Enhanced and Ethernet PLC-5 Programmable Controllers User Manual: Chapter 3 - Placing System Hardware

Pages 37 to 44 of 388, from Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1785-L20B and Allen-Bradley 1785-L40B

Page 37

Chapter

3

Placing System Hardware

Using This Chapter For Information About Determining the proper environment Protecting your controller Avoiding electrostatic damage Laying out your cable raceway Laying out your backpanel spacing Grounding your system

Determining the Proper Environment

Go to Page 3-1 3-3 3-3 3-4 3-5 3-6

Place the controller in an environment with conditions that fall within these guidelines:

Environmental Condition Operating temperature Storage temperature Relative humidity

Acceptable Range 0 to 60° C (32 to 140° F) -40 to 85° C (-40 to 185° F) 5 to 95% (without condensation)

Separate your programmable controller system from other equipment and plant walls to allow for convection cooling. Convection cooling draws a vertical column of air upward over the controller. This cooling air must not exceed 60° C (140° F) at any point immediately below the controller. If the air temperature exceeds 60° C, install fans that bring in filtered air or recirculate internal air inside the enclosure, or install air-conditioning/heat-exchanger units. To allow for proper convection cooling in enclosures containing a controller-resident chassis and remote I/O chassis, follow these guidelines.

1

Publication 1785-UM012D-EN-P - July 2005

Page 38

3-2

Placing System Hardware

Minimum spacing requirements for a controller-resident chassis: Mount the I/O chassis horizontally. Allow 153 mm (6 in) above and below the chassis. Allow 102 mm (4 in) on the sides of each chassis. Allow 51 mm (2 in) vertically and horizontally between any chassis and the wiring duct or terminal strips. Leave any excess space at the top of the enclosure, where the temperature is the highest.

Area reserved for disconnect, transformer, control relays, motor starters, or other user devices.

153mm (6")

51mm (2")

102mm (4") 102mm (4")

153mm (6")

51mm(2")

Wiring Duct

13081

Minimum spacing requirements for a remote I/O and extended-local I/O chassis: Mount the I/O chassis horizontally. Allow 153 mm (6 in) above and below all chassis. When you use more than one chassis in the same area, allow 152.4 mm (6 in) between each chassis. Allow 102 mm (4 in) on the sides of each chassis. When you use more than one chassis in the same area, allow 101.6 mm (4 in) between each chassis. Allow 51 mm (2 in) vertically and horizontally between any chassis and the wiring duct or terminal strips. Leave any excess space at the top of the enclosure, where the temperature is the highest.

Area reserved for disconnect, transformer, control relays, motor starters, or other user devices.

102mm (4")

153mm (6")

51mm (2") 153mm (6")

Wiring Duct 51mm (2")

102mm (4")

102mm (4")

153mm (6")

Wiring Duct

18749

Publication 1785-UM012D-EN-P - July 2005

Page 39

Placing System Hardware

Protecting Your Controller

3-3

You provide the enclosure for your controller system. This enclosure protects your controller system from atmospheric contaminants such as oil, moisture, dust, corrosive vapors, or other harmful airborne substances. To help guard against electromagnetic interference (EMI) and radio frequency interference (RFI), we recommend a steel enclosure. Mount the enclosure in a position where you can fully open the doors. You need easy access to controller wiring and related components so that troubleshooting is convenient. When you choose the enclosure size, allow extra space for transformers, fusing, disconnect switch, master control relay, and terminal strips.

Preventing Electrostatic Discharge ATTENTION

Under some conditions, electrostatic discharge can degrade performance or damage the controller. Read and observe the following precautions to guard against electrostatic damage.ESD protection • Wear an approved wrist strap grounding device when handling the controller. • Touch a grounded object to discharge yourself before handling the controller. • Do not touch the backplane connector or connector pins.

Publication 1785-UM012D-EN-P - July 2005

Page 40

3-4

Placing System Hardware

Laying Out Your Cable Raceway

The raceway layout of a system reflects where the different types of I/O modules are placed in I/O chassis. Therefore, you should determine I/O-module placement prior to any layout and routing of wires. When planning your I/O-module placement, however, segregate the modules based on the conductor categories published for each I/O module so that you can follow these guidelines. These guidelines coincide with the guidelines for “the installation of electrical equipment to minimize electrical noise inputs to controllers from external sources” in IEEE standard 518-1982. To plan a raceway layout, do the following: • categorize conductor cables • route conductor cables

Categorize Conductors Segregate all wires and cables into categories as described in the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. See the installation data for each I/O module that you are using for information about its classification.

Route Conductors To guard against coupling noise from one conductor to another, follow the general guidelines for routing cables described in the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. You should follow the safe grounding and wiring practices called out in the National Electrical Code (NEC, published by the National Fire Protection Association, in Quincy, Massachusetts), and local electrical codes.

Publication 1785-UM012D-EN-P - July 2005

Page 41

Placing System Hardware

3-5

Use 6.35 mm (0.25 inch) mounting bolts to attach the I/O chassis to the enclosure backpanel.

Laying Out Your Backpanel Spacing

Chassis Dimensions (Series B)

1771-A1B 1771-A2B 1771-A3B1 1771-A4B

591mm (23.25")

16-slot 1771 464mm (18.25")

337mm (13.25")

193mm (7.60")

Side

12-slot 8-slot

210mm (8.25")

315mm (12.41")

4-slot

254mm (10")

Power C onnector

171mm (6.75")

483mm (19.01") 229mm (9.01")

610mm (24.01")

16-slot 1771-A4B 12-slot 1771-A3B1

356mm (14.01")

8-slot 1771-A2B 4-slot 1771-A1B

1771-A3B 217mm 1 (8.54")

465mm (18.31")

484mm (19")

9mm (.34")

26mm (1.02") 178mm (7") Side

339mm (13.53")

Front

130mm (5.10") 12450-I

1 Total maximum depth dimension per installation will be dependent upon module wiring and connectors.

Publication 1785-UM012D-EN-P - July 2005

Page 42

3-6

Placing System Hardware

I/O Chassis and External Power Supply Dimensions

U se .25" dia mounting bolts (4 places)

315mm (12.41")

16-slot

591mm (23.25") 337mm (13.25")

464mm (18.25")

12-slot

210mm (8.25")

4-slot

External Power Supply

91mm (3.6")

254mm (10")

483mm (19.01") 229mm (9.01")

610mm (24.01")

Publication 1785-UM012D-EN-P - July 2005

16-slot 1771-A4B 12-slot 1771-A3B1

356mm (14.01")

Clearance depth is 204mm (8") for 8 I/O connection points per module.

Grounding Your System

8-slot

8-slot 1771-A2B 4-slot 1771-A1B 12451-I

For more information on proper grounding guidelines, see the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Page 43

Placing System Hardware

3-7

Recommended Grounding Configuration for Remote I/O Systems Enclosure Grounding Electrode Conductor Ground Bus To Grounding Electrode System I/O Chassis Wall

Ground Lug

Nut

Star Washer Ground Lug

15561

Required Grounding Configuration for Extended-Local I/O Systems

Enclosure

Enclosure

Ground Bus

Ground Bus

To Grounding Electrode System (single point only)

Extended-Local I/O Cables

I/O Chassis Wall I/O Chassis Ground Stud Ground Lug Nut Star Washer Ground Lug 18585

Publication 1785-UM012D-EN-P - July 2005

Page 44

3-8

Placing System Hardware

Notes

Publication 1785-UM012D-EN-P - July 2005