For the Allen-Bradley 1785-L20B and Allen-Bradley 1785-L40B
Page 37
Chapter
3
Placing System Hardware
Using This Chapter For Information About Determining the proper environment Protecting your controller Avoiding electrostatic damage Laying out your cable raceway Laying out your backpanel spacing Grounding your system
Determining the Proper Environment
Go to Page 3-1 3-3 3-3 3-4 3-5 3-6
Place the controller in an environment with conditions that fall within these guidelines:
Environmental Condition Operating temperature Storage temperature Relative humidity
Acceptable Range 0 to 60° C (32 to 140° F) -40 to 85° C (-40 to 185° F) 5 to 95% (without condensation)
Separate your programmable controller system from other equipment and plant walls to allow for convection cooling. Convection cooling draws a vertical column of air upward over the controller. This cooling air must not exceed 60° C (140° F) at any point immediately below the controller. If the air temperature exceeds 60° C, install fans that bring in filtered air or recirculate internal air inside the enclosure, or install air-conditioning/heat-exchanger units. To allow for proper convection cooling in enclosures containing a controller-resident chassis and remote I/O chassis, follow these guidelines.
1
Publication 1785-UM012D-EN-P - July 2005
Page 38
3-2
Placing System Hardware
Minimum spacing requirements for a controller-resident chassis: Mount the I/O chassis horizontally. Allow 153 mm (6 in) above and below the chassis. Allow 102 mm (4 in) on the sides of each chassis. Allow 51 mm (2 in) vertically and horizontally between any chassis and the wiring duct or terminal strips. Leave any excess space at the top of the enclosure, where the temperature is the highest.
Area reserved for disconnect, transformer, control relays, motor starters, or other user devices.
153mm (6")
51mm (2")
102mm (4") 102mm (4")
153mm (6")
51mm(2")
Wiring Duct
13081
Minimum spacing requirements for a remote I/O and extended-local I/O chassis: Mount the I/O chassis horizontally. Allow 153 mm (6 in) above and below all chassis. When you use more than one chassis in the same area, allow 152.4 mm (6 in) between each chassis. Allow 102 mm (4 in) on the sides of each chassis. When you use more than one chassis in the same area, allow 101.6 mm (4 in) between each chassis. Allow 51 mm (2 in) vertically and horizontally between any chassis and the wiring duct or terminal strips. Leave any excess space at the top of the enclosure, where the temperature is the highest.
Area reserved for disconnect, transformer, control relays, motor starters, or other user devices.
102mm (4")
153mm (6")
51mm (2") 153mm (6")
Wiring Duct 51mm (2")
102mm (4")
102mm (4")
153mm (6")
Wiring Duct
18749
Publication 1785-UM012D-EN-P - July 2005
Page 39
Placing System Hardware
Protecting Your Controller
3-3
You provide the enclosure for your controller system. This enclosure protects your controller system from atmospheric contaminants such as oil, moisture, dust, corrosive vapors, or other harmful airborne substances. To help guard against electromagnetic interference (EMI) and radio frequency interference (RFI), we recommend a steel enclosure. Mount the enclosure in a position where you can fully open the doors. You need easy access to controller wiring and related components so that troubleshooting is convenient. When you choose the enclosure size, allow extra space for transformers, fusing, disconnect switch, master control relay, and terminal strips.
Preventing Electrostatic Discharge ATTENTION
Under some conditions, electrostatic discharge can degrade performance or damage the controller. Read and observe the following precautions to guard against electrostatic damage.ESD protection • Wear an approved wrist strap grounding device when handling the controller. • Touch a grounded object to discharge yourself before handling the controller. • Do not touch the backplane connector or connector pins.
Publication 1785-UM012D-EN-P - July 2005
Page 40
3-4
Placing System Hardware
Laying Out Your Cable Raceway
The raceway layout of a system reflects where the different types of I/O modules are placed in I/O chassis. Therefore, you should determine I/O-module placement prior to any layout and routing of wires. When planning your I/O-module placement, however, segregate the modules based on the conductor categories published for each I/O module so that you can follow these guidelines. These guidelines coincide with the guidelines for “the installation of electrical equipment to minimize electrical noise inputs to controllers from external sources” in IEEE standard 518-1982. To plan a raceway layout, do the following: • categorize conductor cables • route conductor cables
Categorize Conductors Segregate all wires and cables into categories as described in the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. See the installation data for each I/O module that you are using for information about its classification.
Route Conductors To guard against coupling noise from one conductor to another, follow the general guidelines for routing cables described in the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. You should follow the safe grounding and wiring practices called out in the National Electrical Code (NEC, published by the National Fire Protection Association, in Quincy, Massachusetts), and local electrical codes.
Publication 1785-UM012D-EN-P - July 2005
Page 41
Placing System Hardware
3-5
Use 6.35 mm (0.25 inch) mounting bolts to attach the I/O chassis to the enclosure backpanel.
Laying Out Your Backpanel Spacing
Chassis Dimensions (Series B)
1771-A1B 1771-A2B 1771-A3B1 1771-A4B
591mm (23.25")
16-slot 1771 464mm (18.25")
337mm (13.25")
193mm (7.60")
Side
12-slot 8-slot
210mm (8.25")
315mm (12.41")
4-slot
254mm (10")
Power C onnector
171mm (6.75")
483mm (19.01") 229mm (9.01")
610mm (24.01")
16-slot 1771-A4B 12-slot 1771-A3B1
356mm (14.01")
8-slot 1771-A2B 4-slot 1771-A1B
1771-A3B 217mm 1 (8.54")
465mm (18.31")
484mm (19")
9mm (.34")
26mm (1.02") 178mm (7") Side
339mm (13.53")
Front
130mm (5.10") 12450-I
1 Total maximum depth dimension per installation will be dependent upon module wiring and connectors.
Publication 1785-UM012D-EN-P - July 2005
Page 42
3-6
Placing System Hardware
I/O Chassis and External Power Supply Dimensions
U se .25" dia mounting bolts (4 places)
315mm (12.41")
16-slot
591mm (23.25") 337mm (13.25")
464mm (18.25")
12-slot
210mm (8.25")
4-slot
External Power Supply
91mm (3.6")
254mm (10")
483mm (19.01") 229mm (9.01")
610mm (24.01")
Publication 1785-UM012D-EN-P - July 2005
16-slot 1771-A4B 12-slot 1771-A3B1
356mm (14.01")
Clearance depth is 204mm (8") for 8 I/O connection points per module.
Grounding Your System
8-slot
8-slot 1771-A2B 4-slot 1771-A1B 12451-I
For more information on proper grounding guidelines, see the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Page 43
Placing System Hardware
3-7
Recommended Grounding Configuration for Remote I/O Systems Enclosure Grounding Electrode Conductor Ground Bus To Grounding Electrode System I/O Chassis Wall
Ground Lug
Nut
Star Washer Ground Lug
15561
Required Grounding Configuration for Extended-Local I/O Systems
Enclosure
Enclosure
Ground Bus
Ground Bus
To Grounding Electrode System (single point only)
Extended-Local I/O Cables
I/O Chassis Wall I/O Chassis Ground Stud Ground Lug Nut Star Washer Ground Lug 18585
Publication 1785-UM012D-EN-P - July 2005
Page 44
3-8
Placing System Hardware
Notes
Publication 1785-UM012D-EN-P - July 2005