The text of a manual ยท part 3 of 5
Allen-Bradley Data Highway Plus Local Area Network Product Data: Connecting Data Highway Plus to Other Networks
Pages 12 to 18 of 28, from Allen-Bradley Data Highway Plus Local Area Network Product Data
The original document is the PDF (424 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1785-KE
Page 12
Allen-Bradley Data Highway Plus Product Data
There are three programming terminals available: 1784-T45 lap-top terminal 1784-T35 rack-mounted terminal 1784-T50 workstation All are available with 20 megabyte hard disk drives and run the 6200 Series software to perform online data manipulation, I/O forcing, creation of contact histograms, and online program testing and editing.
Connecting Data Highway Plus to Other Networks
The networks you can connect to Data Highway Plus and their corresponding hardware interfaces are listed below. To Connect Data Highway Plus to:
Use This Interface:
Data Highway
1785-KA Communication Adapter Module
Data Highway Il
1779-KP5 Interface Module
Broadband Cable Trunkline
1771-KRF Broadband Communication Interface
The following sections discuss the above hardware interfaces.
The 1785-KA Communication Adapter Module You can connect one or more Data Highway Plus networks to an existing Data Highway network using an Allen-Bradley 1785-KA interface (figure 11). You can also use the 1785-KA to interconnect several Data Highway Plus subnetworks via a Data Highway trunkline. You mount the 1785-KA in a Bulletin 1771 I/O chassis. Specifications for the 1785-KA are listed on page 25.
12
Page 13
Allen-Bradley Data Highway Plus Product Data
Figure 11 A Data Highway/Data Highway Plus Configuration
Important: A computer connected to Data Highway Plus through a RS-232-C interface module can access nodes on the local Data Highway Plus network. It cannot access nodes on Data Highway or on a remote Data Highway Plus (through the 1785-KA). A PLC on Data Highway Plus can access nodes on the Data Highway and remote Data Highway Plus. Also, Data Highway nodes cannot access a computer that is connected to Data Highway Plus through a RS-232-C interface module. However, Data Highway nodes can access a computer connected to Data Highway Plus if the computer is using the 1784-KT with version 1.3 or later of the 6001-F1E Standard Driver Software.
13
Page 14
Allen-Bradley Data Highway Plus Product Data
A computer that is connected to Data Highway Plus and is using the 1784-KT with version 1.3 or later of the 6001-F1E Standard Driver Software can access nodes on Data Highway or a remote Data Highway Plus (through the 1785-KA). To find out about the Data Highway network and what it can do for you, refer to the Data Highway Local Area Network Overview (publication 1770-2.39).
The 1779-KP5 Interface Module You can connect one or more Data Highway Plus networks to your Data Highway II network using an Allen-Bradley 1779-KP5 interface. This is also how you attach PLC-5 family controllers to a Data Highway II network. You can also use the 1779-KP5 to connect a Data Highway II network as a high-speed communications link between several Data Highway Plus subnetworks (figure 12). The 1779-KP5 is a stand-alone module and is available as a redundant cable system (catalog no. 1779-KP5R). Important: You can send commands to Data Highway II from Data Highway Plus if the Data Highway Plus node addresses are 002 through 020 (octal). You may assign other valid addresses on your Data Highway Plus network, but these nodes will be unable to initiate messages to Data Highway II devices.
14
Page 15
Allen-Bradley Data Highway Plus Product Data
Figure 12 Data Highway Plus Networks connected by Data Highway II
Specifications for the 1779-KP5 are listed on page 26. Important: A computer connected to Data Highway Plus through a RS-232-C interface module can access nodes on the local Data Highway Plus network. It cannot access nodes on Data Highway or on a remote Data Highway Plus (through the 1785-KA). A PLC on Data Highway Plus can access nodes on the Data Highway and remote Data Highway Plus.
15
Page 16
Allen-Bradley Data Highway Plus Product Data
Also, Data Highway nodes cannot access a computer that is connected to Data Highway Plus through a RS-232-C interface module. However, Data Highway nodes can access a computer connected to Data Highway Plus if the computer is using the 1784-KT with version 1.3 or later of the 6001-F1E Standard Driver Software. A computer that is connected to Data Highway Plus and is using the 1784-KT with version 1.3 or later of the 6001-F1E Standard Driver Software can access nodes on Data Highway or a remote Data Highway Plus (through the 1785-KA). To find out more about the Data Highway II network and what it can do for you, refer to the Data Highway II Local Area Network Overview (publication 1779-2.10).
16
Page 17
Allen-Bradley Data Highway Plus Product Data
The 1771-KRF Broadband Communication Interface You can connect one or more Data Highway Plus networks to a broadband cable network using the Allen-Bradley 1771-KRF interface module (figure 13). Figure 13 A Typical Broadband Data Highway Plus Configuration
The KRF receives input signals from a Data Highway Plus module and transmits them on a broadband cable. This allows you to transmit the Data Highway Plus protocol directly over the broadband, creating a Data Highway Plus link on a broadband cable instead of on the standard twinaxial baseband cable. The 1771-KRF requires a single slot in an I/O rack. You can use a KRF module in conjunction with a 1785-KA Data Highway/Data Highway Plus communication adapter module to connect a single Data Highway Plus baseband network to a Data Highway broadband network.
17
Page 18
Allen-Bradley Data Highway Plus Product Data
You can also use the 1771-KRF with a 1785-KA to connect Data Highway Plus sub-networks to a broadband Data Highway trunkline (figure 14). Figure 14 Baseband Data Highway Plus Networks Connected to a Broadband Data Highway Trunkline
Specifications for the 1771-KRF are listed on page 24. If you connect individual Data Highway Plus stations to a broadband cable network, you must have one KRF module for each station. The KRF is frequency agile over 18 sub-channel pairs. This allows up to 18 Data Highway Plus links to operate on a single broadband cable system.
18