
The 1784-KT, -KL Hardware Interfaces The 1784-KT is a half-slot IBM PC/XT/AT-compatible card that allows you to connect personal computers directly to your Data Highway Plus network (figure 6). The 1784-KL is a 2-card set that allows you to connect an Allen-Bradley T45 Portable Programming Terminal directly to Data Highway Plus. Used with the 6200 Series software, both the 1784-KT and -KL allow direct communication between a computer and PLC-2s, PLC-3s, and PLC5s. You install the 1784-KT directly in your PC XT- or AT-bus. The 1784-KL is used only in the Allen-Bradley T45 Portable Programming Terminal. The 1784-KT, with Allen-Bradley’s 6001-F1E Standard Driver software, allows: user application programs to access Data Highway Plus, with a baud rate of 57.6 Kb. This provides greater throughput than was previously possible for user written applications. direct communication between a personal computer and PLC-2s, PLC-3s, and PLC-5s. See page 11 for more information on Allen-Bradley Industrial Programming Terminals and page 19 for information on Data Highway Plus software. For more information on the 1784-KT, refer to the Processor Communication Interface Module Installation Data Sheet (publication 1784-2.17). For information on the T45/1784-KL refer to the T45 User’s Manual (publication 1784-6.5.7).
8
Page 9
Allen-Bradley Data Highway Plus Product Data
Figure 6 A Personal Computer with 1784-KT on a Data Highway Plus Configuration
Specifications for the 1784-KL, -KL are listed on page 25.
The 1784-KA3 PLC-2 Family Adapter Module You can connect a PLC-2 family programmable controller to your Data Highway Plus network using the 1784-KA3 interface mounted in a Bulletin 1771 I/O chassis (figure 7). For more information on the 1785-KA3, refer to the 1785-KA3 User’s Manual (publication 1785-6.5.3). Figure 7 A PLC-2 Family Programmable Controller on a Data Highway Plus Configuration
Specifications for the 1785-KA3 are listed on page 26.
9
Page 10
Allen-Bradley Data Highway Plus Product Data
The 1775-S5, -SR5 PLC-3 Family I/O Scanner Module You connect a PLC-3 family programmable controller to your Data Highway Plus network with a 1775-S5, -SR5 I/O Scanner Module (figure 8). Figure 8 A PLC-3 Family Programmable Controller on a Data Highway Plus Configuration
The 1775-S5, -SR5 provides four I/O channels for a maximum of 4,096 I/O points. You can use the 1775-S5, -SR5 as a Data Highway Plus (or Data Highway) interface, leaving three I/O channels for a maximum of 3,072 I/O points. This allows you to access both remote I/O communications and Data Highway Plus communications with one 1775-S5 or -SR5 interface. The 1775-S5 requires a PLC-3 chassis or expander chassis for operation. The 1775-SR5 requires a slot in a PLC-3/10. See the section entitled Ordering Information in this publication for the appropriate catalog number. To find out more, refer to the I/O Scanner-Communication Adapter Module Product Data (publication 1775-2.24). Specifications for the 1775-S5, -SR5 are listed on page 25.
10
Page 11
Allen-Bradley Data Highway Plus Product Data
Connecting a PLC-5 Family Programmable Controller The PLC-5 family of programmable controllers has a built-in interface for the Data Highway Plus network. No additional hardware is required to connect your PLC-5 to a Data Highway Plus dropline (figure 9). Figure 9 A PLC-5 Family Programmable Controller on a Data Highway Plus Configuration
Connecting Allen-Bradley Industrial Programming Terminals The Allen-Bradley Programming Terminals are IBM PC/XT/AT based computers you can use to program PLC-2, PLC-3, and PLC-5 family programmable controllers (figure 10). You can connect them: to the programmable controller or interface directly to a Data Highway Plus network Figure 10 Programming Terminals on a Data Highway Plus Configuration
11