Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of A-B Station Module Installation Instructions

Manual · Allen-Bradley

A-B Station Module Installation Instructions

Manual10 pagesPDF 267 KB

Installation instructions for the Allen-Bradley A-B Station Module, which attaches to the side connector of a PLC-5 processor.

What this file really is

The old site listed this file as “Tech Manual” for the Allen-Bradley 1785-L20B and 1785-L40B. The file is the installation instructions for the A-B Station Module, an add-on for PLC-5 processors; it does not name the 1785-L20B or 1785-L40B.

Download the PDF267 KB

Filed with · 2 models

Also filed with these models on the old site

Summary

What is in it

Allen-Bradley installation instructions for the A-B Station Module, which connects to the side connector of a PLC-5 programmable controller and installs with it in a 1771 Universal I/O chassis. They cover sizing the power supply, ESD handling, the items needed, installing and replacing the lithium battery, setting the COMM1 switches, mounting the module on the processor and in the chassis, the LED indicators, specifications and which PLC-5 processors are compatible.

Its parts

  1. Select A Power Supply
  2. Handle the Equipment Properly
  3. Before Installing the A-B Station Module
  4. Install the Battery
  5. Install the A-B Station Module
  6. Apply Power to the I/O Chassis
  7. Interpret LED Indicators
  8. Product Specifications
  9. PLC-5 Processor Compatibility

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Installation instructions (publication 1785-2.37, June 1994) for the A-B station module, which mounts on the side connector of a PLC-5 processor in a 1771 I/O chassis and adds a Foxboro I/A Nodebus port. It covers the A-B station module only, not the processor itself. It walks through power supply sizing, the battery, mounting, the LED indicators and the specifications.

Device
A-B station module, connected to the side connector of a PLC-5 processor in an Allen-Bradley 1771 Universal I/O Chassis p. 10
Compatible processors
All PLC-5 processors with a coprocessor expansion port, except PLC-5/40 and -5/60 series A and PLC-5/40 and -5/60 series B, revision B p. 10
Backplane current
2.50 Amps at +5 Vdc p. 10
COMM0 port
RS-232C, 9-pin p. 10
COMM1 port
Foxboro I/A protocol, DNBI or DNBX adapter; switch assembly set for RS-423 p. 6, 10
Nodebus cable length
Maximum 150 feet with a DNBI or 400 feet with a DNBX p. 10
COMM1 switch settings
RS-423: switches 1, 2, 3 and 6 on; 4, 5 and 7 off p. 6
Battery
3.0 volt lithium, supplied with the module; replacement 1770-XYC, the same battery as the PLC-5 processor p. 3, 5
Battery life
1 year p. 10
Operating temperature
0 - 60° C (32 - 140° F) p. 10
Storage and humidity
Storage -40 - 85° C (-40 - 185° F); relative humidity 5 - 95% without condensation p. 10
Indicators
CPU, COMM0, COMM1 and BATT LEDs p. 9
Power-up check
BATT LED blinks red four times then goes off; CPU LED blinks green four times then stays green p. 9
Publication
1785-2.37, June 1994 p. 10

What this manual walks you through

  • Sizing the chassis power supply, adding 2.5 A for the module p. 2
  • Handling the module without electrostatic damage p. 2
  • Installing and replacing the lithium battery p. 3, 4, 5
  • Disposing of the battery p. 5
  • Setting the COMM1 switch assembly for RS-423 p. 6
  • Joining the module to the PLC-5 processor with the connector header p. 6, 7
  • Installing and removing the module and processor in the 1771 I/O chassis p. 8
  • Reading the LED indicators after power-up p. 9

Good to know

  • An external power supply and a slot-based power supply cannot power the same chassis. p. 2
  • Use only the 3.0 volt battery supplied with the module; do not short, recharge, heat above 100° C or disassemble it. p. 3
  • Replace the battery while the module is powered; removing it with power off can lose the programs. p. 5
  • Turn off power to the I/O chassis before installing or removing the module and processor unit. p. 8
  • Avoid bending pins when fitting the connector header into the processor and the module onto the header. p. 7

Questions this manual answers

What battery does the A-B station module use?

A 3.0 volt lithium battery is supplied with it; replacements are 1770-XYC, the same battery the PLC-5 processor uses. p. 3, 5

Which PLC-5 processors work with the A-B station module?

All PLC-5 processors with a coprocessor expansion port, except PLC-5/40 and -5/60 series A and PLC-5/40 and -5/60 series B, revision B. p. 10

What does a red BATT LED on the A-B station module mean?

The battery needs replacing, or no battery is installed. p. 5, 9

How much backplane current does the A-B station module draw?

2.50 Amps at +5 Vdc, which is added to the I/O modules and the PLC-5 processor when sizing the power supply. p. 2, 10

How long can the Nodebus cable be?

Up to 150 feet with a DNBI adapter or 400 feet with a DNBX. p. 10

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1785-2.37, A-B Station Module, Installation Instructions1
  2. Select A Power Supply2
  3. Handle the Equipment Properly2
  4. Before Installing the A-B Station Module3
  5. Install the Battery3
  6. Install the A-B Station Module6
  7. Apply Power to the I/O Chassis9
  8. Interpret LED Indicators9
  9. Product Specifications10
  10. PLC 5 Processor Compatibility10
  11. Obtaining Allen Bradley Publications10
  12. Back Cover10

From the PDF’s own bookmarks.

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10

The file

Revision and size

RevisionPublication 1785-2.37, June 1994
PublisherAllen-Bradley
Pages10
PDF267 KB
TextText from the PDF itself.

The first pages · 3 of 10

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 10
Page 2
Page 2of 10
Page 3
Page 3of 10

More documents · 1

For the same models