The text of a manual · part 2 of 4
ControlNet-to-DeviceNet Linking Device Installation Instructions, Catalog Number 1788-CN2DN, pages 9 to 16
Pages 9 to 16 of 32
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1788-CN2DN
Page 9
ControlNet-to-DeviceNet Linking Device 9 3. Clip each of the end anchors onto the DIN rail next to the CN2DN device. End Anchor onto DIN Rail
DIN Rail Clip On
End Anchors Next to Device
Grounded DIN Rail
Slide the Anchor Against the CN2DN Device
Tighten the Clamping Screws
4. Slide each anchor against the device and tighten the screws on the front of the end anchor. 5. If you are mounting your CN2DN device in a high-vibration area, insert screws (not included) into the holes of the mounting tabs and tighten so that the screws are firmly anchored into the panel behind the device. Mount Tabs (optional use) Ground Connection (optional). For use if DIN rail or panel is not grounded. If used, this tab must be properly connected to the earth ground.
Mount Tabs (optional use)
You have completed mounting your CN2DN device on a DIN rail.
Rockwell Automation Publication 1788-IN052E-EN-P - December 2014
Page 10
10 ControlNet-to-DeviceNet Linking Device
Mount the CN2DN Device on a Panel or Other Fixture IMPORTANT
If mounting the CN2DN device to a panel, ensure that the panel is conductive metal and properly grounded. Paint or other coatings should be sanded from the panel to ensure the CN2DN device makes sufficient conductive contact with the panel.
To mount the CN2DN device on a panel or other suitable fixture, insert five screws (not included) through the module’s mounting tabs and into the panel or fixture behind the module. Use screws long enough to penetrate the panel or fixture for a secure mount.
Wire a Power Supply to the CN2DN Device ATTENTION: To comply with the CE Low Voltage Directive (LVD), this equipment and DeviceNet must be powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV). To comply with UL restrictions, DeviceNet must be powered from a source compliant with the following: Class 2 or Limited Voltage/Current.
ATTENTION: The 24V DC power connection is not to exceed 10 m (32.8 ft).
WARNING: Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the rated voltage when applied in Zone 2 environments.
The CN2DN device requires 18...30V dc input power provided by a power supply that is separate from the DeviceNet network power supply.
Rockwell Automation Publication 1788-IN052E-EN-P - December 2014
Page 11
ControlNet-to-DeviceNet Linking Device 11 Complete these steps to wire the power supply to the CN2DN linking device. 1. Disconnect power to the power supply. 2. Locate the orange power connector. Power Connector, Top Power Connector
+ - + -
+ -
Daisy Chain to Device Wiring Terminals (optional)
Power Supply Wiring Terminals
3. Loosen the two left-most terminal screws of the power connector. 4. Insert the bare power supply wire ends into the left-side terminals of the power supply connector using the diagram as a guide. IMPORTANT
Do not connect more than two wires to any terminal.
5. Tighten the two left terminal screws using 0.6 Nm (7 lbin) torque. IMPORTANT
You must insert the power supply connector into the CN2DN device for power to reach any devices connected to one another from the CN2DN power supply connector, such as in a linear or ring topology.
6. If you connect another device to the power supply connector of the CN2DN device, loosen the two terminal screws on the right side of the connector. 7. Insert the bare device power wire ends into the two right terminals using the diagram as a reference. 8. Tighten the two right terminal screws using 0.6 Nm (7 lbin) torque. 9. Insert the power supply connector into the power supply connector port. 10. Reapply power to the DC power supply. The LED indicators on the right side of the CN2DN device will flash red to indicate power has been connected. You have completed wiring the power supply to the CN2DN device.
Rockwell Automation Publication 1788-IN052E-EN-P - December 2014
Page 12
12 ControlNet-to-DeviceNet Linking Device
Set the Node Addresses and Communication Rate Complete the following steps to set the node addresses using the switches on the front of the CN2DN device.
CN2DN Device Switches DeviceNet Address Switches
DeviceNet Baud Rate Switch
ControlNet Address Switches
1. To set the DeviceNet node address, use a small flat-head screwdriver to turn the arrows of the switches towards the desired node numbers. DeviceNet switches shown set to node 14. 4
2
4
2
0
0 6
8
6
8
MSD
LSD
2. To set the DeviceNet communication rate, turn the DeviceNet baud rate switch to the communication rate your DeviceNet network is configured to, for example 125 K, 250 K, or 500 K. 3. To set the ControlNet node address, use a small screwdriver to turn the arrows of the switches towards the desired node numbers.
ControlNet switches shown set to node 26. 4
2 0
2
4
0
PGM
6
MSD
8
6
LSD
You have completed setting the ControlNet and DeviceNet node addresses and communication rate.
Rockwell Automation Publication 1788-IN052E-EN-P - December 2014
Page 13
ControlNet-to-DeviceNet Linking Device 13
Connect the CN2DN Device to a ControlNet Network Complete the following steps to connect your CN2DN linking device to the ControlNet network. WARNING: If you connect or disconnect the communications cables with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. 1. Attach the BNC connector of the ControlNet cable to ControlNet port A.
Attach the BNC Connector of the ControlNet tap to ControlNet port A.
Main ControlNet Network Cable
IMPORTANT
If using redundant cabling, attach the BNC connector of the ControlNet tap to ControlNet port B. Redundant ControlNet Network Cable (Optional) Main ControlNet Network Cable
Do not connect more than one ControlNet network to the CN2DN device at a time. Connecting the CN2DN device to two networks at one time will cause erratic behavior of the CN2DN device.
2. If you are connecting to redundant media, attach the BNC connector of the other ControlNet cable to ControlNet port B. The CN2DN linking device is now connected to the ControlNet network.
Rockwell Automation Publication 1788-IN052E-EN-P - December 2014
Page 14
14 ControlNet-to-DeviceNet Linking Device
Connect the CN2DN Device to a DeviceNet Network WARNING: If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Complete the following steps to connect your CN2DN device to a DeviceNet network using the 10-pin linear connector included with the CN2DN device. You may also use the following DeviceNet connectors not included with the device:
• 5-pin linear connector (1799-DNETSCON or 1799-DNETCON) • 5-pin linear to micro connector (1799-DNC5MMS) Consult the DeviceNet Media Design and Installation Guide, publication DNET-UM072, for more information about using the connectors not included with the 1788-CN2DN linking device. 1. Strip 65 mm (2.6 in.) to 75 mm (2.96 in.) of the outer jacket from the end of the DeviceNet cable, leaving no more than 6.4 mm (0.25 in.) of the braided shield exposed. Braided Shield 6.4 mm (0.25 in.) Jacket
65 mm (2.6 in.)
2. Wrap the end of the cable with 38 mm (1.5 in.) of shrink wrap, covering part of the exposed conductors and part of the trunk line insulation. Jacket
38 mm (1.5 in.)
Shrink Wrap
41841
3. Strip 8.1 mm (0.32 in.) of the insulation from the end of each of the colored insulated conductors. Jacket
Shrink Wrap
8.1 mm (0.32 in.) Rockwell Automation Publication 1788-IN052E-EN-P - December 2014
41842
Page 15
ControlNet-to-DeviceNet Linking Device 15 4. Insert each colored conductor into the matching color-coded terminal cavity of the open-style connector. 5. If the CN2DN device is the first or last node on the DeviceNet network, insert an end of a 121resistor into the blue and white terminal cavities of the DeviceNet port connector. The resistor should bridge the blue and white terminal cavities. 121 Resistor
Black
Red White
Blue
41827
Bare or Shield
6. Tighten all of the terminal screws using 0.6 Nm (7 lb-in) torque. You have completed connecting to the DeviceNet network.
Uninstall the CN2DN Linking Device Complete the following steps to uninstall the CN2DN linking device. 1. Remove power from the CN2DN device. 2. Disconnect the power, DeviceNet, and ControlNet connectors. 3. If end anchors are in place, remove by loosening the screws and unclipping the anchor from the DIN rail.
Rockwell Automation Publication 1788-IN052E-EN-P - December 2014
Page 16
16 ControlNet-to-DeviceNet Linking Device 4. To remove the CN2DN linking device from the DIN rail, pull down on the two latches at the bottom of the device while pulling the CN2DN device away from the DIN rail.
Pull down on DIN rail latches.
If needed, insert a flat-head screwdriver between the DIN rail latch and the tab that locks the latch into place to remove the device.
Interpret the LED Indicators Use the LED indicators on the CN2DN linking device to monitor the following:
• • • •
Module Status Linking Activity Status DeviceNet Network Status ControlNet Network Status
CN2DN Device LED Indicators
DeviceNet Network Status Indicators Module Status and Linking Activity Status Indicators
ControlNet Status Indicators
Rockwell Automation Publication 1788-IN052E-EN-P - December 2014