Troubleshooting
Using This Chapter For Information About Troubleshooting:
1
Go to Page:
PLC-5 controller
F-2
Remote I/O system
F-6
Extended-local I/O system
F-9
Unexpected PLC-5 controller operation when entering run mode
F-10
Publication 1785-UM012D-EN-P - July 2005
Page 350
F-2
Troubleshooting
PLC-5 Controller
BATT PROG R E M RUN
General Problems
Indicator
Color
Description
Probable Cause
Recommended Action
PROC
Green (steady)
Controller is in run mode and fully operational
Normal operation
No action required
Green (blinking)
Controller memory is being transferred to EEPROM
Normal operation
No action required
Red (blinking)
Major fault
• RSLogix 5 download in progress • Run-time error
During RSLogix 5 download, this is normal operation - wait for download to complete.
PROC FORCE COMM
If not during RSLogix 5 download: • Check major fault bit in status file (S:11) for error definition • Clear fault, correct problem, and return to run mode
Alternating Red and Green
Controller in FLASH-memory programming mode
Normal operation if controller's FLASH memory is being reprogrammed
No action required - allow flash update to complete
Red
Power cycle with problem battery
Battery is low, disconnected or not installed
Properly replace or install battery (see Chapter 1 for more information)
Fault with memory loss
New controller
Use programming software to clear and initialize memory
(steady) Red (steady)
Invalid ControlNet Verify that ControlNet address network address switch is not set to 0 Controller has failed internal diagnostics
Off
Publication 1785-UM012D-EN-P - July 2005
Controller is in program load or test mode or is not receiving power
Install battery (to preserve failure diagnostics), then power down, reseat controller and power up; then reload your program. If you are unable to reload your program, replace the controller. If you are able to reload your program and fault persists, contact Technical Support at 440.646.6800 to diagnose the problem. Check power supply and connections
Page 351
Troubleshooting
Indicator
Color
Description
Probable Cause
Recommended Action
FORCE
Amber (steady)
SFC and/or I/O forces enabled
Normal operation
No action required
Amber (blinking)
SFC and/or I/O forces present but not enabled
Off
SFC and/or I/O forces not present
Off
No transmission on channel 0
Normal operation if channel is not being used
Green (blinking)
Transmission on channel 0
Normal operation if channel is being used
COMM
F-3
Publication 1785-UM012D-EN-P - July 2005
Page 352
F-4
Troubleshooting
Controller Communication Channel Troubleshooting Indicator Color
Channel Mode
A or B
Remote I/O Scanner Active Remote I/O link, all adapter modules are present and not faulted
Green (steady)
Description
Probable Cause Recommended Action Normal operation No action required
Remote I/O Adapter Communicating with scanner DH+ Green (blinking rapidly or slowly)
Remote I/O Scanner At least one adapter is faulted or has failed
DH+ Red (steady)
Controller is transmitting or receiving on DH+ link • Power off at remote rack • Cable broken
• Restore power to the rack • Repair cable
Hardware error
Turn power off, then on
No other nodes on network
Remote I/O Scanner Hardware fault Remote I/O Adapter DH+
Check that the software configurations match the hardware set-up Replace the controller.
Red (blinking rapidly or slowly)
Remote I/O Scanner All adapters faulted
DH+ Off
Publication 1785-UM012D-EN-P - July 2005
• Cable not connected or broken • Power off at remote racks
Bad communication on DH+ Duplicate node detected
Remote I/O Scanner Channel offline Remote I/O Adapter DH+
Channel is not being used
• Repair cable
• Restore power to racks
Correct station address Place channel online if needed
Page 353
Troubleshooting
F-5
Extended-Local I/O Troubleshooting Indicator Color
Channel Mode
Description
2
Extended local I/O Scanner active extended-local I/O normal operation link, all adapter modules are present and not faulted no action required at least one adapter is faulted or has failed
• restore power to the rack green (steady)
PLC-5/40L and -5/60L processors only BATT PROG green (blinking rapidly or slowly)
PROC
R E M
Probable Cause Recommended Action
• power off at extended-local I/O rack • communication fault
FORCE
• restart adapters using the controller restart lockout pushbutton • repair cable
• cable broken
RUN
COMM red (steady)
red (blinking rapidly or slowly)
Extended local I/O Scanner off hardware fault hardware error
Turn power off, then on. Check that the software configurations match the hardware set-up. Replace the controller.
all adapters faulted
• cable disconnected or broken • terminator off • power off at extended-local racks
• repair cable • replace or repair terminator • restore power to racks channel offline channel is not being used
Place channel online if needed
Ethernet Status Indicator Indicator
Color
Description
Probable Cause
Recommended Action
STAT
Solid red
Critical hardware fault
Controller requires internal repair
Contact your local Allen-Bradley representative
Blinking red
Hardware or software fault (detected and reported via a code)
Fault-code dependent Contact Allen-Bradley’s Global Technical Support (GTS)
Off
Ethernet interface is functioning Normal operation properly but it is not attached to an active Ethernet network
Attach the Controller to an active Ethernet network
Green
Ethernet channel 2 is functioning Normal operation properly and has detected that it is connected to an active Ethernet network
No action required
BATT PROG
PROC
R E M
FORCE
RUN
COMM
ENET
STAT
Publication 1785-UM012D-EN-P - July 2005
Page 354
F-6
Troubleshooting
BATT PROG
Ethernet Transmit LED
PROC
R E M
FORCE
RUN
COMM
The PLC-5 Ethernet interface contains an Ethernet Transmit LED that lights (green) briefly when the Ethernet port is transmitting a packet. It does not indicate whether or not the Ethernet port is receiving a packet.
ENET
TRANSMIT
Remote I/O System
Troubleshooting Guide for the 1771-ASB Series C and D Adapter Module
ACTIVE ADAPTER FAULT I/O RACK FAULT
Indicators
Description
Probable Cause
Recommended Action
Active Adapter I/O Fault Rack On
Off
Off
Normal indication; remote adapter is fully operational
Off
On
Off
On
Blink
Off
Module placement error I/O module in incorrect slot.
Place module in correct slot in chassis.
Blink in unison
Off
Incorrect starting I/O group number
Error in starting I/O group number or I/O rack address
Check switch settings.
On
On
On
Module not communicating
Incorrect transmission rate setting
Off
On
On
Module not communicating
Scan switch set for “all but last four slots” in 1/4 rack
Blink
Off
Off
Remote adapter not actively controlling I/O (scanner to adapter communication link is normal)(1)
Controller is in program or test mode Fault should be cleared by I/O scanner. Scanner is holding adapter module in fault mode
RAM memory fault, watchdog timeout Replace module.
LEDs sequence on/off from Module not top to bottom communicating
Publication 1785-UM012D-EN-P - July 2005
Another remote I/O adapter with the same address is on the link.
Reset scan switch setting.
Correct the address.
Page 355
Troubleshooting
Indicators Active
Description
Probable Cause
F-7
Recommended Action
Adapter I/O Fault Rack
Blink alternately
Off
Adapter module not Controller restart lockout switch on actively controlling I/O(2) chassis backplane switch assembly on(3) Adapter module in controller restart lockout mode (adapter to scanner link is normal)
Press reset button to clear lockout feature or cycle power; if after repeated attempts indicators are still blinking, check: • push button not wired properly to field wiring arm • wiring arm not connected to adapter module • adapter module was reset by process or/ scanner, then immediately faulted
(1)
If a fault occurs and the Controller is in the run mode but is actually operating in the dependent mode, the chassis fault response mode is selected by the last state switch on the chassis backplane.
(2)
The I/O chassis is in faulted mode as selected by the last state switch on the chassis backplane.
(3)
You must select the operating mode of the remote I/O adapter module as outlined in the publication furnished with the remote I/O scanner/distribution panel, remote I/O scanner-program interface module, or I/O scanner-message handling module. Pay close attention to the disable search mode in the 1771-SD, -SD2.
Publication 1785-UM012D-EN-P - July 2005
Page 356
F-8
Troubleshooting
Troubleshooting Guide for the 1771-ASB Series C and D Adapter Module (continued) Indicators Active
Adapter I/O Fault Rack
Off
Off
On
Description
Probable Cause
Recommended Action
I/O chassis fault. (1) No communication on link.
Problem exists between:
Cycle power to the chassis to clear a problem resulting from high noise.(2)
• adapter and module in chassis; the module will stay in fault mode until fault is corrected • shorted printed circuit board runs on backplane or I/O module
• Remove and replace all I/O modules one at a time • If problem does not clear, something is wrong in chassis or I/O module
Blink
Off
On
Communication on link. Possible shorted backplane
• Noise on backplane • Shorted circuit board runs • Faulty card in chassis
• Eliminate noise • Isolate noise • Add surge suppression • Replace chassis • Replace defective card in chassis
Blink
On
Off
Module identification line fault
Excessive noise on backplane
Verify power supply and chassis grounding.
Off
Off
Off
Module not communicating
Power supply fault
Check power supply, cable connections, and make sure adapter module is fully seated in chassis.
Wiring from scanner to adapter module disrupted
Correct cable and wiring defects
Scanner not configured properly
See publication 1772-2.18 for scanner configuration.
Check sequentially from the first module to One faulted chassis within a rack group address causing the last module to pinpoint fault; correct scanner/distribution panel to fault all any faults and proceed to the next chassis. chassis in rack group address (when in disable search mode) (1)
The I/O chassis is in faulted mode as selected by the last state switch on the chassis backplane.
(2)
Cycling power clears block-transfer request queue. All pending block transfers are lost. Your program must repeat the request for block transfers.
Publication 1785-UM012D-EN-P - July 2005
Page 357
Troubleshooting
F-9
Extended-Local I/O System Troubleshooting Guide for the 1771-ALX Adapter Module ACTIVE ADAPTER FAULT
I/O RACK FAULT
Indicators
Description
Probable Cause
Recommended Action
Active
Adapter I/O Fault Rack
On
Off
Off
Normal indication; remote adapter is fully operational
Off
On
Off
Local adapter fault (1)
Local adapter not operating; it will stay in fault mode until fault is corrected
Cycle power to the chassis to clear the adapter fault.(2) Replace adapter if fault does not clear.
Off
Off
On
I/O chassis fault 1
Problem exists between:
Cycle power to the chassis to clear a problem resulting from high noise.2
• adapter and module in chassis; the module will stay in fault mode until fault is corrected • shorted printed circuit board runs on backplane or I/O module
Blinking Off
Off
Outputs are reset
Controller is in program or test mode Local I/O Scanner is holding adapter module in fault mode
• remove and replace all I/O modules one at a time • replace adapter • If problem does not clear, something is wrong in chassis or I/O module
None Fault should be cleared by extended-local I/O scanner.
Blinking alternately Off
Adapter module not Controller restart lockout switch on 1 actively controlling I/O chassis backplane switch assembly Adapter module in on(3) controller restart lockout mode (adapter to scanner link is normal)
Press chassis reset button to clear lockout feature or cycle power; if after repeated attempts indicators are still blinking, check that adapter module was reset by controller/scanner, then immediately faulted.
Off
Off
Off
No power or no communication.
Check power supply, I/O cable and power supply cable connections, and make sure adapter module is fully seated in chassis.
On
Blinking
Off
Module placement error Incorrect placement of high-density in extended-local I/O modules chassis
Power supply fault
Verify addressing modes and switch settings.
(1)
Cycling power clears the block-transfer request queue. All pending block transfers are lost. Your program must repeat the request for block transfers from the chassis.
(2)
If a fault occurs and the controller is in the run mode but is actually operating in the dependent mode, the chassis fault response mode is selected by switch 1 (the last state switch) on the chassis backplane.
(3)
The I/O chassis is in faulted mode as selected by switch 1 (the last stare switch) on the chassis backplane.
Publication 1785-UM012D-EN-P - July 2005
Page 358
F-10
Troubleshooting
Unexpected Operation when Entering Run Mode
If unexpected operation occurs whenever your controller enters run mode, be sure to examine the prescan operation of the instructions in this section. These instructions execute differently during prescan than they do during a normal scan. The prescan function is an intermediate scan between the transition from program to run modes, during which all rungs are scanned as false. The prescan examines all ladder program files and instructions and initializes the data table based on the results of the program. For example, a subroutine that is called infrequently may contain a bad indirect address and generate a major fault. However, many normal program scans may occur before the major fault is actually generated. Prescan provides the opportunity for the controller to examine the program for errors such as this before transitioning to Run mode.
Instructions with Unique Prescan Operations Use the table below to track prescan operations that deviate from normal instruction operation. This Instruction:
Executes These Actions During Prescan:
ARD
If the EN bit is set and the DN and ER bits are cleared, then the control word is cleared. If either the DN or ER bit is set, then the EN bit is cleared and the DN bit is set.
ARL AWT AWA ACB ABL AHL BTR BTW CTU CTD
The CU/CD bit is set to prevent a false count when the first run-mode scan begins.
EOT
This instruction is skipped so all ladder instructions can be prescanned.
FFL
The EL bit is set to prevent a false load when the first run-mode scan begins.
LFL FFU LFU FND
Publication 1785-UM012D-EN-P - July 2005
All non-user configuration bits 15, 14, 13, 12, 10, and 9 are cleared (for both INT and BT file types).
The EU bit is set to prevent a false unload when the first run-mode scan begins. This instruction is skipped so all ladder instructions can be prescanned.
Page 359
Troubleshooting
F-11
This Instruction:
Executes These Actions During Prescan:
FOR
Ladder instructions within the FOR/NXT loop are prescanned.
MSG
If the SFC startover bit is cleared and the CO bit is cleared, then all non-user configuration bits 15, 14, 13, 12, 10, and 9 are cleared in both the INT and MG file types. The MG file type also clears bits 11, 7, 6, 5, 4, 2, 1, and 0.
ONS
The programmed bit address of the instruction is set to inhibit false triggering when the first run-mode scan begins.
OSF OSR
The programmed bit address of the instruction is cleared to inhibit false triggering when the first run-mode scan begins. The output bit is also cleared.
PID
For PD file type, the INI bit is cleared. INT file type clears status bits 8, 9, and 10 (deadband, upper, and lower output alarm). The error register from the previous scan is set to 32767, which indicates that the setpoint and ER bits from previous scans have not yet been initialized). The Integral Accumulator and Derivative Error bits are cleared.
SQL SQO
The EN bit is set to prevent a false increment of the table pointer when the first run-mode scan occurs.
TOF
The TT, TC, TE, and TO bits are cleared and the ACC = preset.
DTR (1)
The reference value is updated (regardless of the rung condition).
(1)
The DTR instruction operates in this manner during a normal scan as well.
Suggested Action To avoid unexpected operation that may result from these prescan activities, follow these guidelines: • Do not use indexed or indirect addressing with the instructions listed in the above table. • If you must use indexed or indirect addressing, use the first scan bit (S:1/15) to pre-initialize all of the other used variables. • If using indirect addressing with any ladder instructions, do not use the data variable holding the indirect address for multiple functions.