Enhanced and Ethernet PLC-5 Programmable Controllers User Manual: Appendix D - Instruction Set Quick Reference, pages 331 to 338
Pages 331 to 338 of 388, from Enhanced and Ethernet PLC-5 Programmable Controllers User Manual
The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1785-L20B and Allen-Bradley 1785-L40B
Page 331
Instruction Set Quick Reference
Category
Arithmetic
Code Title
Execution Time (µs) Floating Point
True
False
True
False
Words of Memory (1)
ADD add
6.1
1.4
14.9
1.4
4-7
SUB subtract
6.2
1.4
15.6
1.4
4-7
MUL multiply
9.9
1.4
18.2
1.4
4-7
DIV divides
12.2
1.4
23.4
1.4
4-7
SQR square root
9.9
1.3
35.6
1.3
3-5
NEG negate
4.8
1.3
6.0
1.3
3-5
CLR clear
3.4
1.1
3.9
1.1
2-3
AVE average file
152+E25.8
30
162+E22.9
36
4-7
STD standard deviation 262+E92.5
34
295+E85.5
34
4-7
TOD convert to BCD
7.8
1.3
3-5
FRD convert from BCD
8.1
1.3
3-5
RAD radian
57.4
1.4
50.1
1.4
3-5
DEG degree
55.9
1.4
50.7
1.4
3-5
SIN sine
414
1.4
3-5
COS cosine
404
1.4
3-5
TAN tangent
504
1.4
3-5
ASN inverse sine
426
1.4
3-5
ACS inverse cosine
436
1.4
3-5
ATN inverse tangent
375
1.4
3-5
LN natural log
409
1.4
403
1.4
3-5
LOG log
411
1.4
403
1.4
3-5
XPY
X to the power of Y 897
1.5
897
1.5
4-7
SRT sort file (5/11, -5/20) (-5/30, -5/40, -5/60, -5/80)
(1)
Execution Time (µs) Integer
D-31
3-5 276 + 12[E**1.34]
227
278 + 16[E**1.35] 227
189
230 + 33[E**1.35] 189
224 + 25[E**1.34]
Use the larger number for addresses beyond 2048 words in the controller’s data table.
E = number of elements acted on per scan SRT true is only an approximation. Actual time depends on the randomness of the numbers.
Publication 1785-UM012D-EN-P - July 2005
Page 332
D-32
Instruction Set Quick Reference
File, Program Control, and ASCII Instructions Category
Code
Title
Time (µs) Integer
Time (µs) Floating Point
True
False
True
Words of Memory(1) False
File Arithmetic and Logic
FAL all
11 + (S[2.3 + i])E
6.16 + Wi[0.16] 11 + (Σ[2.3 + i])E
6.16 + Wi[0.16] 3-5 +Wi
File Search and Compare
FSC all
11 + (S[2.3 + i])E
6.16 + Wi[0.16] 11 + (Σ[2.3 + i])E
6.16 + Wi[0.16] 3-5 +Wi
File
COP copy
16.2+E[0.72]
1.4
17.8+E[1.44]
1.4
4-6 counter, timer, and control
15.7+E[2.16]
1.4 fill
15.7+E[0.64]
1.5
18.1+E[0.80]
1.5
4-6 counter, timer, and control
15.1+E[1.60]
1.5
BSL bit shift left
10.6+B[0.025] 5.2
4-7
BSR bit shift right
11.1 + B[0.025]
5.2
4-7
FFL
FIFO load
8.9
3.8
4-7
FFU
FIFO unload
10.0+E[0.43]
3.8
4-7
LFL
LIFO load
9.1
3.7
4-7
LFU
LIFO unload
10.6
3.8
4-7
FBC
0 mismatch
15.4 + B[0.055]
2.9
6-11
1 mismatch
22.4 + B[0.055]
2.9
2 mismatches
29.9+ B[0.055] 2.9
0 mismatch
15.4 + B[0.055]
2.9
1 mismatch
24.5 + B[0.055]
2.9
2 mismatches
34.2 + B[0.055]
2.9 data transitional
5.3
5.3
FLL
Shift Register
Diagnostic
DDT
DTR (1)
Use the larger number for addresses beyond 2048 words in the controller’s data table.
i = execution time of each instruction (e.g., ADD, SUB, etc.) used within the FAL or the FSC expression E = number of elements acted on per scan B = number of bits acted on per scan Wi = number of words used by the instruction (e.g., ADD, SUB, etc.) within the FAL or FSC expression FAL or FSC instructions are calculated with short direct addressing
Publication 1785-UM012D-EN-P - July 2005
6-11
4-7
Page 333
Instruction Set Quick Reference
Category
Sequencer
Code
Title
Time (µs) Integer
Time (µs) Floating Point
True
False
True
Words of Memory(1) False
SQI sequencer input
7.9
1.3
5-9
SQL sequencer load
7.9
3.5
4-7
SQO sequencer output
9.7
3.7
5-9
Immediate I/O(2) IIN immediate input
1.1
2
1.1
2
• PLC-5/11, -5/20, and -5/20E • PLC5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, and -5/80, -5/80E
IOT
Zone Control
MCR
Program Control JMP JSR(3) /RET
D-33
• 357 • 307 immediate output • PLC-5/11, -5/20, and -5/20E • PLC5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
• 361 • 301 master control
0.16
0.16
1 jump
8.9+(file# - 2) 1.4 * 0.96
2 jump to subroutine /return
3+paramete rs/JSR, 0 parameters
12.3
1.0 not applicable, 1 parameter
16.1
1.0
17.3, increase/ parameter
3.8 not applicable 5.0
SBR not applicable 1+paramete rs/RET 1.0 not applicable 1+ parameters
(1)
Use the larger number for addresses beyond 2048 words in the controller’s data table.
(2)
Timing for immediate I/O instructions is the time for the instruction to queue-up for processing.
(3)
Calculate execution times as follows: (time) + (quantity of additional parameters)(time/parameter). For example: if you are passing 3 integer parameters in a JSR within a PLC-5/11 controller, the execution time = 16.1 + (2)(3.8) = 23.7 ms
Publication 1785-UM012D-EN-P - July 2005
Page 334
D-34
Instruction Set Quick Reference
Category
Code
Title
Time (µs) Integer
Time (µs) Floating Point
True
False 0.16
True
Words of Memory(1) False
Program Control LBL label
0.16
END end negligible
TND temporary end
1
EOT end of transition
1
AFI always false
0.16
0.16
1
ONS one shot
3.0
3.0
2-3
OSR one shot rising
6.2
6.0
4-6
OSF one shot falling
6.2
5.8
4-6
FOR/ NXT for next loop
8.1+ L[15.9]+ (file# - 2) * 0.96
5.3 + N[0.75]
FOR 5-9 NXT 2
BRK break
11.3 + N[0.75] 0.9
UID user interrupt disable (PLC-5/11, -5/20, 175 -5/30, -5/40, -5/60, and -5/80 controllers) 119
1.0
1
UIE user interrupt enable 170 (PLC-5/11, -5/20, -5/30, -5/40, -5/60, and -5/80 controllers) 100
1.0
1
(1)
1
Use the larger number for addresses beyond 2048 words in the controller’s data table.
L = number of FOR/NXT loops N = number of words in memory between FOR/NXT or BRK/NXT
Publication 1785-UM012D-EN-P - July 2005
2
1
Page 335
Instruction Set Quick Reference
Category
Code
Title
Time (µs) Integer True
Process Control PID
False
True
Words of Memory(1) False
PID loop control
5-9
Independent
Gains
Time (µs) Floating Point
D-35
3.0
1120
58
• PLC-5/11, -5/20, • 462 -5/20E • 655 • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L -5/80, -5/80E
ISA • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
1180 • 560 • 895
Manual
Modes
• PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
1150 • 372 • 420
Set Output • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E Cascade
ASCII (2)
ABL
1130 • 380 • 440
Slave
1530
Master
1080 test buffer for line • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
3-5 • 316 • 388
• 214 • 150
(1)
Use the larger number for addresses beyond 2048 words in the controller’s data table.
(2)
Timing for ASCII instructions is the time for the instruction to queue-up for processing in channel 0.
C = number of ASCII characters
Publication 1785-UM012D-EN-P - July 2005
Page 336
D-36
Instruction Set Quick Reference
Category
Code
Title
Time (µs) Integer True
ACB
AEX
(1)
• 214 • 150
1.4
3-5
1.9
4-7
1.9
5-9
• 237 + C[2.6] • 179 + C[5.5]
• 226 + C[1.1] • 159 + C[2.2] set or reset lines • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
5-9 • 318 • 526
• 213 • 157
Use the larger number for addresses beyond 2048 words in the controller’s data table.
Publication 1785-UM012D-EN-P - July 2005
False
• 220 + C[11] • 140 + C[21.4] string extract • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
AHL¡
• 316 • 389 string concatenate • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
True
Words of Memory(1)
3-5 string to integer • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
ACN
False no. of characters in buffer • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
ACI
Time (µs) Floating Point
Page 337
Instruction Set Quick Reference
Category
Code
Title
Time (µs) Integer True
ASCII(2)
AIC integer to string • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
ARD
False 3-5
4-7 • 315 • 380
• 214 • 149
4-7 • 316 • 388
• 214 • 151
1.9
5-9
• 222 + C[1.7] • 151 + C[3.0] string compare • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
True
Words of Memory(1)
• 260 • 270 string search • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
ASR
1.4 read line • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
ASC
False read characters • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
ARL
Time (µs) Floating Point
D-37
3-5 • 234 + C[1.3] • 202 • 169 + C[2.4] • 119
(1)
Use the larger number for addresses beyond 2048 words in the controller’s data table.
(2)
Timing for ASCII instructions is the time for the instruction to queue-up for processing in channel 0.
C = number of ASCII characters
Publication 1785-UM012D-EN-P - July 2005
Page 338
D-38
Instruction Set Quick Reference
Category
Code
Title
Time (µs) Integer True
ASCII(2)
AWA
False write with append • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
AWT
Time (µs) Floating Point
• 319 • 345
• 215 • 154
4-7 • 318 • 344
• 215 • 151
(1)
Use the larger number for addresses beyond 2048 words in the controller’s data table.
(2)
Timing for ASCII instructions is the time for the instruction to queue-up for processing in channel 0.
C = number of ASCII characters
Publication 1785-UM012D-EN-P - July 2005
False 4-7 write • PLC-5/11, -5/20, and -5/20E • PLC-5/30, -5/40, -5/40E, -5/40L -5/60, -5/60L, -5/80, and -5/80E
True