Enhanced and Ethernet PLC-5 Programmable Controllers User Manual: Chapter 2 - Selecting and Placing I/O
Pages 33 to 36 of 388, from Enhanced and Ethernet PLC-5 Programmable Controllers User Manual
The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1785-L20B and Allen-Bradley 1785-L40B
Page 33
Chapter
2
Selecting and Placing I/O
Using This Chapter For Information About Selecting I/O modules Selecting I/O module density Placing I/O modules in a chassis
Selecting I/O Modules
Go to Page 2-1 2-2 2-3
Select I/O modules to interface your PLC-5 controller with machines or processes that you determine while analyzing your plant operation. Use the following list and table as guidelines for selecting I/O modules and operator control interface(s). • How much I/O is required to control your process(es)? • Where will you concentrate I/O points for portions of an entire process when the entire process is distributed over a large physical area? • What type of I/O is required to control your process(es)? • What is the required voltage range for each I/O module? • What is the backplane current required for each I/O module? • What are the noise and distance limitations for each I/O module? • What isolation is required for each I/O module?
1
Publication 1785-UM012D-EN-P - July 2005
Page 34
2-2
Selecting and Placing I/O
Guidelines for Selecting I/O Modules
Choose this Type of I/O Module
For these Types of Field Devices or Operations (examples)
Discrete input module and block I/O module
Selector switches, pushbuttons, photoelectric eyes, limit switches, circuit breakers, proximity switches, level switches, motor starter contacts, relay contacts, thumbwheel switches
Input modules sense on/off or opened/closed signals. Discrete signals can be either ac or dc.
Discrete output module and block I/O module
Alarms, control relays, fans, lights, horns, valves, motor starter, or solenoids
Output module signals interface with on/off or opened/closed devices. Discrete signals can be either ac or dc.
Analog input module
Temperature transducers, pressure transducers, load cell transducers, humidity transducers, flow transducers, and potentiometers
Convert continuous analog signals into input values for the PLC controller.
Analog output module
Analog valves, actuators, chart recorders, electric motor drives, analog meters
Interpret PLC controller output to analog signals (generally through transducers) for field devices.
Specialty I/O modules
Encoders, flow meters, I/O communication, ASCII, RF type devices, weigh scales, bar-code readers, tag readers, display devices
Are generally used for specific applications such as position control, PID, and external device communication.
Selecting I/O Module Density
Explanation
The density of an I/O module is the number of controller input or output image-table bits to which it corresponds. A bidirectional module with 8 input bits and 8 output bits has a density of 8. I/O module density helps determine your I/O addressing scheme. See chapter 4 for more information about I/O addressing. Use these guidelines for selecting I/O module density: Choose this I/O Density If You 8-point I/O module • currently use 8-point modules • need integral, separately-fused outputs 16-point I/O module
• want to minimize cost per module • currently use 16-point modules
32-point I/O module
• need separately-fused outputs with a special wiring arm • currently use 32-point modules • want to minimize number of modules • want to minimize the space required for I/O chassis • want to minimize cost per I/O point
Publication 1785-UM012D-EN-P - July 2005
Page 35
Selecting and Placing I/O
Placing I/O Modules in a Chassis
Place I/O modules in a chassis depending on the electrical characteristics of the module. The placement is made left to right, with the left-most position being closest in the chassis to the PLC-5 controller or the I/O adapter module. The placement order is as follows: Priority:
Module placement priority: 1. block-transfer modules (all types) 2. dc input modules 3. dc output modules 4. ac input modules 5. ac output modules
2-3
P L C / A S B
1
1
2
2
3
Block Block dc dc Transfer Transfer input input
3 dc dc output output
4
4
5 ac input ac input ac ac output output lowV Place block-transfer modules according to these guidelines: Place as many modules as possible for which you need fast block-transfer times in your controller-resident local I/O chassis. Place modules in which block-transfer timing is not as critical in remote I/O chassis. Ac output modules should always be the furthest I/O modules away from any block-transfer modules in the same chassis.
5 empty highV Place input and output modules according to these guidelines: left to right lowest voltage to highest voltage For optimal speed using discrete I/O, use the following module-placement priority scheme: 1. controller chassis 2. extended-local I/O chassis 3. remote I/O chassis
Publication 1785-UM012D-EN-P - July 2005