Enhanced and Ethernet PLC-5 Programmable Controllers User Manual: Appendix E - Switch Setting Reference

Pages 339 to 348 of 388, from Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1785-L20B and Allen-Bradley 1785-L40B

Page 339

Appendix

E

Switch Setting Reference

Using This Chapter For this Switch Setting

1

Go to Page

Enhanced and Ethernet PLC-5 switch 1 for defining the controller’s DH+ address

E-2

Enhanced and Ethernet PLC-5 switch 2 for defining the controller’s serial port electrical interface

E-3

I/O chassis containing a PLC-5 controller

E-4

I/O chassis containing a 1771-ASB, remote I/O adapter module

E-5

I/O chassis configuration plug for defining an external or slot power supply

E-6

1771-ASB not using complementary I/O

E-7

1771-ALX adapter module

E-9

Publication 1785-UM012D-EN-P - July 2005

Page 340

E-2

Switch Setting Reference

Controller Switches

Switch 1

Side View of PLC-5/11, -5/20, -5/26, -5/20E controllers Switch Assembly SW1

Side View of PLC-5/30, -5/40, -5/46, -5/40L, -5/60, -5/60L, -5/80, -5/86, -5/40E, and -5/80E controllers Switch Assembly SW1 toggle pushed down on

1 2 3 4 5 6 7

1 2 3 4 5 6 7 toggle pushed up off

To Select DH+ Baud Rate for Channel 1A: DH+ address DH+ baud rate

Switch

DH+ Station Number

1

2

3

4

5

0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17 20 21 22 23 24 25 26 27 30 31 32 33 34 35 36 37 on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on on off off on on off off on on off off on on off off on on off off on on off off on on off off on on off off on on on on off off off off on on on on off off off off on on on on off off off off on on on on off off off off on on on on on on on on off off off off off off off off on on on on on on on on off off off off off off off off on on on on on on on on on on on on on on on on off off off off off off off off off off off off off off off off

Publication 1785-UM012D-EN-P - July 2005

Set sSitch: To: 1 through 6 (See below) 7 on (down)57.6 kbps off (up)230.4 kbps

Switch

6

DH+ Station Number

1

2

3

4

5

6 on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on

40 41 42 43 44 45 46 47 50 51 52 53 54 55 56 57 60 61 62 63 64 65 66 67 70 71 72 73 74 75 76 77 on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on on off off on on off off on on off off on on off off on on off off on on off off on on off off on on off off on on on on off off off off on on on on off off off off on on on on off off off off on on on on off off off off on on on on on on on on off off off off off off off off on on on on on on on on off off off off off off off off on on on on on on on on on on on on on on on on off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off

Page 341

Switch Setting Reference

E-3

Switch 2 Bottom View of PLC-5/11, -5/20, -5/26, and -5/20E processors Switch Assembly SW2

Bottom View of PLC-5/30, -5/40, -5/46 -5/40L, -5/60, -5/60L, -5/80, -5/86, -5/40E, and -5/80E processors Switch Assembly SW2

Front of Processor

Front of Processor

Side View toggle pushed toward bottom on toggle pushed toward top off

1 2 3 4 5 6 7 8 9 10

12 3 4 5 6 7 8 9 10

To Specify:

Set Switches: 1

2

3

4

5

6

7

8

9

10

RS-232C on on on off off on on off on off

RS-422A off off on off off off off off on off

RS-423 on on on off off on off off on off

Publication 1785-UM012D-EN-P - July 2005

Page 342

E-4

Switch Setting Reference

I/O Chassis Backplane

PLC-5 Controller in the I/O Chassis

Switch

Last State

1 on

Outputs of this I/O chassis remain in their last state when a hardware failure occurs. 1 off

Outputs of this I/O chassis are turned off when a hardware failure occurs. 1

A lways O ff

Switches Addressing

4

5 off off

2 - slot off on

1 - slot on off

1/2 - slot on on

Not allowed

Switches Memory Module Transfer

6

7 off off memory module transfer to processor memory at powerup. 2 3 on on memory module transfers to processor memory if processor memory not valid.

on off memory module does not transfer to processor memory.

Switch

Processor Memory Protection

8 off

Processor memory protection disabled.

on

Processor memory protection enabled. 4

Pressed in at top ON (closed) Pressed in at bottom OFF (open)

1 Regardless of this switch setting, outputs are turned off when any of the following occurs: processor detects a major fault an I/O chassis backplane fault occurs you select program or test mode you set a status file bit to reset a local rack 2 If a memory module is not installed and processor memory is valid, the processor’s PROC LED indicator blinks, and the processor sets S:11/9 in the major fault status word. Power down the processor chassis and either install the correct memory module or set switch 6 ON. 3 If the processor’s keyswitch is set in REMote, the processor enters remote RUN after it powers up and has its memory updated by the memory module. 4 You cannot clear processor memory when this switch is on.

19309

Publication 1785-UM012D-EN-P - July 2005

Page 343

Switch Setting Reference

E-5

1771-ASB Remote I/O Adapter or 1771-ALX Extended-Local I/O Adapter

Switch Last State 1

Always Off on

Outputs of this I/O chassis remain in their last state when a communication fault is detected by this I/O adapter. 1 off

Outputs of this I/O chassis are turned off when a communication fault is detected by this I/O adapter.

Switch Processor Restart Lockout

2 on

Processor can restart the I/O chassis after a communication fault. 2 off

You must manually restart the I/O chassis with a switch wired to the 1771-AS or -ASB.

Always Off

Switches Addressing

5

6 off off

2-slot on off

1-slot 3 off on

1/2-slot 3 on on

Not allowed

Pressed in at top ON (closed) Pressed in at bottom OFF (open) 19308

Publication 1785-UM012D-EN-P - July 2005

Page 344

E-6

Switch Setting Reference

ATTENTION

If you set this switch to the ON position, when a communication fault is detected, outputs connected to this chassis remain in their last state to allow machine motion to continue. We recommend that you set switch 1 to the OFF position to de-energize outputs wired to this chassis when a fault is detected. Also, if outputs are controlled by inputs in a different rack and a remote I/O rack fault occurs (in the inputs rack), the inputs are left in their last non-faulted state. The outputs may not be properly controlled and potential personnel and machine damage may result. If you want your inputs to be anything other than their last non-faulted state, then you need to program a fault routine. Set this switch to ON if you plan to use I/O rack auto-configuration. The 1771-ASB series A adapter does not support 1/2-slot addressing.

I/O Chassis Configuration Plug

1. Locate the chassis configuration plug (between the first two left-most slots of the chassis). 2. Set the I/O chassis configuration plug. The default setting is N (not using a power supply module in the chassis).

Y N

USING POWER SUPPLY MODULE IN THE CHASSIS? Y N

Set Y when you install a power supply module in the chassis.

Publication 1785-UM012D-EN-P - July 2005

Y N

Set N when you use an external power supply.

Important: You cannot power a single I/O chassis with both a power supply module and an external power supply.

17075

Page 345

Switch Setting Reference

E-7

Remote I/O Adapter Module (1771-ASB Series C and D) without Complementary I/O Pressed in at top ON (closed) Pressed in at bottom OFF (open)

S W -1 O 1 N O F F

2

3

I/O Rack Number (see next page)

4

5

6

7

8

S W -2 O 1 N O F F

2

3

4

5

6

First I/O Group Number (see below) Link Response: ON*for series B emulation OFF*for unrestricted

Switch

Communication Rate

1

2

ON

OFF

57.6 Kbps

OFF

OFF

115.2 Kbps

OFF

ON

230.4 Kbps

ON

ON

Not used

First I/O Group Number:

Scan: ON*for all but last 4 slots OFF*for all slots

7

8

0 on on

2 on off

4 off on

6 off off

Publication 1785-UM012D-EN-P - July 2005

Page 346

E-8

Switch Setting Reference

(1771-ASB Series C and D) I/O Rack Number without Complementary I/O Rack

Publication 1785-UM012D-EN-P - July 2005

1

2

3

4

5

6

01 on on on on on off

02 on on on on off on

03 on on on on off off

04 on on on off on on

05 on on on off on off

06 on on on off off on

07 on on on off off off

10 on on off on on on

11 on on off on on off

12 on on off on off on

13 on on off on off off

14 on on off off on on

15 on on off off on off

16 on on off off off on

17 on on off off off off

20 on off on on on on

21 on off on on on off

22 on off on on off on

23 on off on on off off

24 on off on off on on

25 on off on off on off

26 on off on off off on

27 on off on off off off

Page 347

Switch Setting Reference

Extended-Local I/O Adapter Module

E-9

(1771-ALX) Switch SW1

SW-1 1 2 3 4 5 6 7 8

SW-2 Not Used OPEN

First I/O Group Number I/O Rack Number

Rack:

1

2

3

4

5

6

01 on on on on on off

02 on on on on off on

03 on on on on off off

04 on on on off on on

05 on on on off on off

06 on on on off off on

07 on on on off off off

10 on on off on on on

11 on on off on on off

12 on on off on off on

13 on on off on off off

14 on on off off on on

15 on on off off on off

16 on on off off off on

17 on on off off off off

20 on off on on on on

21 on off on on on off

22 on off on on off on

23 on off on on off off

24 on off on off on on

25 on off on off on off

26 on off on off off on

27 on off on off off off

Publication 1785-UM012D-EN-P - July 2005

Page 348

E-10

Switch Setting Reference

(1771-ALX) Configuration Plug

1. Lay the module on its right side. The configuration plugs are visible on the lower rear of the module. 2. Set the configuration plug as shown below according to your application.

Configuration Plug Do not place a jumper on this set of pins.

17341

If You are Using

Publication 1785-UM012D-EN-P - July 2005

But Not

Set Configuration Plug

32-point I/O modules and 1771-IX or 1771-IY any address method on the 2 lower pins

1771-IX and 1771-IY modules and any addressing method on the 2 upper pins

32-point I/O modules