Enhanced and Ethernet PLC-5 Programmable Controllers User Manual: Appendix F - Troubleshooting

Pages 349 to 360 of 388, from Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1785-L20B and Allen-Bradley 1785-L40B

Page 349

Appendix

F

Troubleshooting

Using This Chapter For Information About Troubleshooting:

1

Go to Page:

PLC-5 controller

F-2

Remote I/O system

F-6

Extended-local I/O system

F-9

Unexpected PLC-5 controller operation when entering run mode

F-10

Publication 1785-UM012D-EN-P - July 2005

Page 350

F-2

Troubleshooting

PLC-5 Controller

BATT PROG R E M RUN

General Problems

Indicator

Color

Description

Probable Cause

Recommended Action

PROC

Green (steady)

Controller is in run mode and fully operational

Normal operation

No action required

Green (blinking)

Controller memory is being transferred to EEPROM

Normal operation

No action required

Red (blinking)

Major fault

• RSLogix 5 download in progress • Run-time error

During RSLogix 5 download, this is normal operation - wait for download to complete.

PROC FORCE COMM

If not during RSLogix 5 download: • Check major fault bit in status file (S:11) for error definition • Clear fault, correct problem, and return to run mode

Alternating Red and Green

Controller in FLASH-memory programming mode

Normal operation if controller's FLASH memory is being reprogrammed

No action required - allow flash update to complete

Red

Power cycle with problem battery

Battery is low, disconnected or not installed

Properly replace or install battery (see Chapter 1 for more information)

Fault with memory loss

New controller

Use programming software to clear and initialize memory

(steady) Red (steady)

Invalid ControlNet Verify that ControlNet address network address switch is not set to 0 Controller has failed internal diagnostics

Off

Publication 1785-UM012D-EN-P - July 2005

Controller is in program load or test mode or is not receiving power

Install battery (to preserve failure diagnostics), then power down, reseat controller and power up; then reload your program. If you are unable to reload your program, replace the controller. If you are able to reload your program and fault persists, contact Technical Support at 440.646.6800 to diagnose the problem. Check power supply and connections

Page 351

Troubleshooting

Indicator

Color

Description

Probable Cause

Recommended Action

FORCE

Amber (steady)

SFC and/or I/O forces enabled

Normal operation

No action required

Amber (blinking)

SFC and/or I/O forces present but not enabled

Off

SFC and/or I/O forces not present

Off

No transmission on channel 0

Normal operation if channel is not being used

Green (blinking)

Transmission on channel 0

Normal operation if channel is being used

COMM

F-3

Publication 1785-UM012D-EN-P - July 2005

Page 352

F-4

Troubleshooting

Controller Communication Channel Troubleshooting Indicator Color

Channel Mode

A or B

Remote I/O Scanner Active Remote I/O link, all adapter modules are present and not faulted

Green (steady)

Description

Probable Cause Recommended Action Normal operation No action required

Remote I/O Adapter Communicating with scanner DH+ Green (blinking rapidly or slowly)

Remote I/O Scanner At least one adapter is faulted or has failed

DH+ Red (steady)

Controller is transmitting or receiving on DH+ link • Power off at remote rack • Cable broken

• Restore power to the rack • Repair cable

Hardware error

Turn power off, then on

No other nodes on network

Remote I/O Scanner Hardware fault Remote I/O Adapter DH+

Check that the software configurations match the hardware set-up Replace the controller.

Red (blinking rapidly or slowly)

Remote I/O Scanner All adapters faulted

DH+ Off

Publication 1785-UM012D-EN-P - July 2005

• Cable not connected or broken • Power off at remote racks

Bad communication on DH+ Duplicate node detected

Remote I/O Scanner Channel offline Remote I/O Adapter DH+

Channel is not being used

• Repair cable

• Restore power to racks

Correct station address Place channel online if needed

Page 353

Troubleshooting

F-5

Extended-Local I/O Troubleshooting Indicator Color

Channel Mode

Description

2

Extended local I/O Scanner active extended-local I/O normal operation link, all adapter modules are present and not faulted no action required at least one adapter is faulted or has failed

• restore power to the rack green (steady)

PLC-5/40L and -5/60L processors only BATT PROG green (blinking rapidly or slowly)

PROC

R E M

Probable Cause Recommended Action

• power off at extended-local I/O rack • communication fault

FORCE

• restart adapters using the controller restart lockout pushbutton • repair cable

• cable broken

RUN

COMM red (steady)

red (blinking rapidly or slowly)

Extended local I/O Scanner off hardware fault hardware error

Turn power off, then on. Check that the software configurations match the hardware set-up. Replace the controller.

all adapters faulted

• cable disconnected or broken • terminator off • power off at extended-local racks

• repair cable • replace or repair terminator • restore power to racks channel offline channel is not being used

Place channel online if needed

Ethernet Status Indicator Indicator

Color

Description

Probable Cause

Recommended Action

STAT

Solid red

Critical hardware fault

Controller requires internal repair

Contact your local Allen-Bradley representative

Blinking red

Hardware or software fault (detected and reported via a code)

Fault-code dependent Contact Allen-Bradley’s Global Technical Support (GTS)

Off

Ethernet interface is functioning Normal operation properly but it is not attached to an active Ethernet network

Attach the Controller to an active Ethernet network

Green

Ethernet channel 2 is functioning Normal operation properly and has detected that it is connected to an active Ethernet network

No action required

BATT PROG

PROC

R E M

FORCE

RUN

COMM

ENET

STAT

Publication 1785-UM012D-EN-P - July 2005

Page 354

F-6

Troubleshooting

BATT PROG

Ethernet Transmit LED

PROC

R E M

FORCE

RUN

COMM

The PLC-5 Ethernet interface contains an Ethernet Transmit LED that lights (green) briefly when the Ethernet port is transmitting a packet. It does not indicate whether or not the Ethernet port is receiving a packet.

ENET

TRANSMIT

Remote I/O System

Troubleshooting Guide for the 1771-ASB Series C and D Adapter Module

ACTIVE ADAPTER FAULT I/O RACK FAULT

Indicators

Description

Probable Cause

Recommended Action

Active Adapter I/O Fault Rack On

Off

Off

Normal indication; remote adapter is fully operational

Off

On

Off

On

Blink

Off

Module placement error I/O module in incorrect slot.

Place module in correct slot in chassis.

Blink in unison

Off

Incorrect starting I/O group number

Error in starting I/O group number or I/O rack address

Check switch settings.

On

On

On

Module not communicating

Incorrect transmission rate setting

Off

On

On

Module not communicating

Scan switch set for “all but last four slots” in 1/4 rack

Blink

Off

Off

Remote adapter not actively controlling I/O (scanner to adapter communication link is normal)(1)

Controller is in program or test mode Fault should be cleared by I/O scanner. Scanner is holding adapter module in fault mode

RAM memory fault, watchdog timeout Replace module.

LEDs sequence on/off from Module not top to bottom communicating

Publication 1785-UM012D-EN-P - July 2005

Another remote I/O adapter with the same address is on the link.

Reset scan switch setting.

Correct the address.

Page 355

Troubleshooting

Indicators Active

Description

Probable Cause

F-7

Recommended Action

Adapter I/O Fault Rack

Blink alternately

Off

Adapter module not Controller restart lockout switch on actively controlling I/O(2) chassis backplane switch assembly on(3) Adapter module in controller restart lockout mode (adapter to scanner link is normal)

Press reset button to clear lockout feature or cycle power; if after repeated attempts indicators are still blinking, check: • push button not wired properly to field wiring arm • wiring arm not connected to adapter module • adapter module was reset by process or/ scanner, then immediately faulted

(1)

If a fault occurs and the Controller is in the run mode but is actually operating in the dependent mode, the chassis fault response mode is selected by the last state switch on the chassis backplane.

(2)

The I/O chassis is in faulted mode as selected by the last state switch on the chassis backplane.

(3)

You must select the operating mode of the remote I/O adapter module as outlined in the publication furnished with the remote I/O scanner/distribution panel, remote I/O scanner-program interface module, or I/O scanner-message handling module. Pay close attention to the disable search mode in the 1771-SD, -SD2.

Publication 1785-UM012D-EN-P - July 2005

Page 356

F-8

Troubleshooting

Troubleshooting Guide for the 1771-ASB Series C and D Adapter Module (continued) Indicators Active

Adapter I/O Fault Rack

Off

Off

On

Description

Probable Cause

Recommended Action

I/O chassis fault. (1) No communication on link.

Problem exists between:

Cycle power to the chassis to clear a problem resulting from high noise.(2)

• adapter and module in chassis; the module will stay in fault mode until fault is corrected • shorted printed circuit board runs on backplane or I/O module

• Remove and replace all I/O modules one at a time • If problem does not clear, something is wrong in chassis or I/O module

Blink

Off

On

Communication on link. Possible shorted backplane

• Noise on backplane • Shorted circuit board runs • Faulty card in chassis

• Eliminate noise • Isolate noise • Add surge suppression • Replace chassis • Replace defective card in chassis

Blink

On

Off

Module identification line fault

Excessive noise on backplane

Verify power supply and chassis grounding.

Off

Off

Off

Module not communicating

Power supply fault

Check power supply, cable connections, and make sure adapter module is fully seated in chassis.

Wiring from scanner to adapter module disrupted

Correct cable and wiring defects

Scanner not configured properly

See publication 1772-2.18 for scanner configuration.

Check sequentially from the first module to One faulted chassis within a rack group address causing the last module to pinpoint fault; correct scanner/distribution panel to fault all any faults and proceed to the next chassis. chassis in rack group address (when in disable search mode) (1)

The I/O chassis is in faulted mode as selected by the last state switch on the chassis backplane.

(2)

Cycling power clears block-transfer request queue. All pending block transfers are lost. Your program must repeat the request for block transfers.

Publication 1785-UM012D-EN-P - July 2005

Page 357

Troubleshooting

F-9

Extended-Local I/O System Troubleshooting Guide for the 1771-ALX Adapter Module ACTIVE ADAPTER FAULT

I/O RACK FAULT

Indicators

Description

Probable Cause

Recommended Action

Active

Adapter I/O Fault Rack

On

Off

Off

Normal indication; remote adapter is fully operational

Off

On

Off

Local adapter fault (1)

Local adapter not operating; it will stay in fault mode until fault is corrected

Cycle power to the chassis to clear the adapter fault.(2) Replace adapter if fault does not clear.

Off

Off

On

I/O chassis fault 1

Problem exists between:

Cycle power to the chassis to clear a problem resulting from high noise.2

• adapter and module in chassis; the module will stay in fault mode until fault is corrected • shorted printed circuit board runs on backplane or I/O module

Blinking Off

Off

Outputs are reset

Controller is in program or test mode Local I/O Scanner is holding adapter module in fault mode

• remove and replace all I/O modules one at a time • replace adapter • If problem does not clear, something is wrong in chassis or I/O module

None Fault should be cleared by extended-local I/O scanner.

Blinking alternately Off

Adapter module not Controller restart lockout switch on 1 actively controlling I/O chassis backplane switch assembly Adapter module in on(3) controller restart lockout mode (adapter to scanner link is normal)

Press chassis reset button to clear lockout feature or cycle power; if after repeated attempts indicators are still blinking, check that adapter module was reset by controller/scanner, then immediately faulted.

Off

Off

Off

No power or no communication.

Check power supply, I/O cable and power supply cable connections, and make sure adapter module is fully seated in chassis.

On

Blinking

Off

Module placement error Incorrect placement of high-density in extended-local I/O modules chassis

Power supply fault

Verify addressing modes and switch settings.

(1)

Cycling power clears the block-transfer request queue. All pending block transfers are lost. Your program must repeat the request for block transfers from the chassis.

(2)

If a fault occurs and the controller is in the run mode but is actually operating in the dependent mode, the chassis fault response mode is selected by switch 1 (the last state switch) on the chassis backplane.

(3)

The I/O chassis is in faulted mode as selected by switch 1 (the last stare switch) on the chassis backplane.

Publication 1785-UM012D-EN-P - July 2005

Page 358

F-10

Troubleshooting

Unexpected Operation when Entering Run Mode

If unexpected operation occurs whenever your controller enters run mode, be sure to examine the prescan operation of the instructions in this section. These instructions execute differently during prescan than they do during a normal scan. The prescan function is an intermediate scan between the transition from program to run modes, during which all rungs are scanned as false. The prescan examines all ladder program files and instructions and initializes the data table based on the results of the program. For example, a subroutine that is called infrequently may contain a bad indirect address and generate a major fault. However, many normal program scans may occur before the major fault is actually generated. Prescan provides the opportunity for the controller to examine the program for errors such as this before transitioning to Run mode.

Instructions with Unique Prescan Operations Use the table below to track prescan operations that deviate from normal instruction operation. This Instruction:

Executes These Actions During Prescan:

ARD

If the EN bit is set and the DN and ER bits are cleared, then the control word is cleared. If either the DN or ER bit is set, then the EN bit is cleared and the DN bit is set.

ARL AWT AWA ACB ABL AHL BTR BTW CTU CTD

The CU/CD bit is set to prevent a false count when the first run-mode scan begins.

EOT

This instruction is skipped so all ladder instructions can be prescanned.

FFL

The EL bit is set to prevent a false load when the first run-mode scan begins.

LFL FFU LFU FND

Publication 1785-UM012D-EN-P - July 2005

All non-user configuration bits 15, 14, 13, 12, 10, and 9 are cleared (for both INT and BT file types).

The EU bit is set to prevent a false unload when the first run-mode scan begins. This instruction is skipped so all ladder instructions can be prescanned.

Page 359

Troubleshooting

F-11

This Instruction:

Executes These Actions During Prescan:

FOR

Ladder instructions within the FOR/NXT loop are prescanned.

MSG

If the SFC startover bit is cleared and the CO bit is cleared, then all non-user configuration bits 15, 14, 13, 12, 10, and 9 are cleared in both the INT and MG file types. The MG file type also clears bits 11, 7, 6, 5, 4, 2, 1, and 0.

ONS

The programmed bit address of the instruction is set to inhibit false triggering when the first run-mode scan begins.

OSF OSR

The programmed bit address of the instruction is cleared to inhibit false triggering when the first run-mode scan begins. The output bit is also cleared.

PID

For PD file type, the INI bit is cleared. INT file type clears status bits 8, 9, and 10 (deadband, upper, and lower output alarm). The error register from the previous scan is set to 32767, which indicates that the setpoint and ER bits from previous scans have not yet been initialized). The Integral Accumulator and Derivative Error bits are cleared.

SQL SQO

The EN bit is set to prevent a false increment of the table pointer when the first run-mode scan occurs.

TOF

The TT, TC, TE, and TO bits are cleared and the ACC = preset.

DTR (1)

The reference value is updated (regardless of the rung condition).

(1)

The DTR instruction operates in this manner during a normal scan as well.

Suggested Action To avoid unexpected operation that may result from these prescan activities, follow these guidelines: • Do not use indexed or indirect addressing with the instructions listed in the above table. • If you must use indexed or indirect addressing, use the first scan bit (S:1/15) to pre-initialize all of the other used variables. • If using indirect addressing with any ladder instructions, do not use the data variable holding the indirect address for multiple functions.

Publication 1785-UM012D-EN-P - July 2005

Page 360

F-12

Troubleshooting

Notes

Publication 1785-UM012D-EN-P - July 2005