Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of ControlNet-to-DeviceNet Linking Device Installation Instructions, Catalog Number 1788-CN2DN

Manual · Allen-Bradley

ControlNet-to-DeviceNet Linking Device Installation Instructions, Catalog Number 1788-CN2DN

Manual32 pagesPDF 1.2 MB

Installation instructions for the Allen-Bradley 1788-CN2DN ControlNet-to-DeviceNet linking device: mounting, power, addressing and LEDs.

Download the PDF1.2 MB

Covers · 1 model

The models it covers

Summary

What is in it

Installation instructions for the Allen-Bradley 1788-CN2DN ControlNet-to-DeviceNet linking device. They list the parts included and the required system components, then cover mounting on a DIN rail or panel, wiring the power supply, setting the ControlNet and DeviceNet node addresses and the DeviceNet communication rate, connecting to both networks, uninstalling, reading the LED indicators, and troubleshooting the DeviceNet and ControlNet networks with scanner status codes and controller status tags.

Its parts

  1. About the Linking Device
  2. Install the CN2DN Device
  3. Set the Node Addresses and Communication Rate
  4. Connect the CN2DN Device to a ControlNet Network
  5. Connect the CN2DN Device to a DeviceNet Network
  6. Uninstall the CN2DN Linking Device
  7. Interpret the LED Indicators
  8. Troubleshoot the DeviceNet Network
  9. Troubleshoot the ControlNet Network
  10. Additional Resources

From the manual

Key facts from this manual

Each line names its page in the PDF.

Installation instructions (publication 1788-IN052E-EN-P, December 2014) for the Allen-Bradley 1788-CN2DN ControlNet-to-DeviceNet linking device. They show how to mount and power it, set its node addresses and DeviceNet rate, and connect it to both networks. They also explain its LED indicators and how to troubleshoot DeviceNet with scanner status codes and RSLogix5000 controller tags.

Read for this summary: pages 1 and 5 to 31 of 32.

Function
Linking device between a ControlNet network and a DeviceNet network p. 1, 17
Power
18...30V dc from a 24V DC supply separate from the DeviceNet network supply; power connection no longer than 10 m (32.8 ft) p. 6, 10
ControlNet ports
BNC ports A and B; port B for optional redundant cabling p. 5, 13
DeviceNet connection
10-pin linear connector included; 5-pin linear (1799-DNETSCON or 1799-DNETCON) or 5-pin linear to micro (1799-DNC5MMS) also usable p. 14
Switches
DeviceNet and ControlNet node address switches; DeviceNet baud rate switch set to the network rate, for example 125 K, 250 K or 500 K p. 5, 12
Mounting
Grounded zinc-plated yellow-chromate steel DIN rail with end anchors, or a grounded metal panel with five screws p. 8, 9, 10
Included parts
Power input connector, DeviceNet 10-pin linear connector, five 121 resistors, two end anchors p. 5
DeviceNet termination
As first or last DeviceNet node, a 121 resistor bridges the blue and white terminals p. 15
Terminal torque
0.6 Nm (7 lbin) on power and DeviceNet terminal screws p. 11, 15
Configuration software
RSNetworx p. 17
LED indicators
Module Status, Linking Activity, DNet Network Status, DNet I/O Status, CNet A and CNet B p. 16, 18, 19
ControlNet LED faults
CNet A and CNet B both red steady: no ControlNet network found; both red alternating: incorrect ControlNet node configuration p. 18
DeviceNet LED faults
DNet Network Status red steady: communication error (bus off); red flashing: one or more connections timed out p. 19
Firmware upgrade state
Linking Activity LED flashing red and green: running boot code only, used for FLASH upgrades p. 17

What this manual walks you through

  • Mounting the linking device on a DIN rail or panel p. 8, 9, 10
  • Wiring the power supply, including daisy-chaining power to another device p. 10, 11
  • Setting the DeviceNet and ControlNet node addresses and the DeviceNet rate p. 12
  • Connecting to a ControlNet network, with optional redundant media p. 13
  • Preparing DeviceNet cable and wiring the DeviceNet connector p. 14, 15
  • Removing the linking device p. 15, 16
  • Reading the module, linking, DeviceNet and ControlNet LED indicators p. 16, 17, 18, 19
  • Interpreting DeviceNet scanner status codes and their fixes p. 20, 21, 22, 23
  • Troubleshooting DeviceNet with controller status tags in RSLogix5000 p. 24, 25, 26, 27, 28, 29
  • Where to look when troubleshooting the ControlNet network p. 30

Good to know

  • The network access port (NAP) is for temporary local programming only, not a permanent connection. p. 5
  • Connecting two ControlNet networks to the device at once causes erratic behavior. p. 13
  • DeviceNet status codes show only on the DeviceNet scanner module, not on the 1788-CN2DN. p. 20
  • The 24V DC power connection must not exceed 10 m (32.8 ft). p. 10
  • Aluminum or plastic DIN rail can cause improper or intermittent grounding. p. 8

Questions this manual answers

What power supply does the 1788-CN2DN need?

18...30V dc input from a power supply separate from the DeviceNet network power supply, with the connection no longer than 10 m. p. 10

How do I set the DeviceNet baud rate on the 1788-CN2DN?

Turn the DeviceNet baud rate switch on the front to the rate the DeviceNet network uses, such as 125 K, 250 K or 500 K. p. 12

What software configures the 1788-CN2DN?

RSNetworx software. p. 17

What does DeviceNet status code 91 mean?

A bus-off condition, likely from cable or signal errors; cycle power, check that all devices share one baud rate, and check cabling and noise sources. p. 23

What does a steady red CNet A and CNet B light mean on the 1788-CN2DN?

No ControlNet network was found. p. 18

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. ControlNet-to-DeviceNet Linking Device Installation Instructions1
    1. Important User Information2
    2. About the Linking Device5
    3. Install the CN2DN Device6
    4. Set the Node Addresses and Communication Rate12
    5. Connect the CN2DN Device to a ControlNet Network13
    6. Connect the CN2DN Device to a DeviceNet Network14
    7. Uninstall the CN2DN Linking Device15
    8. Interpret the LED Indicators16
    9. Troubleshoot the DeviceNet Network20
    10. Troubleshoot the ControlNet Network30
    11. Additional Resources30
  2. Back Cover32

From the PDF’s own bookmarks.

The whole text · 4 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8
  2. Pages 9 to 169-16
  3. Pages 17 to 2417-24
  4. Pages 25 to 3225-32

The file

Revision and size

Part no.1788-IN052E-EN-P
RevisionDecember 2014
PublisherRockwell Automation
Pages32
PDF1.2 MB
TextText from the PDF itself.
1788-IN052E-EN-P

The first pages · 3 of 32

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 32
Page 2
Page 2of 32
Page 3
Page 3of 32